Parameter Setup
4.4 GRoUP 1 PARAMeteR Set UP: CHARGe CURVe
Please refer to Parameters under Group 1 at Fig 4.1. Details of Parameter set up are given below:
tABLe 4.4. GRoUP 1 PARAMeteR Set UP: CHARGe CURVe
Screen
no. for
Group
1 (Fig
4.1)
Parameter
Programming Range
Default
eVo-
2212e
eVo-
3012e
eVo-
2224e
eVo-
4024e
eVo-
2212e
eVo-
3012e
eVo-
2224e
eVo-
4024e
1
“BULK CURRent”
(Bulk Charge Current
“Io”)
0 – 100A 0 – 130A 0 – 70A 0 – 110A
40A
2
“ABSoRP VoLtAGe”
(Absorption Voltage)
13.5V – 16.0V
27.0V – 32.0V
14.4V
28.8V
3
“eQUALiZe VoLtAGe”
(Equalization Voltage)
14.0V – 16.0V
28.0V – 32.0V
14.4V
28.8V
4
“FLoAtinG VoLtAGe"
(Float Voltage)
13.0V – 15.0V
26.0V – 30.0V
13.5V
27.0V
5
“CoMPenSAte”
(Temperature
Compensation)
-3mV to -5mV /°C/Cell
-4mV /°C/Cell
6
“BAtt oVeR VoLt”
(Battery Over Voltage
Shut Down)
14.0V – 17.0V
28.0V – 35.0V
16.0V
32.0V
7
“ReSet VoLtAGe”
("Battery Low
Voltage!") Reset
12.0V – 17.0V
24.0V – 35.0V
14.0V
28.0V
8
“LoW VoLt ALARM”
(Battery Low Voltage
Alarm)
9.5V – 12.5V
19.0V – 25.0V
11.0V
22.0V
9
“BAtt LoW VoLtAGe”
(Battery Low Voltage
Shut Down)
9.1V – 12.0V
18.1V – 24.0V
10.5V
21.0V
10
“LV DeteCt tiMe”
(Detect Time to
Qualify as "Battery
Low Voltage" Shut
Down Condition)
0-600 sec
10 sec
11
“LV CUt oFF tiMe”
(Time in pre Low Volt-
age Shut Down Condi-
tion (No AC output)
before complete shut
down is activated)
0-7200 sec
1200 sec