6.3.3 Setting menu
15
Display
Menu Level 1
Menu Level 2
Description
NET P P SET
02.0 bar
02.0 bar
Display in STANDARD mode.
F PREF PRES
Q
50 02.0 02.0 1
Display in SERVICE mode.
MENU
SETTINGS
LANGUAGE
ENGLISH
LANGUAGE
Language setting.
I MAX PUMP
OFF
I MAX PUMP
Nominal current setting as mentioned on the
identification plate of the pump.
ROTATION SENSE
0
HZ
ROTATION SENSE
Setting of the rotation sense. See the pump
identification plate. Push on to start the
pump (at 30hz) and check the rotation sense.
MIN SPEED
30 HZ
MIN SPEED
Define the minimum motor rotation speed.
DRY RUN PROT
NO
DRY RUN PROT
If the installation is provided with a level switch
(flow switch or other ones) change No by Yes.
PRESSURE SETTING
2.0 BAR
PRESSURE SETTING Working pressure setting in the installation.
START DELTA P
0.3 BAR
START DELTA P
Define the starting pressure as: starting pressure
= setpoint pressure – start delta P
TIME BEFORE STOP
5 S
TIME BEFORE STOP
Time setting before pump stop when there is no
flow.
STANDARD
DISPLAY
DISPLAY
Define the display mode:
- STANDARD: pressure setting (bar) + network
pressure (bar)
- SERVICE: rotation frequency (Hz) + pressure
setting (bar) + networkpressure (bar) + flow
switch detection (1 or 0)
HISTORIC
RUNNING TIME
HOURS
26h
RUNNING TIME
Total pump running hours (H).
PUMP CYCLES
30
PUMP CYCLES
Total number of pump cycles, one cycle includes
one start and one stop.
POWER ON
30
POWER ON
Number of Acson Vario switching on.
MAX PRESSURE
0.0 bar
MAX PRESSURE
Storage of the maximum pressure reached in the
installation (bar).
ALARM COUNT
SHT CIRCUIT
15
ALARM COUNT
SHT CIRCUIT
Total number of short circuits.
ALARM COUNT
OV CURRENT
10
ALARM COUNT
OV CURRENT
Total number of overcurrents.
ALARM COUNT
OVERT T°
5
ALARM COUNT
OVERT T°
Total number of exceeding temperatures.
ALARM COUNT
DRY RUN
6
ALARM COUNT
DRY RUN
Number of dry running Only internal detection
no counter for external detection.