salmson ALTI-HU VARIO Series Installation And Starting Instructions Download Page 13

13

English

4. Application

The booster is designed for boosting and main-
taining the pressure when the water supply net-
work is not well dimensioned or does not exist.
It is used for water supply in high-rise apart-
ments, hospitals, offices and industrial buildings.
Non aggressive clear fluids (potable water, water
containing glycol...).
A control box is used to control, monitor and
protect the boosting system.
The booster is either supplied from the public
water mains or from a mains collection tank.
In case of pressure deviations more than 1 bar in
the suction pipe it is recommended to use a pres-
sure relief valve. The pressure downstream of the
pressure relief valve (back-pressure) is the basis
for the total head calculation of the booster.

5. Product data

5.1  Type key

ALTI-HU-Vario-304-2-M

Booster name

HU: Type of pump (MUH)

304: nominal output and number  

of stages (3 m

3

/h 4 stages)

2: number of pumps

M: Single-phase

5.2  Technical data

- Maximum operating pressure:

10 bars

- Maximum ambient temperature: 0 to +40°C
- Maximum water temperature:

+55°C

- Single-phase supply voltage:

230V (±10%)
50/60Hz

- Nominal current:

see type plate

5.3  Scope of delivery

- Booster.
- Installation and operating instruction of the

booster.

5.4  Accessories

as required

- Diaphragm pressure tank
- Dry running kit or tank

as option

- Insulation valves
- Vibration compensators
- Pressure relief valve
- Counterflanges according to manifold diameter

6. Description and operation

6.1   General description

The booster is a compact installation that is sup-
plied completely piped-up and ready to connect.
The only connections that have to be made are
for suction and delivery pipe and also the power
mains.
Every accessory ordered is delivery separately.
The relevant instructions or standards must be
observed for the connection to the public water
supply mains. Regulations from the water com-
panies must be included when appropriate. Local
conditions (e.g. a supply pressure that is too high
or fluctuates considerably and which might
require the installation of a pressure relief valve)
must also be observed.

6.2   Product description

6.2.1  The booster (Fig. 1)

1.  Control box
2.  Acson Vario
3.  Pressure gauge
4.  Multistage horizontal pumps MUH
5.  Filling plug
6.  Draining plug
7.  Support and fixing frame
8.  Suction manifold
9.  Delivery manifold

NOTA: each pump is fitted with insulation valves
on suction side and insulating valves and non-
return valves on delivery side.

6.2.2  Control box

•  Ensure complete automatic operation of the

booster.

•  Tightness, protection class IP 54.
•  External safety and starting switch of the booster.

Inside (Fig. 2)

1.  Main switch with power supply connection terminals
2.  Motor magnetic circuit-breaker
3.  CEM Filter

6.2.3  Description of the Acson Vario (Fig. 3)

1.  Cable gland of the Acson Vario power supply
2.  Cable gland of the pump power supply
3.  Cable gland of the dry running protection
4.  Cable gland of the series connection (as option)
5.  Suction
6.  Discharge
7.  User interface

POMPES SALMSON SAS 04/2013

Summary of Contents for ALTI-HU VARIO Series

Page 1: ...N M S STOCK N 4 168 504 Ed 3 04 13 ALTI HU VARIO INSTALLATION ET MISE EN SERVICE INSTALLATION AND STARTING INSTRUCTIONS FRAN AIS ENGLISH INSTALLAZIONE E MESSA IN SERVIZIO ITALIANO...

Page 2: ...Fig 1 Fig 2 3 9 1 7 1 2 5 6 2 4 8...

Page 3: ...Fig 3 Fig 5 Fig 6 MAX MIN Fig 4 Acson Vario auto auto 235 262 262 196 G11 4 G11 4 1 3 4 2 6 7 5 2 3 1...

Page 4: ...t tre les suivants d faillance de fonctions importantes de la pompe ou de l installation d faillance du processus d entretien et de r pa ration prescrit dangers pour les personnes par influences lec t...

Page 5: ...essoires Obligatoires R servoir vessie Kit manque d eau ville ou b che Optionnels Vannes d isolement Manchettes anti vibratoires D tendeur de pression Contre brides au diam tre du collecteur 6 Descrip...

Page 6: ...RES a atteint la pression de consigne P REF et que le d bit est nul L Acson Vario assure la protection de la pompe contre 10 2 Le manque d eau Les surintensit s Les temp ratures d eau excessives Le g...

Page 7: ...AVANT ARR T 5 S TPS AVANT ARR T Temporisation avant l arr t de la pompe et apr s la d tection d absence de d bit AFFICHAGE STANDARD AFFICHAGE D fini le mode d affichage Standard Pression R f bar Press...

Page 8: ...ation peut supporter la pression maxi de la pompe d bit nul major e de la pression d eau de ville Dans le cas contraire raccorder un d tendeur de pression la sortie du surpresseur Nous vous recommando...

Page 9: ...rifier l amor age Au besoin tester les pompes l une apr s l autre En aspiration sur b che Fermer la vanne au refoulement Ouvrir la vanne l aspiration D visser les bouchons de remplissage et les enleve...

Page 10: ...montage de la pompe D faut bobinage D connecter le bornier du moteur con cern et contr ler le r seau aux bornes et l isolement du stator remplacer le moteur si n cessaire Manque de pression au refoul...

Page 11: ...par des techniciens locaux et ou le service client le de Salmson Pour viter les demandes de pr cision et com mandes erron es veuillez indiquer toutes les donn es de la plaque signal tique lors de cha...

Page 12: ...y functions failure of the maintenance and repairing process recommended danger to persons due to electrical mechanical and bacteriological influences material damages 2 4 Safety precautions for the o...

Page 13: ...nifold diameter 6 Description and operation 6 1 General description The booster is a compact installation that is sup plied completely piped up and ready to connect The only connections that have to b...

Page 14: ...set point pressure P SET and when the flow is zero The Acson Vario protects the pump against 10 2 dry running over currents too high water temperatures frost short circuits over voltages Under voltage...

Page 15: ...tarting pressure setpoint pressure start delta P TIME BEFORE STOP 5 S TIME BEFORE STOP Time setting before pump stop when there is no flow STANDARD DISPLAY DISPLAY Define the display mode STANDARD pre...

Page 16: ...ter mains pressure Otherwise connect the pressure relief valve to the booster outlet We recommend to install a pressure relief and regulating valve on the booster inlet on the water supply inlet to av...

Page 17: ...k Close the delivery valve Open the suction valve Screw off the filling plugs and remove them With a funnel placed inside the port fill in slowly and completely the pumps and the suction pipes After w...

Page 18: ...connect the terminal block of the motor concerned Check the network at the terminals and the stator insulation Replace the motor if necessary No delivery pressure Flow higher than booster capabilities...

Page 19: ...Spare parts All spare parts must be ordered through Salmson Customer Services In order to avoid any mistakes please specify the name plate data for orders Subject to technical alterations POMPES SALMS...

Page 20: ...a di cautela pu portare a problemi come guasto di importanti funzioni della pompa o del l impianto mancato rispetto del processo di manutenzione e riparazione pericolo alle persone dovuto ad influenze...

Page 21: ...razione Valvola sfogo pressione Controflange in base a diametro collettore 6 Descrizione e funzionamento 6 1 Descrizione generale Il booster un assieme compatto che viene forni to munito di tubazioni...

Page 22: ...pianto P RES ha raggiunto la pres sione di consegna P REF e che il flusso nullo Acson Vario garantisce la protezione della pompa contro 10 2 La mancanza d acqua Le sovraintensit Le temperature d acqua...

Page 23: ...S TPS PRIMA DELLA SENTENZA Temporisation prima dell arresto della pompa e dopo l individuazione d assenza di flusso VISUALIZZAZIONE STANDARD VISUALIZZAZIONE Definito il modo di visualizzazione Standa...

Page 24: ...uesto ingresso ATTENZIONE Non applicare voltaggio esterno ai terminali 6 3 4 Modo Manuale Questo modo accessibile con la chiave La spia luminosa allora estinta fuggevole e pu essere ottenuto soltanto...

Page 25: ...vitare i tappi di riempimento e rimuoverli Con un imbuto posizionato all interno della porta riempire lentamente e completamente le pompe e le tubazioni di aspirazione Dopo l uscita dell acqua e dell...

Page 26: ...la pompa Guasto avvolgimento Scollegare la morsettiera del motore in questione Controllare i collegamenti presso i terminali e l isolamento dello statore Sostituire il motore se necessario Mancanza di...

Page 27: ...ono essere ordinate presso il Servizio Assistenza Clienti Salmson Per evitare richieste di chiarimenti ed errate ordi nazioni necessario indicare all atto dell ordina zione tutti i dati della targhett...

Page 28: ......

Page 29: ...n i n g s 2006 95 EG El e k t r o m a g n e t i s k K o m p a t i b i l i t e t 2004 108 EG De t v e r e n s s t m m e r v e n m e d f l j a n d e e u r o p e i s k a s t a n d a r d e r s o m n m n...

Page 30: ...30 POMPES SALMSON SAS 04 2013...

Page 31: ...31 POMPES SALMSON SAS 04 2013...

Page 32: ...80 380 FAX 39 059 280 200 info tecniche salmson it QUESTO LIBRETTO D USO DEVE ESSERE RIMESSO ALL UTILIZZATORE FINALE E RIMANERE SEMPRE DISPONIBILE SUL POSTO Questo prodotto stato fabbricato in un sito...

Reviews: