background image

16

5.  OPERATION.

5.1.  

START UP AND ShUTDOWN.

Starting up the UPS with mains voltage (Line mode).

1. 

 

a. 

After  making  sure  that  the  connection  with  the  power 
supply is correct, turn ON the circuit breaker of the bat-
tery module (models with extended autonomy only) and 
the  input  one,  keeping  this  order.  From  now  on  the  fan 
will start up and the UPS will supply power to the loads 
through the bypass line. The UPS is on bypass mode, code 
«01».

Start up the UPS by pressing for more than 1 second the 

b. 

ON button. The buzzer will beep once.

A few seconds later, the UPS switches to Line mode, code 

c. 

«02». If the mains voltage is not correct, the UPS will run 
on Battery mode without breaking the output voltage.

Starting  up  the  UPS  without  mains  voltage  (Battery 

2. 

mode).

 

a. 

Make sure that the circuit breaker of the battery module is 
turned  ON (models with extended autonomy only).

Press the ON button for more than 1 second to start up 

b. 

the UPS. The buzzer will beep once. The UPS will run on 
No output mode, code «00».

 A  few  seconds  later,  the  UPS  will  transfer  to  Battery 

c. 

mode, code «03».

Shutdown the UPS with mains voltage (Line mode).

3. 

 

a. 

Shutdown the UPS inverter by pressing the OFF button for 
more than 1 second. The buzzer will beep once and the 
UPS will transfer to Bypass mode.

Once the shutdown is completed, the UPS still has voltage 

b. 

on its output. To turn it off definitely, just break the mains 
voltage  and  a  few  seconds  later  the  LCD  panel  will  be 
turned off and the output voltage will not be present.

Shutdown  the  UPS  without  mains  voltage  (Battery 

4. 

mode).

Shutdown the UPS by pressing the OFF button for more 

a. 

than 1 second. The buzzer will beep once.

Once shutdown, the UPS will transfer to No output mode. 

b. 

Finally the LCD panel will be turned OFF and there will not 
be  output voltage.

Advice

: Turn off the connected loads before starting up 

the UPS. Later, once the UPS runs on INV mode, connect 
them one by one. Turn off  all the loads before turning off 
the UPS.

5.2.  

PARALLEL OPERATING (NOT fOR MODELS IN RACk 
19’’).

Maintenance of the parallel device.

1. 

This  UPS  has  a  parallel  device.  To  add  or  remove  units  from  the 
system, follow the next procedure:

Procedure to add a new UPS.

2. 

Before installing it, prepare the input and output wiring, 

a. 

switches and parallel cable.

 Turn OFF the input and output breakers of the new unit. 

b. 

Connect its input, output and battery cables. Remove the 
bridge between JP1 and JP2 in the terminal strip.

Shutdown the UPSs that are started up. Once all the UPSs 

c. 

are transferred to bypass, remove the cover of the main-
tenance bypass of each UPS, change the position of the 
maintenance switch from «UPS» to «BPS» and turn OFF 
the input circuit breaker of each UPS.

 If the UPS that it is started up is single, remove also the 

d. 

bridge between JP1 and JP2 of the terminal strip.

Remove the cover of the parallel port from the new UPS, 

e. 

push one side of the parallel cable into the parallel kit slot 
and screw the connector; screw the parallel cover back.

Remove  the  maintenance  bypass  cover  from  the  new 

f. 

UPS and change the position of the switch from «UPS» 
to «BPS».

Turn ON the battery switch and the external circuit breaker 

g. 

of the new UPS; measure the voltage difference between 
the  output  of  the  new  UPS  and  the  parallel  system,  in 
order  to  check  if  the  voltage  difference  is  lower  than  1 
V. If yes, turn ON the output circuit breaker. If the voltage 
difference is higher than 1 V, check the wiring.

Remove the cover of the parallel port card located in the 

h. 

UPS, which has been done the maintenance bypass trans-
ference,  and  push  the  other  parallel  cable  side  into  the 
parallel kit slot and fix the connector. Screw the cover of 
the parallel port back.

 Turn ON the input circuit breakers of all UPSs (including 

i. 

the new one) of the parallel system. Once all have trans-
ferred  to  Bypass  mode,  screw  the  maintenance  bypass 
cover back.

 Start up each UPS and check its LCD panel. Make sure 

j. 

that each UPS has a normal operating and all has trans-
ferred to INV mode together. Measure the voltage in JP1 
and JP2 in the terminal strip of each UPS in order to check 
if the voltage difference is lower than 1 V. It the quoted 
difference is higher than 1 V, the output relay of the UPS 
can’t be closed.

 Measure the voltage between each JP2 of each UPS to 

k. 

check if the voltage difference is lower than 5 V (usually 
2 V). If the difference is higher than 5 V, it means that the 
new UPS has to be set again or the parallel cable of the 
parallel kit has to be checked.

USER MANUAL

Summary of Contents for SLC TWIN series

Page 1: ...S L CT WI N I N D E X U S E R S MA N U A L F R O M0 7 k V AT O3 k V A P a g e 2 U S E R S MA N U A L F R O M4 k V AT O2 0 k V A P a g e 3 4...

Page 2: ...UPS VOLTAGE STABILIZERS AND POWER LINE CONDITIONERS SWITCH MODE POWER SUPPLY INDUSTRIAL POWER SUPPLY LIGHTING FLOW DIMMER STABILIZERS STATIC INVERTERS SLC TWIN series from 0 7 to 3 kVA USER S MANUAL...

Page 3: ......

Page 4: ...ng 4 4 2 Installation 4 4 3 Procedure to connect the models with external batteries extended autonomies 4 5 Communication ports 4 5 1 RS 232 interface C7 4 5 2 AS400 interface C16 Option 4 6 Overvolta...

Page 5: ...series This manual has to be read carefully before installing and operating it Keep this manual for future consults 1 2 1 Used symbols and conventions Warning symbol Carefully read the indicated para...

Page 6: ...InthenextPROCESSMAPisrepresentedtheinteractionamongallthe processes of the Quality and Environmental System of SALICRU 2 2 Standard The UPS product SLC TWIN series is designed manufactured and commer...

Page 7: ...ons of voltage frequencies electrical noises black outs and mains faults which are present in the energy distribu tion mains This is the essential target of the UPSs of SLC TWIN series This manual is...

Page 8: ...1 Input breaker protection Fan RJ 45 C7 RS232 communication port Rear view SLC 700 and 1000 TWIN TWIN B1 to 110 Fig 2 115 120 127 VAC C2 Extended autonomy connector C16 AS400 SNMP USB communication po...

Page 9: ...00 SNMP USB communication port optional C11 and C12 Transient protection Fax m dem C4 Outlet C0 Inlet M1 Input breaker protection Fan C7 RS232 communication port Rear view SLC 3000 TWIN to 208 220 230...

Page 10: ...m C4 Outlet C0 Inlet Fan Rear view SLC 700 and 1000 TWIN R TWIN R B1 Fig 8 C2 Extended autonomy connector C16 AS400 SNMP USB communication port optional C7 Communication port RS232 M1 Input breaker pr...

Page 11: ...some other usefull one are in the rear panel C2 Extended au tonomy connector C16 AS400 SNMP USB communication port optional C7 Communication port RS232 M1 Input breaker protection C11 and C12 Transie...

Page 12: ...Transient protection Fax modem C4 Outlets C0 Inlet Fans Rear view SLC 1500 TWIN R B1 Fig 14 C2 Extended au tonomy connector C16 AS400 SNMP USB communication port optional C7 Commu nication port RS232...

Page 13: ...owed from 0 to 999 Vac Hz It displays the frequency value of the output voltage which will be showed from 0 to 99 Hz Load information It displays the of the load in W or VA the maximum value will be s...

Page 14: ...MOD BAT TWIN 2x3AB003 40A R W C0 EE29503 Battery module special EE CO Silk screen printing Made in Spain in the equipment and packing customs topics W White label team R Rack format Protection caliber...

Page 15: ...IN series is card type in order to be inserted into the slot that UPS has in its rear side Thanks to this format it is avoided to have small devices around the UPS The connection from the UPS with the...

Page 16: ...e earth leakage currents at the UPS output plus the connected load s do not overcome 3 5 mA 4 1 4 Operating Do not disconnect the power cord plug of the UPS meanwhile the loads are turned on because t...

Page 17: ...2 6 hours before its use Once the input circuit breaker is turned On the UPS will charge the batteries automatically The UPS can be used immediately without charging the batteries previously but the...

Page 18: ...ifference of potential will provoke a short circuit which will cause dam ages to the UPS and or to the battery modules Any connection between the UPS and battery module s will 3 be done taking care on...

Page 19: ...e new UPS monitoring software which facilitates a friendly monitoring and control interface In case of mains failure this software gives an automatic Shutdown for a system made by several PCs With thi...

Page 20: ...epending if the initial setting has been modi fied or not On bypass mode code 01 the equipment will still be supplying output voltage through the bypass so the input circuit breaker of the switchgear...

Page 21: ...charges the batteries too The acoustic alarm of the UPS will beep once every 2 minutes The UPS doesn t have available the autonomy function when it runs on Bypass mode so if the mains faults the load...

Page 22: ...Operating mode screen Battery mode code 03 Fig 28 220Vac equipments 5 2 5 Fault mode Anyone of the fault or warning codes showed in the table 8 are considered as fault mode Besides some warning word c...

Page 23: ...ect of the LCD panel Step 2 The blinking black point is displayed beside 230 V after pressing twice the button Select Step 3 When pressing the button Enter for more than 1 second the new selected valu...

Page 24: ...or mainte nance job turn off the battery circuit breaker or remove the connection between battery blocks The batteries have dangerous voltages The maintenance 8 or replacement of the batteries has to...

Page 25: ...s guaranteed the perfect operating and the pos sible coming faults are avoided These supervisions are usually done without shutdown the equipment In those cases that a shutdown were needed a date and...

Page 26: ...3 THDv with non linear load 6 in accordance with EN 62040 3 Dynamic response time 150 ms Overload on line mode 150 for 30 s 150 for 0 3 s Overload on battery mode 150 for 30 s 150 for 0 3 s Permissib...

Page 27: ...ble 11 Output power derate according to the operating altitude 7 2 GlosSarY AC It is nominated as alternating current CA in Spanish abbreviation and AC in English to the electrical current in which th...

Page 28: ...d it is crossed by an electric current The colour wave longitude depends on the semiconductor ma terial used in its manufacturing being able to vary from the ultraviolet one going through the visible...

Page 29: ...28 NOTES USER MANUAL...

Page 30: ...29 SALICRU NOTES...

Page 31: ...30 NOTES USER MANUAL...

Page 32: ......

Page 33: ...RLANDA NORUEGA REP BLICA CHECA SUECIA SUIZA UCRANIA ARGENTINA BRASIL CHILE COLOMBIA ECUADOR PER ARABIA SAUD ARGELIA EGIPTO JORDANIA KUWAIT MARRUECOS T NEZ KAZAJST N PAKIST N FILIPINAS INDONESIA MALASI...

Page 34: ...UPS VOLTAGE STABILIZERS AND POWER LINE CONDITIONERS SWITCH MODE POWER SUPPLY INDUSTRIAL POWER SUPPLY LIGHTING FLOW DIMMER STABILIZERS STATIC INVERTERS UPS SLC TWIN series from 4 to 20kVA USER S MANUAL...

Page 35: ......

Page 36: ...4 Operating 4 1 5 Maintenance service and faults 4 2 To keep in mind 4 3 Unpacking and content checking 4 4 Connection of the input output and protective earth wiring 4 4 1 Notes for the installation...

Page 37: ...tion measures Danger of electrical discharge symbol Pay special attention to it both in the indication on the equipment and in the paragraph referred to this instruction s manual i Main protective ear...

Page 38: ...represented the interaction among all the processes of the Quality and Environmental System of SALICRU 2 2 Standard The UPS product SLC TWIN series is designed manufactured and commercialized in acco...

Page 39: ...ectrical noises blackouts and mains faults which are present in the energy distribution mains This is the essential target of the UPSs of SLC TWIN series Furthermore the 4 5 and 6kVA equipments can al...

Page 40: ...on port Intelligent slot Fans Input breaker Terminal strip cover Parallel port Maintenance bypass switch Rear view of the 12 15 and 20 kVA equipment bat Fig 3 tery cabinet 40 x 9Ah Communication port...

Page 41: ...m 0 to 999 Vac It displays the frequency value of the output voltage which will be showed from 0 to 99 Hz Load information It displays the of the load in W or VA the maximum value will be showed from...

Page 42: ...single phase UPS Power in VA KIT Equipments with two or more cabinets in a single code MOD BAT TWIN 2x3AB003 40A R W C0 EE29503 Battery module special EE CO Silkscreen Made in Spain in the equipment...

Page 43: ...r equipments with standard autonomy and adapts it to the optimal levels of the battery bank to charge This double conversion structure is complemented with two addi tional functional blocks the bypass...

Page 44: ...accepted by the main software and hardware manufacturers The available SNMP optional for TWIN series is card type in order to be inserted into the slot that UPS has in its rear side Thanks to this fo...

Page 45: ...ctrical shock risk Although the unit is disconnected from the electrical mains there are internal parts in the UPS that are still connected to the batteries therefore they are under dangerous voltage...

Page 46: ...e input and output cables to their corresponding 5 UPS terminals and according to the model circuit diagram i Tighten the connections The protective earth is the connection cable between the 6 equipme...

Page 47: ...eans the number of faulty UPSs that the system can allow simultaneously The higher is X the higher will be the reliability of the system For those occasions where the reliability is the essential N X...

Page 48: ...AINS FAULT REMOTE SHUTDOWN GENERAL ALARM UPS FAULT GND DB 9 interface of AS400 communication protocol Fig 13 4 8 Software Free software WinPower WinPower is the brand of the new UPS monitoring softwar...

Page 49: ...rocedure to add a new UPS 2 Before installing it prepare the input and output wiring a switches and parallel cable Turn OFF the input and output breakers of the new unit b Connect its input output and...

Page 50: ...ed OFF Do not touch the maintenance switch meanwhile the c system runs on inverter mode 5 3 CONTROL Panel All the codes will be displayed in the LCD panel corresponding to their operating modes as fol...

Page 51: ...one those loads that are not critical in order to decrease the load percentage under 90 of the UPS nominal power rate Note To connect a generator or genset proceed as follows Turn on the generator an...

Page 52: ...ternated between the Pn symbol and the code of the mode The P symbol means that the UPS runs on Parallel mode and n number means the parallel quantity Warning mode 6 The LCD panel on Warning mode is s...

Page 53: ...cy or By pass status will be modified by the selected one In case the ENTER or Select buttons are not pressed in 10 seconds period the black point will disappear without applying any changes Only one...

Page 54: ...ing should start when the UPS would have shutdown due to a deep battery discharge The charge time for a standard UPS should 12 hours as minimum 6 2 Notes for installing and replacing the battery Befor...

Page 55: ...e load and reduce the number of loads connected to the UPS Check that they are not damaged The Warning mode is 23 the buzzer beeps every second The UPS charger is faulty Contact with the technical ser...

Page 56: ...s are avoided These supervisions are usually done without shutdown the equipment In those cases that a shutdown were needed a date and time would agree with the customer to do the task This maintenanc...

Page 57: ...the output is broken Internal charger Technology DC DC Flyback Charge type P U Constant power constant voltage Floating voltage accuracy 1 V Maximum charging current 2 A single phase input 4 A three p...

Page 58: ...romag netic interference considerably EMi is the perturbation that occurs in a radio transmis sion or any other electrical circuit caused by an electromagnetic perturbation coming from an external sou...

Page 59: ...nt This isdoneby rectifier diodes which can be solid state semiconduc tors vacuum or gassy valves like the mercury vapour Depending on the features of the alternating current power supply used it is c...

Page 60: ......

Page 61: ...NAMARCA GRECIA HOLANDA IRLANDA NORUEGA REP BLICA CHECA SUECIA SUIZA UCRANIA ARGENTINA BRASIL CHILE COLOMBIA ECUADOR PER ARABIA SAUD ARGELIA EGIPTO JORDANIA KUWAIT MARRUECOS T NEZ KAZAJST N PAKIST N FI...

Reviews: