6. MAINTENANCE, WARRANTY AND SERVICE.
6.1.
BATTERY MAINTENANCE.
This UPS series only requires a minimum maintenance. The bat-
•
tery used in the standard models is lead acid, sealed, valve reg-
ulated and maintenance free. These models require a minimum
of repairs only. The only requirement is to charge the UPS regu-
larly to prolong the expected battery lifetime. Meanwhile it is
connected to the mains power supply, never mind if the UPS is
turned on or not, it will keep the batteries charged and will also
give a protection against overcharging and over discharging.
The UPS has to be charged every 3 months, if it is not used for
•
long time.
In hot areas, the battery should be charged and discharged
•
every 2 months. The standard charging period should be 5 hours
to 90% of the charge batteries.
Under normal conditions, the battery lifetime is from 3 to 5
•
years at 25ºC ambient temperature. In such case that the bat-
tery were not in good conditions, it should be replaced before.
The replacing has to be done by qualified staff.
Always replace them with the same number and type.
•
Do not replace one battery only. All the batteries have to be
•
replaced together and according to the manufacturer’s instruc-
tions.
Usually, the batteries have to be charged and discharged every
•
3 months. The charging should start when the UPS would have
shutdown due to a deep battery discharge. The charge time for a
standard UPS should be 5 hours to 90% of the charge batteries.
6.2.
NOTES fOR INSTALLING AND REPLACING ThE
BATTERY.
Before installing the batteries, take rings, watches and brace-
1.
lets off.
If it were needed to replace the connection of any cable, ask
2.
for original parts to authorised distributors or service centres
in order to avoid overheating or sparks with fire danger due to
an inadequate size.
Do not throw the batteries to fire, explosion danger exists.
3.
Do not open the batteries; the electrolyte spillage is very toxic
4.
and harmful for the skin and eyes.
Do not short-circuit the + and - poles of the batteries, electro-
5.
cution or fire danger exists.
Make sure that there is not any voltage before handling the
6.
batteries. The battery circuit is not isolated from the input cir-
cuit. There could be dangerous voltages between the battery
and earth terminals.
Although the input circuit breaker is turned off, internal parts
7.
of the UPS are still connected to the batteries, therefore dan-
gerous voltage exists. So, before doing any repair or mainte-
nance job, turn off the battery circuit breaker or remove the
connection between battery blocks.
The batteries have dangerous voltages. The maintenance
8.
or replacement of the batteries has to be done by qualified
staff, which should be familiarized with them. No other person
should handle them.
6.3.
TROUBLEShOOTING GUIDE.
Problem
Possible
cause
Solution
With the UPS
connected to mains,
the equipment seems
not be connected to it
There is no
input voltage
With a measurement instrument
check that the input voltage is
available and all the cables of
the UPS and loads are connected
properly.
The warning code 09 is
displayed
The phase and
neutral are
swapped
Take out the plug from wall socket,
rotate it 180º and insert it again.
The warning code is 03
and the symbols “H” or
“L” can be displayed
The voltage
and/or
frequency of
the mains are
out of range
Check the voltage and frequency
values of the input. If they are out
from range for long period times,
inform your distributor energy
company.
Although the displayed
code is 00 or 01, the
UPS is ready to feed
the loads
The inverter is
not started up
Press for more than 1 second the
key “I”.
The warning code is 03
and the acoustic alarm
beeps every 4 seconds
Fault in the
power supply
to the UPS.
The loads are supplied from UPS
batteries. When the alarm frequency
is accelerated, 1 beep per second,
the end of autonomy is close to.
The power supply to the loads will
broken in short. It is recommended
to shutdown them.
The warning code is 07
and the acoustic alarm
beeps every second.
Oveload
Reduce the number of loads
connected to the UPS output.
The warning code is
08 or 06 or 08 with a
continuous acoustic
alarm
Fault in the
power supply
to the UPS
Contact with the nearest distributor
or Service and Technical Support
(STS) center.
The autonomy time is
less and less.
Battery has
not been fully
charged
Charge the batteries between 1
and 2 hours. If the problem persists
contact with the nearest distributor
or STS.
UPS overloaded Reduce the number of loads
connected to the UPS output.
Aged battery
Replace the batteries. Contact with
the nearest distributor or STS.
The warning code is 13
with an acoustic alarm
every second
Battery charger
faulty
Contact with the nearest distributor
or Service and Technical Support
(STS) center
The warning code is 10 The fan/s are
blocked or do
not work
Check the fan/s and inform the
nearest distributor or Service and
Technical Support (STS) center.
Table 9.
Fault location for tower format.
In case were needed to contact with the assistance service, pro-
vide the following information:
Model and serial number of the UPS.
•
Date of the problem.
•