Put all the equipments on Bypass and, next, remove the
l.
cover of the maintenance bypass of each UPS and move
the maintenance switch from «BPS» to «UPS» and screw
the cover back.
Start up the UPSs on Line mode to operate in parallel op-
m.
erating.
i
If the UPS is wrong with the above procedure,
make the maintenance according to the steps to
remove one UPS.
Procedure to remove one UPS.
3.
In case is needed to remove one UPS from the parallel
a.
system, which is running normal, press the OFF Button
twice consecutively and that UPS will shutdown its output
immediately.
Turn OFF the circuit breakers of input, mains, output and
b.
battery of the UPS to remove.
Press the OFF button of the rest of UPSs. Once all have
c.
transferred to Bypass mode, remove the maintenance by-
pass cover of each UPS, move the maintenance switch
from «UPS» to «BPS» and turn OFF the input circuit
breaker.
Once removed the UPS, the bridge between JP1 and JP2
d.
of the UPS terminal strip has to be done in case only one
UPS will remain in the system.
Once all the LCD panels are shutdown, remove the cover
e.
from the parallel port located in the UPS to remove, ex-
tract parallel cable and screw the cover back.
Turn OFF all the input circuit breakers of the rest UPSs. Once
f.
all UPSs have transferred to Bypass mode, move the main-
tenance switch from «BPS» to «UPS» and screw the cover
back. Put all he UPSs on Line mode to run on parallel.
If the removed UPS will be used on single mode, JP1 and
g.
JP2 have to be bridged.
Parallel system warnings:
When the system runs on inverter mode, make sure that
a.
all the maintenance switches of the UPSs are in the same
position (either on «UPS» or on «BPS»).
Enter into inverter mode before start up the system. The
b.
output circuit breaker has to be turned OFF.
Do not touch the maintenance switch meanwhile the
c.
system runs on inverter mode.
5.3.
CONTROL PANEL.
All the codes will be displayed in the LCD panel corresponding to
their operating modes, as follows:
Operating mode
Code
Operating mode
Code
Code table of Mode
No output mode
00
Battery mode
03
Bypass mode
01
Battery test mode
04
Line mode
02
Code table of Warning
ID lost
21
Charger fault
23
Fan error
22
Input fuse blown
24
Code table of fault
Bus fault
05
STS Bypass short-circuited
13
Inverter fault
06
Battery SCR short-circuited
14
Overload fault
07
Parallel communication fault
15
Overtemperature fault
08
Partial fault current Un
16
Inverter short-circuit
09
Model error
17
Communication fault
10
SCI Rx error
18
Battery opened
27
Negative output power fault
20
Inverter relay short-circuited
12
Table 1.
Correspondence between codes and modes of operation.
Nr.
Operating
LCD
panel
code
Alarm
1
Output mode
00
None
2
Bypass mode
01
Beep every 2 minutes
3
Line Mode
02
None
4
Battery
mode
0-20% of the
battery capacity
03
Beep every second
21%-100% of the
battery capacity
Beep every 4 seconds
5
Battery test mode
04
None
6
Overload on Bypass mode
01
Beep twice every second
7
Overload on Line mode
02
Beep twice every second
8
Overload on Battery mode,
previous warning
03
Beep twice every second
9
Fault BUS voltage
05
Continuous beeping
10
INVERTER damaged
06
Continuous beeping
11
Overload and no output
07
Continuous beeping
12
Overtemperature
08
Continuous beeping
13
Output short-circuit
09
Continuous beeping
14
Communication fault
10
Continuous beeping
15
Battery opened
27
Continuous beeping
16
INVERTER relay fault
12
Continuous beeping
17
BAT SCR fault
14
Continuous beeping
18
Fault parallel
15
Continuous beeping
19
ID lost
21
Beep every second
20
Fault fan
22
Beep every second
21
Charger and battery faulty
23
Beep every second
Table 2.
Correspondence between alarms, codes and modes of
operation.