Salicru SLC TWIN series User Manual Download Page 50

17

SALICRU

Put all the equipments on Bypass and, next, remove the 

l. 

cover of the maintenance bypass of each UPS and move 
the maintenance switch from «BPS» to «UPS» and screw 
the cover back.

Start up the UPSs on Line mode to operate in parallel op-

m. 

erating.

i

If  the  UPS  is  wrong  with  the  above  procedure, 
make the maintenance according to the steps to  

 

remove one UPS.

Procedure to remove one UPS.

3. 

In  case  is  needed  to  remove  one  UPS  from  the  parallel 

a. 

system,  which  is  running  normal,  press  the  OFF  Button 
twice consecutively and that UPS will shutdown its output 
immediately.

Turn OFF the circuit breakers of input, mains, output and 

b. 

battery of the UPS to remove.

Press the OFF button of the rest of UPSs. Once all have 

c. 

transferred to Bypass mode, remove the maintenance by-
pass cover of each UPS, move the maintenance switch 
from  «UPS»  to  «BPS»  and  turn  OFF  the  input  circuit 
breaker.

Once removed the UPS, the bridge between JP1 and JP2 

d. 

of the UPS terminal strip has to be done in case only one 
UPS will remain in the system.

 Once all the LCD panels are shutdown, remove the cover 

e. 

from the parallel port located in the UPS to remove, ex-
tract parallel cable and screw the cover back.

 Turn OFF all the input circuit breakers of the rest UPSs. Once 

f. 

all UPSs have transferred to Bypass mode, move the main-
tenance switch from «BPS» to «UPS» and screw the cover 
back. Put all he UPSs on Line mode to run on parallel.

If the removed UPS will be used on single mode, JP1 and 

g. 

JP2 have to be bridged.

Parallel system warnings:

When the system runs on inverter mode, make sure that 

a. 

all the maintenance switches of the UPSs are in the same 
position (either on «UPS» or on «BPS»).

 Enter into inverter mode before start up the system. The 

b. 

output circuit breaker has to be turned OFF.

Do  not  touch  the  maintenance  switch  meanwhile  the 

c. 

system runs on inverter mode.

5.3.  

CONTROL PANEL.

All the codes will be displayed in the LCD panel corresponding to 
their operating modes, as follows:

Operating mode

Code

Operating mode

Code

Code table of Mode

No output mode

00

Battery mode

03

Bypass mode

01

Battery test mode

04

Line mode

02

Code table of Warning

ID lost

21

Charger fault

23

Fan error

22

Input fuse blown

24

Code table of fault

Bus fault

05

STS Bypass short-circuited

13

Inverter fault

06

Battery SCR short-circuited

14

Overload fault

07

Parallel communication fault

15

Overtemperature fault

08

Partial fault current Un

16

Inverter short-circuit

09

Model error

17

Communication fault

10

SCI Rx error

18

Battery opened

27

Negative output power fault

20

Inverter relay short-circuited

12

Table 1. 

Correspondence between codes and modes of operation.

Nr.

Operating

LCD 

panel 

code

Alarm

1

Output mode

00

None

2

Bypass mode

01

Beep every 2 minutes

3

Line Mode

02

None

4

Battery 

mode

0-20% of the 

battery capacity

03

Beep every second

21%-100% of the 

battery capacity

Beep every 4 seconds

5

Battery test mode

04

None

6

Overload on Bypass mode

01

Beep twice every second

7

Overload on Line mode

02

Beep twice every second

8

Overload on Battery mode, 

previous warning

03

Beep twice every second

9

Fault BUS voltage

05

Continuous beeping

10

INVERTER damaged

06

Continuous beeping

11

Overload and no output

07

Continuous beeping

12

Overtemperature

08

Continuous beeping

13

Output short-circuit

09

Continuous beeping

14

Communication fault

10

Continuous beeping

15

Battery opened

27

Continuous beeping

16

INVERTER relay fault

12

Continuous beeping

17

BAT SCR fault

14

Continuous beeping

18

Fault parallel

15

Continuous beeping

19

ID lost

21

Beep every second

20

Fault fan

22

Beep every second

21

Charger and battery faulty

23

Beep every second

Table 2. 

Correspondence  between  alarms,  codes  and  modes  of 
operation.

5.3.1.   Modos de trabajo.

Summary of Contents for SLC TWIN series

Page 1: ...S L CT WI N I N D E X U S E R S MA N U A L F R O M0 7 k V AT O3 k V A P a g e 2 U S E R S MA N U A L F R O M4 k V AT O2 0 k V A P a g e 3 4...

Page 2: ...UPS VOLTAGE STABILIZERS AND POWER LINE CONDITIONERS SWITCH MODE POWER SUPPLY INDUSTRIAL POWER SUPPLY LIGHTING FLOW DIMMER STABILIZERS STATIC INVERTERS SLC TWIN series from 0 7 to 3 kVA USER S MANUAL...

Page 3: ......

Page 4: ...ng 4 4 2 Installation 4 4 3 Procedure to connect the models with external batteries extended autonomies 4 5 Communication ports 4 5 1 RS 232 interface C7 4 5 2 AS400 interface C16 Option 4 6 Overvolta...

Page 5: ...series This manual has to be read carefully before installing and operating it Keep this manual for future consults 1 2 1 Used symbols and conventions Warning symbol Carefully read the indicated para...

Page 6: ...InthenextPROCESSMAPisrepresentedtheinteractionamongallthe processes of the Quality and Environmental System of SALICRU 2 2 Standard The UPS product SLC TWIN series is designed manufactured and commer...

Page 7: ...ons of voltage frequencies electrical noises black outs and mains faults which are present in the energy distribu tion mains This is the essential target of the UPSs of SLC TWIN series This manual is...

Page 8: ...1 Input breaker protection Fan RJ 45 C7 RS232 communication port Rear view SLC 700 and 1000 TWIN TWIN B1 to 110 Fig 2 115 120 127 VAC C2 Extended autonomy connector C16 AS400 SNMP USB communication po...

Page 9: ...00 SNMP USB communication port optional C11 and C12 Transient protection Fax m dem C4 Outlet C0 Inlet M1 Input breaker protection Fan C7 RS232 communication port Rear view SLC 3000 TWIN to 208 220 230...

Page 10: ...m C4 Outlet C0 Inlet Fan Rear view SLC 700 and 1000 TWIN R TWIN R B1 Fig 8 C2 Extended autonomy connector C16 AS400 SNMP USB communication port optional C7 Communication port RS232 M1 Input breaker pr...

Page 11: ...some other usefull one are in the rear panel C2 Extended au tonomy connector C16 AS400 SNMP USB communication port optional C7 Communication port RS232 M1 Input breaker protection C11 and C12 Transie...

Page 12: ...Transient protection Fax modem C4 Outlets C0 Inlet Fans Rear view SLC 1500 TWIN R B1 Fig 14 C2 Extended au tonomy connector C16 AS400 SNMP USB communication port optional C7 Commu nication port RS232...

Page 13: ...owed from 0 to 999 Vac Hz It displays the frequency value of the output voltage which will be showed from 0 to 99 Hz Load information It displays the of the load in W or VA the maximum value will be s...

Page 14: ...MOD BAT TWIN 2x3AB003 40A R W C0 EE29503 Battery module special EE CO Silk screen printing Made in Spain in the equipment and packing customs topics W White label team R Rack format Protection caliber...

Page 15: ...IN series is card type in order to be inserted into the slot that UPS has in its rear side Thanks to this format it is avoided to have small devices around the UPS The connection from the UPS with the...

Page 16: ...e earth leakage currents at the UPS output plus the connected load s do not overcome 3 5 mA 4 1 4 Operating Do not disconnect the power cord plug of the UPS meanwhile the loads are turned on because t...

Page 17: ...2 6 hours before its use Once the input circuit breaker is turned On the UPS will charge the batteries automatically The UPS can be used immediately without charging the batteries previously but the...

Page 18: ...ifference of potential will provoke a short circuit which will cause dam ages to the UPS and or to the battery modules Any connection between the UPS and battery module s will 3 be done taking care on...

Page 19: ...e new UPS monitoring software which facilitates a friendly monitoring and control interface In case of mains failure this software gives an automatic Shutdown for a system made by several PCs With thi...

Page 20: ...epending if the initial setting has been modi fied or not On bypass mode code 01 the equipment will still be supplying output voltage through the bypass so the input circuit breaker of the switchgear...

Page 21: ...charges the batteries too The acoustic alarm of the UPS will beep once every 2 minutes The UPS doesn t have available the autonomy function when it runs on Bypass mode so if the mains faults the load...

Page 22: ...Operating mode screen Battery mode code 03 Fig 28 220Vac equipments 5 2 5 Fault mode Anyone of the fault or warning codes showed in the table 8 are considered as fault mode Besides some warning word c...

Page 23: ...ect of the LCD panel Step 2 The blinking black point is displayed beside 230 V after pressing twice the button Select Step 3 When pressing the button Enter for more than 1 second the new selected valu...

Page 24: ...or mainte nance job turn off the battery circuit breaker or remove the connection between battery blocks The batteries have dangerous voltages The maintenance 8 or replacement of the batteries has to...

Page 25: ...s guaranteed the perfect operating and the pos sible coming faults are avoided These supervisions are usually done without shutdown the equipment In those cases that a shutdown were needed a date and...

Page 26: ...3 THDv with non linear load 6 in accordance with EN 62040 3 Dynamic response time 150 ms Overload on line mode 150 for 30 s 150 for 0 3 s Overload on battery mode 150 for 30 s 150 for 0 3 s Permissib...

Page 27: ...ble 11 Output power derate according to the operating altitude 7 2 GlosSarY AC It is nominated as alternating current CA in Spanish abbreviation and AC in English to the electrical current in which th...

Page 28: ...d it is crossed by an electric current The colour wave longitude depends on the semiconductor ma terial used in its manufacturing being able to vary from the ultraviolet one going through the visible...

Page 29: ...28 NOTES USER MANUAL...

Page 30: ...29 SALICRU NOTES...

Page 31: ...30 NOTES USER MANUAL...

Page 32: ......

Page 33: ...RLANDA NORUEGA REP BLICA CHECA SUECIA SUIZA UCRANIA ARGENTINA BRASIL CHILE COLOMBIA ECUADOR PER ARABIA SAUD ARGELIA EGIPTO JORDANIA KUWAIT MARRUECOS T NEZ KAZAJST N PAKIST N FILIPINAS INDONESIA MALASI...

Page 34: ...UPS VOLTAGE STABILIZERS AND POWER LINE CONDITIONERS SWITCH MODE POWER SUPPLY INDUSTRIAL POWER SUPPLY LIGHTING FLOW DIMMER STABILIZERS STATIC INVERTERS UPS SLC TWIN series from 4 to 20kVA USER S MANUAL...

Page 35: ......

Page 36: ...4 Operating 4 1 5 Maintenance service and faults 4 2 To keep in mind 4 3 Unpacking and content checking 4 4 Connection of the input output and protective earth wiring 4 4 1 Notes for the installation...

Page 37: ...tion measures Danger of electrical discharge symbol Pay special attention to it both in the indication on the equipment and in the paragraph referred to this instruction s manual i Main protective ear...

Page 38: ...represented the interaction among all the processes of the Quality and Environmental System of SALICRU 2 2 Standard The UPS product SLC TWIN series is designed manufactured and commercialized in acco...

Page 39: ...ectrical noises blackouts and mains faults which are present in the energy distribution mains This is the essential target of the UPSs of SLC TWIN series Furthermore the 4 5 and 6kVA equipments can al...

Page 40: ...on port Intelligent slot Fans Input breaker Terminal strip cover Parallel port Maintenance bypass switch Rear view of the 12 15 and 20 kVA equipment bat Fig 3 tery cabinet 40 x 9Ah Communication port...

Page 41: ...m 0 to 999 Vac It displays the frequency value of the output voltage which will be showed from 0 to 99 Hz Load information It displays the of the load in W or VA the maximum value will be showed from...

Page 42: ...single phase UPS Power in VA KIT Equipments with two or more cabinets in a single code MOD BAT TWIN 2x3AB003 40A R W C0 EE29503 Battery module special EE CO Silkscreen Made in Spain in the equipment...

Page 43: ...r equipments with standard autonomy and adapts it to the optimal levels of the battery bank to charge This double conversion structure is complemented with two addi tional functional blocks the bypass...

Page 44: ...accepted by the main software and hardware manufacturers The available SNMP optional for TWIN series is card type in order to be inserted into the slot that UPS has in its rear side Thanks to this fo...

Page 45: ...ctrical shock risk Although the unit is disconnected from the electrical mains there are internal parts in the UPS that are still connected to the batteries therefore they are under dangerous voltage...

Page 46: ...e input and output cables to their corresponding 5 UPS terminals and according to the model circuit diagram i Tighten the connections The protective earth is the connection cable between the 6 equipme...

Page 47: ...eans the number of faulty UPSs that the system can allow simultaneously The higher is X the higher will be the reliability of the system For those occasions where the reliability is the essential N X...

Page 48: ...AINS FAULT REMOTE SHUTDOWN GENERAL ALARM UPS FAULT GND DB 9 interface of AS400 communication protocol Fig 13 4 8 Software Free software WinPower WinPower is the brand of the new UPS monitoring softwar...

Page 49: ...rocedure to add a new UPS 2 Before installing it prepare the input and output wiring a switches and parallel cable Turn OFF the input and output breakers of the new unit b Connect its input output and...

Page 50: ...ed OFF Do not touch the maintenance switch meanwhile the c system runs on inverter mode 5 3 CONTROL Panel All the codes will be displayed in the LCD panel corresponding to their operating modes as fol...

Page 51: ...one those loads that are not critical in order to decrease the load percentage under 90 of the UPS nominal power rate Note To connect a generator or genset proceed as follows Turn on the generator an...

Page 52: ...ternated between the Pn symbol and the code of the mode The P symbol means that the UPS runs on Parallel mode and n number means the parallel quantity Warning mode 6 The LCD panel on Warning mode is s...

Page 53: ...cy or By pass status will be modified by the selected one In case the ENTER or Select buttons are not pressed in 10 seconds period the black point will disappear without applying any changes Only one...

Page 54: ...ing should start when the UPS would have shutdown due to a deep battery discharge The charge time for a standard UPS should 12 hours as minimum 6 2 Notes for installing and replacing the battery Befor...

Page 55: ...e load and reduce the number of loads connected to the UPS Check that they are not damaged The Warning mode is 23 the buzzer beeps every second The UPS charger is faulty Contact with the technical ser...

Page 56: ...s are avoided These supervisions are usually done without shutdown the equipment In those cases that a shutdown were needed a date and time would agree with the customer to do the task This maintenanc...

Page 57: ...the output is broken Internal charger Technology DC DC Flyback Charge type P U Constant power constant voltage Floating voltage accuracy 1 V Maximum charging current 2 A single phase input 4 A three p...

Page 58: ...romag netic interference considerably EMi is the perturbation that occurs in a radio transmis sion or any other electrical circuit caused by an electromagnetic perturbation coming from an external sou...

Page 59: ...nt This isdoneby rectifier diodes which can be solid state semiconduc tors vacuum or gassy valves like the mercury vapour Depending on the features of the alternating current power supply used it is c...

Page 60: ......

Page 61: ...NAMARCA GRECIA HOLANDA IRLANDA NORUEGA REP BLICA CHECA SUECIA SUIZA UCRANIA ARGENTINA BRASIL CHILE COLOMBIA ECUADOR PER ARABIA SAUD ARGELIA EGIPTO JORDANIA KUWAIT MARRUECOS T NEZ KAZAJST N PAKIST N FI...

Reviews: