Elektrische verwarmingsbatterijjj 

(enkel

8

www.salda.lt

RIRS 1200HE EKO 3.0 / RIRS 1200HW EKO 3.0 / RIRS 1200HE EKO 3.0 2X230  

•  Electrical  heater  does  not  need  to  be  serv-

iced additionally. It is compulsory to change 

filters as described above

•  Heaters have 2 thermal protections: automat-

ically self-resetting, which activates at +50°C 

and the manually restored, which activates at 

+100°C.

•  After the activation of the manually restored 

protection,  the  unit  must  be  disconnected 

from the power supaply. Wait until the heating 

elements cool down and the fans stop rotat-

ing. After identifying and removing the reason 

of failure, to start the unit, press the “

reset

” 

button. 

The  failure  can  be  identified only 

by a qualified professional

•  If  necessary,  the  electrical  heater  can  be 

removed.  Disconnect  the  electrical  connec-

tor  from  the  heater  and  remove  the  heater 

(Pic. a-b).

•  Das Elektro-Heizregister bedarf keiner zusätzli-

chen Wartung. Es sind nur die Filter rechtzeitig 

zu wechseln, wie oben aufgeführt.

•  Heizregister  verfügen  über  2  Wärmeschutz-

vorrichtungen:  die  mit  einer  automatischen 

Rückstellung, die bei +50 ºC anspricht; die mit 

einer manuellen Rückstellung, die bei +100 ºC 

anspricht.

•  Bei Ansprechen der Schutzvorrichtung mit ma-

nueller Rückstellung ist das Gerät vom Strom-

netz zu trennen. Abwarten, bis die Heizkörper 

sich  abgekühlt  haben  und  die  Ventilatoren 

zum Stillstand gekommen sind. Nachdem das 

Problem identi

fi

ziert und gelöst ist, die „

reset

“ 

Taste drücken und das Gerät wieder in Betrieb 

nehmen. 

Ausfall kann nur durch Fachperso-

nal festgestellt werden.

 Bei Bedarf kann das 

Elektro-Heizregister  herausgenommen  wer-

den. Dazu den Stromanschluss am Heizregis-

ter trennen und das Heizregister herausziehen 

(Abb. a-b).

•  La  batterie  électrique  ne  nécessite  pas 

d’entretien  supplémentaire.  Il  suffit de  rem-

placer  les  filtres, comme  il  est  indiqué  ci-

dessus.

•  Les  batteries  électriques  sont  équipées  de 

deux  protections  thermiques  :  automatique, 

qui se remet en marche automatiquement et 

qui déclenche à une température de + 50°C 

et manuelle, qui doit être remise en marche 

manuellement  et  qui  déclenche  à  une  tem-

pérature de +100°C.

•  Lorsque  la  protection  thermique  à  remise 

en  marche  manuelle  déclenche,  il  est  né-

cessaire  de  déconnecter  l’unité  du  réseau 

d’alimentation.  Attendre  jusqu’au  refroidis-

sement  complète  des  éléments  chauffants 

et l’arrêt de tout mouvement dans les venti-

lateurs. Déterminer la cause de la panne et 

l’éliminer. Appuyer su le bouton « 

reset

 » et 

remettre l’appareil en marche. 

La cause de a 

panne ne peut être déterminée que par le 

personnel qualifié

•  Au besoin on peu démonter et sortir la batte-

rie électrique du caisson. Il faut déconnecter 

la  connexion  électrique  et  sortir    la  batterie 

(fig. a-b)

• De elektrische verwarmingsbatterij vereist 

geen bijkomend onderhoud. Het volstaat om 

de filters te vervangen, zoals hierboven 

aangegeven.

• De elektrische verwarmingsbatterijen zijn 

uitgerust met twee thermische beveiligingen: 

een  beveiliging die automatisch reset en die 

in werking treedt wanneer de temperatuur 

+50°C bedraagt, en een  beveiliging die 

manueel wordt gereset en die in werking 

treedt bij een temperatuur vanaf +100°C.

• Wanneer de manuele thermische beveiliging 

afgaat, is het nodig om de unit los 

te koppelen van het elektriciteitsnet. Wacht 

dan tot de warme elementen volledig 

afgekoeld zijn en tot de ventilator stop met 

draaien. Ga na wat de panne veroorzaakt 

heeft, en herstel het defect. Druk op de 

"reset"-knop en schakel het apparaat 

opnieuw in. 

De oorzaak van de panne mag 

alleen bepaald worden door bekwaam 

personeel.

• Indien nodig kan de elektrische verwarmer uit 

het apparaat genomen worden. Koppel de 

verwarmingsbatterij daarvoor los van het 

elektriciteitsnet en verwijder de 

verwarmingsbatterij.  (afb. a-b)

Summary of Contents for RIRS 1200HE EKO 3.0

Page 1: ...sche gegevens te wijzigen Donn es techniques fr Technische handleiding nl Technical manual en Bedienungsanleitung de CENTRALES DE TRAITEMENT D AIR AVEC R CUP RATION DE CHALEUR LUCHTBEHANDELINGSGROEP M...

Page 2: ...branchement lectrique RIRS 1200HW EKO 3 0 33 Sch ma de branchement lectrique RIRS 1200HW EKO 3 0 2X230 34 Notes 35 Tableau d entretien du produit 36 Samenvatting 4 4 4 5 5 6 6 6 7 Elektrische verwarmi...

Page 3: ...ram RIRS 1200HW EKO 3 0 2X230 34 Notes 35 Product maintenance table 36 Inhalt Transport und Lagerung 4 Beschreibung 4 Schutzmassnahmen 4 Bestandeile des Ger tes 5 Betriebsbedingungen 5 Bedienung 6 Fil...

Page 4: ...bject make sure that any mechanical motion has stopped the heater has cooled down and the restart is not possible Do not connect to any other power voltage source than indicated on the model label Use...

Page 5: ...nit in potentially explosive environment Unit is designed to supply extract only clean air free of chemical compounds causing metal corrosion of substances aggressive to zinc plastic and rubber and of...

Page 6: ...ou de r paration s assurer que la cen trale est d connect e du r seau lectrique Ne commencer les travaux de maintenance qu l arr t de tout mouvement dans le ventila teur Respecter toutes les r gles de...

Page 7: ...uid as it can harm the heat exchanger It is NECESSARY to protect the motor of the heat exchanger from the moisture and liquid while cleaning the heat exchanger CAUTION It is forbidden to use the heat...

Page 8: ...retien suppl mentaire Il suffit de rem placer les filtres comme il est indiqu ci dessus Les batteries lectriques sont quip es de deux protections thermiques automatique qui se remet en marche automati...

Page 9: ...se de rotation rotatiesnelheid speed Drehzahl min 1 3400 insufflation Toevoer supply zuluft puissance courant vermogen stroom power current Nennleistung Nennstrom kW A 0 44 2 9 0 44 2 9 vitesse de rot...

Page 10: ...H mm 350 Profondeur Diepte Depth Tiefe L2 mm 46 Insufflation Toevoer supply Zuluft F7 Largeur Breedte Width Breite L mm 745 Hauteur Hoogte Height H he H mm 350 Profondeur Diepte Depth Tiefe L2 mm 46 M...

Page 11: ...external protective means must be fitted Die Montage darf nur durch ausgebildetes und eingewiesenes Fachpersonal durchgef hrt werden Das Ger t ist auf einer ebenen und horizontalen Oberfl che nicht g...

Page 12: ...automatique DTJ temp et capteur d humidit pour l air extrait PS1 Relai de pression d air souffl PS2 Relai de pression d air extrait IV Abluftventilator PV Zuluftventilator RR Rotorw rmetauscher R Mot...

Page 13: ...de changer c t service du dispositif c est dire il peut tre install avec une prise d air neuf droite ou une prise d air neuf gauche Il faut pour cela transposer les portes arri re et frontale La versi...

Page 14: ...14 www salda lt RIRS 1200HE EKO 3 0 RIRS 1200HW EKO 3 0 RIRS 1200HE EKO 3 0 2X230 RIRS 1200HE EKO 3 0 RIRS 1200HE EKO 3 0 2X230...

Page 15: ...erbatterij voor ronde ventilatiekanalen Round duct water heater Warmasserheizregister f r runde Kan le AVA Batterie eau AVA pour conduits de ventilation circulaires Waterkoeler voor ronde kanalen Circ...

Page 16: ...electric or water is switched on and operates heater valve is opened closed if water heater is used until the set temperature is reached When supply air temperature exceeds the set temperature the he...

Page 17: ...extracted air fans can be adjusted synchronously or asynchronously see sections II 6 7 and II 6 8 of the FLEX description If water supply air heater is used and after HVAC unit is switched on fans are...

Page 18: ...en Druckes im System zu steuern m ssen zwei Drucktauscher gebraucht werden Es ist auch eine M glichkeit vorgesehen den CO2 Tauscher Abluft anzuschlie en in dem Falle wenn die Drucktauscher nicht anges...

Page 19: ...beiten wird Diese Einstel lung kann ge ndert werden mehr dar ber Flex_meniu_montuotojas_LT Punkt 14 Misc ModBus Typ RTU F rs Anschlie en des ModBusses wird RS485_2 Anschluss gebraucht Abb 3 Einstellun...

Page 20: ...Niedrige Spannung fr Signal d alarme de la sonde de temp rature DTJ 100 nl Alarmsignaal van de temperatuursonde DTJ 100 1 en DTJ 100 temperature sensor alarm de DTJ 100 Temperatursensor Alarm fr Sign...

Page 21: ...nlage gew hlt werden falls die Speiseleitung der Anlage fern vom Aggregat ist ist es n tig den Abstand und Spannungs fall zu bewerten Die Anlage muss unbedingt geerdet werden Steuerpult muss auf dem v...

Page 22: ...erij When the water heater Wenn Wasserheizregister 4 0016A 0 1 2 0k X16 X16 BOOST START NC STOP NO Jumper valve actuator Water cooler Y1 Y2 G M5 24VAC 3 position Y1 OPEN 24VAC Y2 CLOSE 24VAC G System...

Page 23: ...enutzer nur durch entsprechend qualifizierte und geschulte Fachkr fte ausgef hrt werden Falls man w n scht dass das automatische Steuersystem von der L ftungsanlage richtig funktioniert muss sie entsp...

Page 24: ...verbindingen niet beschadigd zijn en Inspect sockets and plugs of connections Make sure that contacts are not damaged de Verbindungsdosen und stecker pr fen Sich vergewissern dass Anschlusskontakte ni...

Page 25: ...hanger le ventilateur Apr s l limination du disfonctionnement nl Controleer de elektrische verbindingen van de ventilator Controleer of de blazers van de ventilatoren goed werken of ze niet geklemd zi...

Page 26: ...Ontkoppel de juiste fiche uit het automaat Meet en controleer de weerstande van de sonde volgende de hieronder aangegevens afhankelijkheid Fig 1a Indien de verkregen resultaten niet overeenstemmen met...

Page 27: ...nl Controller RG1 27 www salda lt RIRS 1200HE EKO 3 0 RIRS 1200HW EKO 3 0 RIRS 1200HE EKO 3 0 2X230...

Page 28: ...loten LED2 LED3 Luchtklep open LED4 Waterventiel open LED5 Waterventiel gesloten LED6 BYPASS rotor open LED7 BYPASS rotor gesloten LED8 Maximale snelheid van de ventilatoren LED9 Mediumsnelheid ventil...

Page 29: ...warmwaterbatterij DX cooler or water heater circulatory pump control Kontrollieren des Freonk hlers bzw der Zirkulationspumpe von der Wasser Erw rmungseinrichtung X33 9 CHIL DO 0 05mA X33 10 COM COM...

Page 30: ...and humidity sensor for extract air Abluftfeuchte und Temperaturf hler X38 1 Sonde de temp rature de l air repris Vochtigheidsensor afvoerlucht Extract air temperature sensor Abzugsluft Temperatursen...

Page 31: ...le fabricant en indiquant le motif et livrer le dis positif l usine ses propres frais All equipment manufactured in our factory is pre run and tested before leaving and is shipped in good working orde...

Page 32: ...L1 PE N L1 L2 L2 L1 N PE L1 L2 L3 N PE 1 2 3 4 5 6 7 8 9 9 8 7 6 5 4 3 2 1 X4 X3 0 10V in GND IV K1 K1 L N PE L N PE PE N L PE N L K1 K1 PV GND 0 10V in X32 X33 A 0 10 COM X33 16 X33 15 X31 L K1 4 6 2...

Page 33: ...18 L N N L L 16 230V AC 230V AC ON OFF ON OFF X37 TL 1 3 4 2 LOW X32 1 COM X32 4 HIGH X32 2 TIMER X32 3 COM X33 1 MIDL X33 2 CHIL X33 9 COM X33 10 BOOST STOP NO START NC A2 A1 R1 8 7 X16 3 ALARM X33 1...

Page 34: ...Elektrisch verbindingsdiagram indien met elektrische batterij 34 www salda lt RIRS 1200HE EKO 3 0 RIRS 1200HW EKO 3 0 RIRS 1200HE EKO 3 0 2X230...

Page 35: ...Nota s nl 35 www salda lt RIRS 1200HE EKO 3 0 RIRS 1200HW EKO 3 0 RIRS 1200HE EKO 3 0 2X230...

Page 36: ...ce du produit NOOT De koper is verplicht om de Onderhoudstabel van het product in te vullen NOTE The purchaser is required to fill in the Product maintenance table HINWEIS Der K ufer ist verpfl ichtet...

Reviews: