Advanced Program Group
51
A401 [Accel Time 2]
Related Parameter(s):
P109
When active, sets the rate of acceleration for all speed increases except jog. Refer to the flowchart on
page 1-20
for details.
Maximum Freq / Accel Time
=
Accel Rate
Values
Default
20.0 Secs
Min/Max:
0.1/ 600.0 Secs
Display:
0.1 Secs
A402 [Decel Time 2]
Related Parameter(s):
P110
When active, sets the rate of deceleration for all speed decreases except jog. Refer to the flowchart on
page 1-20
for details.
Maximum Freq / Decel Time=Decel Rate
Values
Default
20.0 Secs
Min/Max:
0.1/ 600.0 Secs
Display:
0.1 Secs