VG5 Installation & Quick-Start Manual
103
Pr
otec
tion
Fu
nc
tio
n L6 T
or
que De
tec
tio
n
L6-02
Overtorque
Detection Level 1
(Torq Det 1 Lvl)
0~300
1%
150
—
x B B B B
L6-03
Overtorque
Detection Time 1
(Torq Det 1 Time )
0.0~
10.0
0.1s
0.1
—
x B B B B
L6-04
Overtorque
Detection
Selection 2
(Torq Det 2 Sel)
0~4 1 0
0: (Disabled)
1: (@SpdAgree - Alm)
Detected during speed
agree only. Operation con-
tinues after detection and
OL4 flashes on display.
2: (At RUN - Alarm)
Overtorque detection during
running. Operation contin-
ues after detection and OL4
flashes on the display.
3: (@SpdAgree - Flt)
Detected during the speed
agree only. Inverter trips on
OL4, output is shut OFF.
4: (At RUN - Fault)
Detected during running,
and the inverter trips on
OL4. Output is shut OFF.
x A A A A
L6-05
Overtorque
Detection Level 2
(Torq Det 2 Lvl)
0~300
1%
150
—
x A A A A
L6-06
Overtorque
Detection Time 2
(Torq Det 2 Time)
0.0~
10.0
0.1s
0.1
—
x A A A A
Fun
cti
on L7
T
orque
Li
mi
t
L7-01
Forward Torque
Limit
(Torq Limit Fwd)
0~300 1% 200
—
x
-
- B B
L7-02
Reverse Torque
Limit
(Torq Limit Rev)
0~300 1% 200
—
x
-
- B B
L7-03
Forward Regenera-
tive Torque Limit
(Torq Lmt Fwd Rgn)
0~300 1% 200
—
x
-
- B B
L7-04
Reverse Regenera-
tive Torque Limit
(Torq Lmt Rev Rgn)
0~300 1% 200
—
x
-
- B B
Function
Parameter
No.
Name
(Digital Operator
Display)
Setting
Range
Setting
Unit
Factory
Setting
Remarks
(Digital Operator Display)
Change
during
Operation
o: Enabled
x: Disabled
Parameter Access Level
User
Setting
V/f
V/f
w/
PG
Open
Loop
Vector
Flux
Vector
Appendix
VG5 Parameters
Summary of Contents for CIMR-VG5
Page 2: ...2 VG5 Installation Quick Start Manual This page intentionally left blank...
Page 36: ...36 VG5 Installation Quick Start Manual This page intentionally left blank...
Page 60: ...60 VSG5 Installation Quick Start Manual This page intentionally left blank...
Page 113: ...VG5 Installation Quick Start Manual 113 This page intentionally left blank Appendix Notes...