VG5 Installation & Quick-Start Manual
109
CE CONFORMANCE - Electro-Magnetic Compatibility (EMC) Compliance
In order to conform to EMC standards, exclusive-use methods are required for line filter applica-
tion, cable shielding and inverter installation. An outline of the methods follows.
The line filter and the inverter must be mounted on the same metal plate. The filter should be
mounted as close to the inverter as practical. Keep cable as short as possible. The metal plate should
be securely grounded. The ground of the line filter and inverter must be bonded to the metal plate
with as much area as possible.
For line power input cable, screened cable is recommended at least within the panel. The screen of
the cable should be connected to a solid ground. For the motor cable, screened cable (max. 20m)
must be used and the screen of the motor cable is connected to ground at both ends by a short con-
nection, using as large an area as practical.
The following table and figures show the line filter list for EMC standards and the installation/wir-
ing of inverter and line filter.
Line Filter List for EMC Standards
Inverter
Model
CIMR-
VG5Uxxxx
Line Filter (Manufactured by Schaffner)
Model
Rated
Current
(A)
Mass
(kg)
Dimensions (mm)
W
D
H
40P4
FS4874-7/07 7 1.1
50
126
255
40P7
41P5
42P2
FS4874-18/07 18 1.7 55
142
305
43P7
44P0
45P5
FS4874-30/07 30 1.8 60
150
335
47P5
4011
FS4874-42/07 42 2.8 70
185
329
4015
4018 FS4874-55/07 55 3.1 80
185
329
4022
FS4874-75/34 75 4.0 80
220
329
4030
4037 FS4874-100/35 100 5.5 90
220
379
4045 FS4874-130/35 130 7.5 110
240
429
4055 FS4874-180/07 180 11 110
240
438
4075 FS4874-300/99 300 15 300
564
160
4110
FS4874-400/99 400 22 300
564
160
4160
4185 FS4874-500/99 500 19.5 300
564
160
4220 FS4874-600/99 600 20.5 300
564
160
4300 FS4874-900/99 900 33.5 300
564
160
Appendix
CE Conformance Information
Summary of Contents for CIMR-VG5
Page 2: ...2 VG5 Installation Quick Start Manual This page intentionally left blank...
Page 36: ...36 VG5 Installation Quick Start Manual This page intentionally left blank...
Page 60: ...60 VSG5 Installation Quick Start Manual This page intentionally left blank...
Page 113: ...VG5 Installation Quick Start Manual 113 This page intentionally left blank Appendix Notes...