User Manual of HD-TVI Speed Dome
32
3.
Configure the alarm rest delay.
If there
’
s a linkage action has already been triggered by an alarm input, the speed dome will
only respond to the input from the same channel again after the user-defined reset delay time
.
This is the rest time that the speed dome considers an alarm to be active when it
’
s physically
cleared. You can set the
DELAY TIME
from 0 to 300 seconds.
4.
Resume the dome activity.
You can set
ALARM RESUME
to
ON
to enable the speed dome to resume its previous activity
after the triggered actions finished.
⚫
If the speed dome is moving when a linkage action is triggered, it will stop at the current
position and resume from this position after the linkage action finishes.
⚫
The speed dome can be configured to resume the PTZ positions, focus and iris value.
3.5.3
Configuring Alarm Output
Purpose:
An alarm output is a configurable alarm output interface on the speed dome back box which can
connect and trigger another alarm device to operate.
Steps:
1.
Enter the alarm output configuration submenu:
MAIN MENUS > DOME SETTINGS > ALARM OUTPUT
ALARM OUTPUT
ALARM OUTPUT 1 CLOSE
DWELL TIME 2
ALARM OUTPUT 2 OPEN
DWELL TIME 0
BACK EXIT
Figure 3-21
Configure the Alarm Output
2.
Click
IRIS+
to edit the status of the alarm outputs. You can set the alarm output type as
OPEN
(normally open) and
CLOSE
(normally closed).
There is 1 alarm output configurable; configuring the alarm output 2 will be invalid.
3.
Move the cursor to
DWELL TIME
to set the duration of the alarm output signal. The configurable
rage is 0~60 seconds.
4.
Link the alarm output to the configured alarm.
Steps:
(1)
Enter
MAIN MENUS > DOME SETTINGS > ALARM INPUT > ALARM SETTING
and choose the
alarm number that you want to link the alarm output to.