10 SETUP MENU
6 DISPLAY
Par
Description
Units
VALUES
Notes
Default Min. Max.
6.7 Digital input 2
Indicates whether input 2 is enabled or not;
if it is enabled, the reason for this.
6.8 Relay 1 output
Indicates whether relay 1 is enabled or not;
if it is enabled, the reason for this.
6.9 Relay 2 output
Indicates whether relay 2 is enabled or not;
if it is enabled, the reason for this.
6.10 Software version
Indicates the version of the software of the
control panel (screen) and the power panel
(aluminium radiator).
6.11 Power consumed by pump
W
Indicates the instantaneous power
consumed by the pump.
6.12 Power consumed by network
W
Indicates the instantaneous power
consumed by all the pumps that are
operating at that time.
7 LOG
Shows a log of anomalies of the pump where the speed variator is connected, indicating the date, the time
and the anomaly that occurred. This information is very important for detecting possible anomalies in the
functioning of the installation.
8 INPUTS OUTPUTS
Par
Description
Units
VALUES
Notes
Default Min. Max.
8.1 Digital input 1
Unused
Unused /
Emergency
stop / Forced
start
An input can be enabled to carry out a
remote stop or to force the pump to start,
even though it is out of reach of a filtration
cycle.
Important: Input 1 is a normally open input,
therefore to enable it the contact must be
closed without voltage.
8.2 Input 1 frequency
Hz
50
10
50
If digital input 1 is activated for forced
operation, you can indicate the frequency at
which you want the pump to function when
the input is enabled.
8.3 Digital input 2
Unused
Unused /
Emergency
stop / Forced
start
A second input can be enabled to carry out
a remote stop or to force the pump to start,
even though it is beyond the scope of a
filtration cycle.
Important: Input 2 is a normally open input,
therefore to enable it the contact must be
closed without voltage.
8.4 Input 2 frequency
Hz
50
10
50
If digital input 2 is activated for forced
operation, you can indicate the frequency at
which you want the pump to function when
the input is enabled.
VSD Magnus - [e]Magnus
VSD Magnus - [e]Magnus
Summary of Contents for VSD magnus
Page 2: ...VSD Magnus e Magnus...
Page 148: ...148 10 40 10 30 mA B V 3 50 60Hz400 Hz 50Hz10 A 11 IP 55 A 3 2 VSD Magnus e Magnus...
Page 149: ...149 2 2 1 1 x400V3 4 5 2 1 24 Vdc 9 2 1 2 8 Va2030 BACK WASH VSD Magnus e Magnus...
Page 150: ...150 BACK WASH F1 F2 POWER RUN ALARM back wash 5 VSD Magnus e Magnus...
Page 153: ...153 r a B 0 4 F12 1 5 F12 1 6 8 8 8 VSD Magnus e Magnus...
Page 161: ...161 10 90 50 75 9 6 10 1 2 9 7 9 8 9 9 9 10 9 11 9 VSD Magnus e Magnus...
Page 162: ...162 11 4 5 F01 F02 F03 F04 F06 F07 X13 BACK WASH VSD Magnus e Magnus...