13 SELECTING THE OPERATING
VOLTAGE OF VALVE ACTUATORS
The control is able to manage both valves on / off at
230 Vac that 3 points 24 Vac.
230 Vac
24 Vac
13.1 Configuration for 24 Vac 3 point
actuators
24 Vac
In order to use 24 Vac 3 point actuators you need
to connect the jumper supply valves to the M17
connector.
Using the configuration for 24 Vac actuators
it is mandatory to place the cover on the M14
clamp.
13.2 Configuration for ON-OFF 230 Vac
actuators
230 Vac
To use the oN/oFF 230 Vac actuators it is mandato-
ry to connect the jumper supply valves to the M14
connector