Energy Plus
35
WATER COIL
Water
inlet
Water
outlet
Condensate drain
Duct fitted by the installer
Condensate
drain
Duct fitted by the installer
Water
outlet
Water
inlet
Air flow (m
3
/h)
Air flow (m
3
/h)
Pressure drop (Pa)
Pressure drop (Pa)
Air side pressure drop
ENY–P1 / ENY–P2
ENY–P3 / ENY–P4
It consists of a galvanised steel structure insulated externally
complete with circular flanges which facilitate its connection to the
heat recovery unit or application to the circular duct. The interior
of the section is fitted with a finned coil mounted on a special
supporting frame made of galvanised sheet metal, expanded 3/8”
copper tubes, aluminium fins pitch 2.5 mm, brass manifolds
protruding at the sides. The interior of the section contains the
condensate collection tray with 16 mm drain fitting. The treatment
section is suitable both for post-heating and for cooling the intake
air. The sections of post-treatment valves can be managed by the
main board. The valves are open when the setpoint of the winter or
summer cooling temperature on return air is not reached and closed if it
is.
COLD
HOT
Inverted-flow version