Energy Plus
29
ELECTRIC
ANTIFREEZE COIL
BEP
(to be placed on the "External air"
intake duct)
Electric heating coil consisting of armored
elements inserted inside a galvanised sheet
metal duct section with circular flanges and
rubber gasket. The electric coil can be used
in premises with air temperature between
-20° C and +40° C and is equipped with double
safety thermostat: one with automatic reset
and one with manual reset. The purpose of
the pre-heating resistance is to prevent the
heat exchanger from freezing and is controlled
from the control board with PWM modulating
logic in order to maintain the exaust air temperatu-
re over the freezing value. Protection class IP 43.
0
2
4
6
8
10
12
14
16
18
0
500
1000
1500
2000
2500
3000
BEP40/9
BEP35/5
BEP25/2
BEP25/3
0
2
4
6
8
10
12
14
16
18
0
500
1000
1500
2000
2500
3000
BEP40/9
BEP35/5
BEP25/2
BEP25/3
c
ode
9022113
9022213
9022313
9022413
2,1
230V 50Hz 1Ph + Pe
3,0
400V 50Hz 3Ph + Pe
6,0
9,0
9,1
13,0
8,7
13,0
250
250
355
400
270
300
600
690
kW
V/Hz/Ph
A
mm
m
3
/h
Rated power
Power supply voltage
Amperes absorbed by the resistance
Circular Flange Diameter
D
Minimum air flow rate
BEP 25/2/M
BEP 25/3/M
BEP 35/6/T
BEP 40/9/T
ENY–P1
ENY–P2
ENY–P3
ENY–P4
f
or
heaT
recovery
uniT
resisTance
i
denTificaTion
0
2
4
6
8
10
12
14
16
18
0
500
1000
1500
2000
2500
3000
BEP40/9
BEP35/5
BEP25/2
BEP25/3
Air flow rate (m
3
/h)
Pressure drop (Pa)
Pressure drop
BEP
Fresh air
Duct fitted
by the installer
AIR