3.4.2
Device Settings
The device settings contain data to configure the device and the user interface. This registers are also accessible
through the button interface in administration-mode. The data is stored persistently and will be preserved during
power loss.
Register Name
Register
Address
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
modbus_parameter
176
0x00B0
R
[0]
R
[0]
PAR
[0x2]
modbus_baud
[0x6]
device_addr
[0x01]
This register contains the configuration for the Modbus port of the Rymaskon 200.
!!!
Compare Table 4 on Page 15 for device settings editable via the user interface.
PAR
: defines the parity bit used for Modbus communication. Valid are:
0x0 – odd (odd parity bit, 1 stop bit)
0x1 – even (even parity bit, 1 stop bit)
0x2 – none (no parity bit, 2 stop bits)
modbus_baud
: defines the Modbus baudrate, following values are valid:
0x0 – 1200
0x1 – 2400
0x2 – 4800
0x3 – 9600
0x4 – 19200
0x5 – 38400
0x6 – 57600
0x7 – 115200
device_addr
: defines the Modbus slave address.
Valid addresses are 1(0x01) to 247 (0xF7).
Table 18: Modbus Parameter
Register Name
Register
Adresse
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
pincode_
system_administrator
177
0x00B1
R
[0]
R
[0]
[0x0000]
pincode_
end_user
178
0x00B2
R
[0]
R
[0]
[0x0000]
pincode_system_administrator defines the pincode for the system administrator.
If set to 0000 the pincode is disabled. Possible values are 0000 (0x0000) to 9999 (0x270F).
pincode_end_user defines the pincode for the end user.
If set to 0000 the pincode is disabled. Possible values are 0000 (0x0000) to 9999 (0x270F).
!!!
Compare Table 4 on Page 15 for device settings editable via the user interface.
Table 19: Pincodes