RYM
ASKON
®
200-Modbus
Modbus Slave
User Manual
© S+S REGELTECHNIK GMBH
| THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |
Page 25 of 55
Register Name
Register
Address
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
direct_value
104
0x0068
[0x0000]
direct_value_config
105
0x0069
EN
[0]
R
[0]
R
[0]
R
[0]
R
[0]
R
[0]
R
[0]
R
[0]
R
[0]
R
[0]
unit
[0x0]
exp
[00]
These registers are used to display specific values instead of display_values or set_points. For an
overview on how to setup the configuration please refer to Figure 7 on Page 18.
!!! If disabled, the last viewed value will be visible again as defined with the
user_interface_direct_access register at adderss 101 (Table 13 on Page 23).
direct_value:
16 bit signed integer to be displayed
EN:
direct value enable bit (1 – enabled, 0 – disabled)
unit:
defines a unit symbol to be displayed, following values are possible:
0x0 0x1 0x2 0x3 0x4 0x5 0x6
0x7
0x8 0x9
0xA
0xB
no
unit
°C
°F
cfm
l/s
m³/h Pa
inWC
V
%
%RH ppm
exp:
exponent, defines the number of decimal places:
00 – no decimal point
01 – one decimal place
10 – two decimal places
11 – three deciml places
Table 15: Direct Value
Register Name
Register
Address
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
system_time
112
0x0070
system_time_0
[0x0000]
113
0x0071
system_time_1
[0x0000]
system_time
represent a 32 bit timestamp in seconds since JAN-01-1970. The timestamp has to be
initially set by the Modbus master because the device has no back-up battery and so it would start at 0
(00:00:00 JAN-01-1970) after a reboot.
The timestamp is incremented by the device but anyway it has to be set by the master at defined intervals
to prevent time offsets.
Table 16: System Time