![S+S Regeltechnik Rymaskon 200-Modbus Series User Manual Download Page 33](http://html1.mh-extra.com/html/s-s-regeltechnik/rymaskon-200-modbus-series/rymaskon-200-modbus-series_user-manual_3093030033.webp)
RYM
ASKON
®
200-Modbus
Modbus Slave
User Manual
© S+S REGELTECHNIK GMBH
| THURN-UND-TAXIS-STR.22 | 90411 NÜRNBERG | GERMANY | FON +49(0)911 519470 |
Page 33 of 55
Description
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
no special function
0
0
0
0
0
0
0
1
0
➔
The button is enabled but has no special function (e.g. OCCUPANCY-button). The set point index has no
influence in this case.
MENU-button
0
0
0
0
0
1
0
1
0
➔
This combination can be used to determine the MENU-button. The set point index has no influence in this
case.
UP-button
0
0
1
0
1
0
0
1
0
➔
This button will increment a set point in EDIT- or DIRECT_ACCESS-mode when pressed. The set point
index has no influence in this case.
DOWN-button with
direct access
1
1
0
1
0
0
0
1
0
➔
This button will decrement a set point in EDIT- or DIRECT_ACCESS-mode when pressed. Additionally
a setpoint defined with the set_point_index is displayed when pressed and can be edited in
DIRECT_ACCESS-mode.
Table 25: Button Example Configuration
Register Name
Register
Address
Bit Position
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
config_bar_graph_left
240
0x00F0
R
[0]
R
[0]
R
[0]
R
[0]
R
[0]
R
[0]
R
[0]
EN
[0]
set_point_index
[0x00]
config_bar_graph_right
241
0x00F1
R
[0]
R
[0]
R
[0]
R
[0]
R
[0]
R
[0]
R
[0]
EN
[1]
set_point_index
[0x01]
These registers are used to associate a set point as source for the bar graph on the left and on the right side
of the LCD. If enabled the bar graph is updated corresponding to the value of the set point defined with
the set_point_index.
The bar graph segments can also be set manually by writing the symbol_direct_access registers at address
99 and 100 ( Table 12 on Page 23)
set_point_index
:
defines a set point register that is used as source for the bar graph.
EN
: if set to ‘1’ the corresponding bar-graph will be updated to visualize the value of
a set point with the defined set_point_index.
Table 26: Bar Graph Configuration