Specifications
7.1.
Physical Specifications
Operating Voltage
24 V DC (±10 %)
Power Consumption
max. 0.8 W
In rush current
up to 4A (at 24 V DC)
Operating range, temperature
0....+50
C
Operating range, humidity
10... 90 % r.H. (without dew formation)
Dimensions
94.5 x 110 x 19.5mm
Protection type
IP 30 (according to EN 60529)
Installation
using a plastic mounting plate, on in-wall flush box, Ø 55 mm
Following Table 40 should provide support for dimensioning of an installation and the power supply. For each
device type there is a listing for up to 16 devices of the maximum possible cable length and the resulting power
loss on the cable for different supply voltage levels. Together with the power consumption of the devices one can
calculate the required power of the power supply.
Conditions of the Installation
Number of Devices
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
R
Y
M
A
S
K
O
N
2
0
0
maximum power
consumption of devices
[W]
0,8
1,6
2,4
3,2
4,0
4,8
5,6
6,4
7,2
8,0
8,8
9,6
10,4
11,2
12,0
12,8
24V
DC
max. Cable length
[m]
for 0,5mm²
1.620
810
540
400
320
270
230
200
180
160
140
130
120
110
100
100
for 1,0mm²
3.250
1.620 1.080
810
650
540
460
400
360
320
290
270
250
230
210
200
max. Power loss on
cable
[W]
0,2
0,4
0,6
0,9
1,1
1,3
1,5
1,7
1,9
2,1
2,3
2,6
2,8
3,0
3,2