The calibratable
PREMASGARD
®
114x
series compact pressure sensors are equipped with eight switchable measuring ranges and with or without
optional display (eight devices in one) and are used for measuring above-atmospheric, below-atmospheric, or differential pressures in air. The
piezoresistive measuring element is temperature-compensated and guarantees a high degree of reliability and accuracy. These pressure transmitters
have a pushbutton for manual zero point calibration and an adjustable offset. Applications of these pressure sensors are in clean room, medical and
filter technology, in ventilation and air conditioning ducts, in spray booths, in large-scale catering facilities, for monitoring filters, for level measurement,
or for triggering frequency converters. Media measured with these pressure transducers are air (non-precipitating), or other gaseous non-
aggressive, non-combustible media. The pressure sensor has eight selectable measuring ranges and therefore, minimizes the diversity of types and
inventory levels while covering a greater range of applications. The differential pressure sensor is supplied including connection set
ASD-06
(2 m
connection hose, two pressure connection nipples, screws).
Electronic pressure sensors and switches
PREMASREG
®
114x
are equipped with eight switchable measuring ranges, one switching output and one
continuous output, and a display for setting the switchpoint and to display the ACTUAL pressure (eight devices in one, plus differential pressure
switch ⁄ differential pressure monitor, continuous pressure sensor in a single device). The pressure sensor is used for above-atmospheric, below-
atmospheric, or differential pressure measurement in clean air with limit value switching. The piezo-resistive measuring element guarantees a high
degree of reliability and accuracy. Applications of these pressure sensors are in clean room, medical and filter technology, in ventilation and air
conditioning ducts, in spray booths, in large-scale catering facilities, for monitoring filters, for level measurement, or for triggering frequency
converters. Media measured with these pressure transducers are air (non-precipitating), or other gaseous non-aggressive, non-combustible media.
The pressure sensor has a manual zero point pushbutton and an offset potentiometer for final value and switchpoint correction. Fine adjustment by
the user is possible at any time. A connection set
ASD-06
(2 m connection hose, two pressure connection nipples, screws) is included in the scope
of supply.
TECHNICAL DATA
Power consumption:
< 1 VA ⁄ 24 V DC, < 2.2 VA ⁄ 24 V AC
Measuring ranges:
multi-range switching with 8 switchable measuring ranges
(see table)
Media temperature:
–20...+ 50 °C
Pressure connection:
4 ⁄ 6 x 11 mm (hoses Ø = 4 ⁄ 6 mm), metal pressure connection nozzles
Type of pressure:
differential pressure
Medium:
clean air and other non-aggressive, non-combustible gases
Above- ⁄ below-atmospheric pressure:
max. ± 200 hPa
Signal filtering:
switchable 1 s ⁄ 10 s
PREMASGARD
®
114x
Power supply:
24 V AC (± 20 %); 15...36 V DC for U variant
15...36 V DC for I variant, depending on working resistance, residual ripple stabilised ± 0.3 V
Working resistance:
R
a
(ohm) = (U
b
-14 V) ⁄ 0.02 A for I variant
Load resistance:
R
L
> 5 kOhm for U variant
Output signal:
0 -10 V or 4 ... 20 mA
Electrical connection:
2- or 3-wire connection
Accuracy:
Type 1140
(100 Pa): ± 2 Pa with display / ± 3 Pa without display
Type 1141
(1000 Pa): ± 5 Pa with display / ± 10 Pa without display
Type 1145
(5000 Pa): ± 25 Pa with display / ± 50 Pa without display
compared to the calibrated reference device
Sum of Lihysteresis:
< ± 1 % of final value with display
< ± 2 % of final value without display, standard (optional ± 1 % of final value)
Temperature drift values:
± 0.1 % ⁄ °C with display
± 0.3 % ⁄ °C without display
Zero point offset:
< ± 0.7 % of final value with display
< ± 1.5 % of final value without display
PREMASREG
®
114x
Power supply:
24 V AC ⁄ DC (± 20 %)
Load resistance:
R
L
> 5 kOhm
Output signal:
0 -10 V;
1 changeover contact (24 V), 1 A ohmic load
Electrical connection:
3-wire connection (U)
Accuracy:
Type 1141
(1000 Pa): ± 5 Pa
Type 1145
(5000 Pa): ± 25 Pa
compared to the calibrated reference device
Sum of Lin hysteresis:
< ± 1 % of final value
Temperature drift values:
± 0.1 % per °C
Zero point offset:
< ± 0.7 % of final value
Enclosure:
plastic, UV-stabilised, material polyamide, 30 % glass-globe reinforced, colour traffic white (similar to RAL 9016)
Dimensions:
108 x 70 x 73.5 mm (Thor 2)
Electrical connection:
0.14 - 1.5 mm², via
removable plug-in screw terminals
Cable gland:
M 16 x 1.5; including strain relief
Humidity:
< 95 % r.H., non-precipitating air
Protection class:
III (according to EN 60 730)
Protection type:
IP 65 (according to EN 60 529)
Standards:
CE conformity, according to EMC directive 2014 ⁄ 30 ⁄ EU, according to EN 61326-1, according to EN 61326-2-3
Features: two-line
display with illumination
, cutout approx. 36 x 15 mm (W x H), for displaying ACTUAL pressure and ⁄ or
SETPOINT pressure or undercutting or exceeding the measuring range
ACCESSORIES
ASD - 06
Connection set (nipple straight) – (included in the scope of delivery)
ASD - 07
Connection nipple (at 90° angle)
DAL-01
Pressure outlet for ceiling or in-wall installation (e.g. in clean rooms)
WS-04
Weather and sun protection, 130 x 180 x 135 mm, stainless steel