G  

Installation and Commissioning 

Rev.  2020 - V22

Display readout

The 

1st line

 of the display shows the 

ACTUAL humidity

 in % r.H. and the 

ACTUAL 

temperature

 in °C. The displays showing the ACTUAL values alternate in a 3-second 

rhythm. Resolution: 1/10  % r.H. or 1/10 °C.
The 

2nd line

 shows information about the 

switching status of the relay

 (as a circuit), 

and indicates the  

switching value

 in % r.H. or °C (adjustable via the corresponding set 

potentiometer). The readouts of the switching thresholds for the first and second relay 
are displayed alternately at an interval of twenty seconds. For improved legibility,  
backlighting is provided.

Zero point calibration

The sensors are pre-set and calibrated at the factory. Adjustment is possible either for 
temperature or relative humidity, depending on the output allocation (DIP switch 3).  
Range  of  adjustment:  approx.  ± 10 %  r.H.  or  ± 5 K. 

Internal setting of the switching value for relay 1      (at  RHT - 30  WU)

The variant without a potentiometer leading out to the thumb wheel requires the 

switching 

value for relay 1

 to be set using the inserted direction of rotation indicator.  

If the notch is pointing upwards, the switching value is set to 50 % r.H. or + 25 °C. 
The left stop defines the switching value to 5 % r.H. or + 5 °C, 
the right stop defines it to 95 % r.H. or + 45 °C.

See illustration on last page!

Switching output

  RHT - 30

Mode  1:   

Independent switchpoints for both relay outputs can be defined in the range of 5...95 %  r.H. by the control knobs (setpoint 1 for relay 1, set-

point 2 for relay 2, see schematic diagram). When the respective switchpoint is exceeded, the corresponding relay switches over (changeover contact  1 

switches from position  2 to position  3). When the pre-set switchpoint is undershot again by more than 3 %  r.H. (hysteresis), the respective switching 

output switches back to the initial position (changeover contact 1 switches from position  3 to position  2). 

Mode  2:   

In Mode 2, only control knob setpoint 1 is active (setpoint 2 without function)! The switchpoint for the first relay is defined in the range of 

5...95 %  r.H. by the control knob setpoint  1 (see schematic diagram). The switchpoint for the second relay output is invariably defined in mode 2  

as "Switchpoint 1 + 5 %  r.H.". Hysteresis of 3 %  r.H. is also predefined for each switching output in mode  2. 

Mode  3:   

Independent switchpoints for both relay outputs can be defined in the range of +5...+45 °C r.H. by the control knobs (setpoint 1 for relay 1, 

setpoint 2 for relay 2). If the respective switchpoint is exceeded, the corresponding relay switches over. If the pre-set threshold value is undershot again 

by 1 K (hysteresis), the respective switching output switches back to the initial position. The thresholds of the setting range (temperature) are 5 °C 

above the minimum or below the maximum range value respectively.

Mode  4:   

In mode 4, the control knob is allocated to setpoint 1 of the temperature, while control knob is allocated to setpoint 2 of the relative humidity. The 

switchpoints can be adjusted in the range of +5...+45 °C or 5...95 % r.H. The thresholds of the setting range (temperature) are 5°C above  

the minimum or below the maximum range value respectively. The control knob for the temperature can be operated from outside, if necessary. 

11

12 13

11

12 13

Gone below

preset

switchpoint

threshold

Preset

switchpoint

threshold

exeeded

Falls below 

the preset value with

3% r.H./1K hysteresis

Exceeding 

the preset value

Hysteresis

3% r.H./1K

Switching output 1

°C / % r.H.

21

22 23

21

22 23

Gone below

preset

switchpoint

threshold

Preset

switchpoint

threshold

exeeded

Falls below 

the preset value with

3% r.H./1K hysteresis

Exceeding 

the preset value

Hysteresis

3% r.H./1K

Switching output 2

°C / % r.H.

Relay switching value

Relay switching status  (

 ⁄ 

○)

Relay  displayed    (1 ⁄  2)

 

Circuit, empty

  =   

relay in idle state

 

 Circuit, full

  =   

 relay energised

Supply

AC

DC

→   1

24 V∼

24 V  DC

→   3

0 V

GND

12

 

(A1) →

Relay 1

  Breaker contact

11

  (W1) →

Relay 1

  Changeover contact

13

 

(B1) →

Relay 1

  Normally open contact

22

 

(A2) →

Relay 2

  Breaker contact

21

  (W2) →

Relay 2

  Changeover contact

23

 

(B2) →

Relay 2

  Normally open contact

DIP switches 

RHT

 

- 30

Function mode

DIP 1

DIP 2

Mode 1

  (

2x 

  5...95 % r.H.)  (default)

OFF

OFF

Mode 2

  (5...95 % r.H. 

+  5 %

 r.H.)

O N

OFF

Mode 3

  (

2x 

  +5...+45 °C)

OFF

O N

Mode 4

  (5...95 % r.H. / +5...+45 °C)

O N

O N

Output

DIP 3

Temperature

O N

Relative humidity  (default)

OFF

Backlighting

DIP 4

activated

O N

deactivated  (default)

OFF

Summary of Contents for HYGRASREG RHT-30 Series

Page 1: ...schaltenden Ausgang G Operating Instructions Mounting Installation Room hygrostats and humidity and temperature sensors 2 0 electronic two step with continuous switching outputs F Notice d instruction...

Page 2: ...HYGRASREG RHT 30 D G F r Ma zeichnung RHT 30 Dimensional drawing Plan cot T K 6 0 98 98 32 6 34 6 RHT 30U mit Inneneinstellung with internal setting avec r glage interne...

Page 3: ...ur Lagerung 35 85 C Betrieb 30 70 C nicht kondensierend Langzeitstabilit t 1 Jahr Geh use Kunststoff Werkstoff ABS Farbe Reinwei hnlich RAL 9010 Abma e Geh use 98 x 98 x 35 mm Baldur 2 Montage Wandmon...

Page 4: ...festgelegt Der Schaltpunkt des zweiten Relaisausganges ist im Mode 2 immer mit Schalt punkt 1 5 r H festgelegt Auch im Mode 2 ist f r jeden Schaltausgang eine Hysterese von 3 r H vorgegeben Mode 3 F...

Page 5: ...ntfallen alle Gew hrleistungsanspr che Dieses Ger t darf nicht in der N he von W rmequellen z B Heizk rpern oder deren W rmestrom eingesetzt werden eine direkte Sonnen einstrahlung oder W rmeeinstrahl...

Page 6: ...5 C operation 30 70 C non precipitating Long term stability 1 per year Housing plastic material ABS colour pure white similar to RAL 9010 Housing dimensions 98 x 98 x 35 mm Baldur 2 Installation wall...

Page 7: ...rol knob setpoint 1 see schematic diagram The switchpoint for the second relay output is invariably defined in mode 2 as Switchpoint 1 5 r H Hysteresis of 3 r H is also predefined for each switching o...

Page 8: ...by the user all warranty claims are forfeited This device must not be installed close to heat sources e g radiators or be exposed to their heat flow Direct sun irradiation or heat irradiation by simi...

Page 9: ...umidit typique 2 0 20 80 h r 25 C sinon 3 0 cart temp rature typique 0 2K 25 C Temp rature ambiante stockage 35 85 C fonctionnement 30 70 C sans condensation Stabilit long terme 1 an Bo tier mati re p...

Page 10: ...ar le potentiom tre setpoint 1 voir sch ma de raccordement dans une plage allant de 5 95 h r En mode 2 le point de commutation de la deuxi me sortie relais est toujours d termin comme point de commuta...

Page 11: ...tinue de nos produits En cas de modifications des appareils par l utilisateur tous droits de garantie ne seront pas reconnus Cet appareil ne doit pas tre utilis proximit des sources de chaleur par ex...

Page 12: ...5 C 30 70 C 1 ABS RAL 9010 98 x 98 x 35 Baldur 2 55 III EN 60 730 IP 30 EN 60 529 0 14 1 5 2 CE 2014 30 EU 36 x 15 x 1 11 12 3 1 S1 11 12 2 21 22 3 1 S2 21 22 2 1 11 13 S1 11 13 2 21 23 S2 21 23 2 HYG...

Page 13: ...below the preset value with 3 r H 1K hysteresis Exceeding the preset value Hysteresis 3 r H 1K Switching output 1 C r H 21 22 23 21 22 23 Gone below preset switchpoint threshold Preset switchpoint th...

Page 14: ...r ZVEI VDE EMV 0 10 0 UB 15 36 UB GND 24 Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15 36V GND...

Page 15: ...te of publication They are only meant to inform about our products and their application potential but do not imply any warranty as to certain product characteristics Since the devices are used under...

Page 16: ...umidifying Cooling 1 2 3 12 11 13 22 21 23 Befeuchten Heizen Relais 1 Entfeuchten K hlen Befeuchten Heizen Relais 2 Entfeuchten K hlen potentialfreier Wechsler 24V UB 24V AC DC Ausgang 0 10V UB GND mi...

Reviews: