background image

12

HYGRASGARD

®

    FSFTM - Modbus

  |  Configuration

 

Rev.  2018 - V16  intro

BUS ADDRESS

Bus address  

(binary coded, value selectable from 1 to 247)

MODBUS

DIP switch [A]

DIP 1 

DIP 2

DIP 3 

DIP 4 

DIP 5 

DIP 6 

DIP 7

DIP 8 

1 2 3 4 5 6 7 8

ON

DIP A

128

64

32

16

8

4

2

1

O N

O N

OFF

OFF

OFF

OFF

OFF

O N

Example shows  128 + 64 + 1 = 193  as Modbus address.

The 

device address

 in the range of 

1 to 247

 is set at DIP switch [A].  

For switch positions 1 to 8 see the table on the back!
Address 0 is reserved for broadcast messages. Addresses greater than 247 must not be assigned  
and are ignored by the device. The DIP switches are binary-coded with the following values:
DIP 1 = 

128

 ............  DIP 1 = 

ON

 

DIP 2 = 

64

 ............  DIP 2 = 

ON

 

DIP 3 =  32 ............  DIP 3 = OFF 
DIP 4 =  16 ............  DIP 4 = OFF 
DIP 5 = 

8 ............  DIP 5 = OFF  

DIP 6 = 

4 ............  DIP 6 = OFF  

DIP 7 = 

2 ............  DIP 7 = OFF 

DIP 8 = 

1

 ............  DIP 8 = 

ON

  

The switch positions shown here result in the Modbus address 

128 + 64 + 1 = 193

BUS PARAMETERS

Baud rate 

(selectable)

DIP  

DIP  

2

MODBUS

DIP switch [B] 

  9600 baud

O N

OFF

1 2 3 4 5 6

ON

DIP B

19200 baud

O N

O N

38400 baud

OFF

O N

Reserved

OFF

OFF

Parity 

(selectable)

DIP 

3

Parity check 

(on / off)

DIP 

4

8N1-Modus 

(on / off)

DIP 

5

Bus termination 

(on / off)

DIP 

6

EVEN   

(numbered)

O N

Active   

(1 stop bit)

O N

Active

O N

Active

O N

ODD   

(numbered)

OFF

Inactive (no parity) 

(2 stop bits)

OFF

Inactive (default)

OFF

Inactive  

OFF

The

 baud rate

 (speed of transmission) is set at DIP switches 1 and 2 of DIP switch block [B].  

Selectable are 

9600 baud, 19200 baud,

 or 

38400 baud

 – see table!

Parity

 is set at DIP switch 3 of DIP switch block [B]. 

Selectable are 

EVEN

 or 

ODD

 – see table! 

Parity check

 is activated via DIP switch 4 of DIP switch block [B].  

Selectable are 

active (1 stop bit)

, or 

inactive (2 stop bits)

, i.e. no parity check – see table! 

The 8N1 mode is activated via DIP switch 5 of DIP switch block [B]. 
The functionality of DIP switch 3 (parity) and DIP switch 4 (parity check) of DIP switch block [B] is therefore deactivated. 
Selectable are 8N1 active or inactive (default) – see table !. 

Bus termination

 is activated via DIP switch 6 of DIP switch block [B].  

Selectable are 

active

 (bus termination resistance of 120 Ohm), or 

inactive

 (no bus termination) – see table!

When bus parameters and bus address are changed at devices with 

display

,  

the respective settings are shown on the display for approx. 30 seconds. 

COMMUNICATION INDICATOR

Communication is indicated via two LEDs. Error-free received telegrams are signalized by the green LED lighting up, regardless of 
the device address. Faulty telegrams or triggered Modbus exception telegrams are depicted by the red LED lighting up.

DIAGNOSTICS

An error diagnostic function is integrated

POTENTIOMETER 

The potentiometer setting is recorded in the range from 0-100% and is emitted via the register 3x0005 (setpoint potentiometer). 

Summary of Contents for FSFTM-Modbus

Page 1: ...relative absolute humidity dew point mixture ratio enthalpy in wall in the panel switch programme with Modbus connection F Notice d instruction Sonde d ambiance d humidit et de temp rature resp conve...

Page 2: ...GRASGARD FSFTM Modbus D G F r Ma zeichnung Dimensional drawing Plan cot Ma zeichnung Dimensional drawing Plan cot FSFTM Modbus P FSFTM Modbus 15 5 55 3 43 80 55 80 50 60 60 12 40 5 55 3 80 55 80 50 60...

Page 3: ...Busschnittstelle RS 485 galvanisch getrennt Busabschluss ber DIP Schalter aktivierbar Bis zu 32 Ger te auf einem Segment m glich Bei gr erer Anzahl von Ger ten m ssen RS 485 Transceiver eingesetzt wer...

Page 4: ...odbus 1201 9226 1000 162 FSFTM Modbus P 0 100 r H default 0 80 g kg MV 0 80 g m3 a F 0 85 kJ kg ENT 20 80 C TP 0 50 C Potentiometer Modbus 1201 9226 1400 282 Datenpunkte relative Feuchte r H absolute...

Page 5: ...sgeschwindigkeit wird ber Pos 1 und 2 des DIP Schalters B eingestellt Einstellbar sind 9600 Baud 19200 Baud oder 38400 Baud siehe Tabelle Die Parity wird ber Pos 3 des DIP Schalters B eingestellt Eins...

Page 6: ...t tzt Sub Function Code Parameter Data Type Antwort 00 Echo der Sendedaten Loopback Echodaten 01 Neustart Modbus Reset Listen Only Mode Echo Telegramm 04 Aktivierung Listen Only Mode Keine Antwort 10...

Page 7: ...etrennte Segmente aufzuteilen Die Teilnehmeradresse kann von 1 bis 247 eingestellt werden F r die Busleitung ist ein Kabel mit paarverseilter Datenleitung Spannungsversorgung und Kupferabschirmgeflech...

Page 8: ...rlegung mit stromf hrenden Leitungen ist unbedingt zu vermeiden es wird empfohlen abgeschirmte Leitungen zu verwenden dabei ist der Schirm einseitig an der DDC SPS aufzulegen Der Einbau hat unter Beac...

Page 9: ...sem Ger t entstehen sind von der Gew hrleistung und Haftung ausgeschlossen Montage und Inbetriebnahme der Ger te darf nur durch Fachpersonal erfolgen Es gelten ausschlie lich die technischen Daten und...

Page 10: ...RS 485 galvanically isolated bus termination can be activated via DIP switch Up to 32 devices possible in one segment In case of a greater number of devices RS 485 transceivers must be used Bus protoc...

Page 11: ...20 80 C TP 0 50 C Modbus 1201 9226 1000 162 FSFTM Modbus P 0 100 r H default 0 80 g kg MV 0 80 g m3 a F 0 85 kJ kg ENT 20 80 C TP 0 50 C Potentiometer Modbus 1201 9226 1400 282 Data points relative hu...

Page 12: ...ault OFF Inactive OFF The baud rate speed of transmission is set at DIP switches 1 and 2 of DIP switch block B Selectable are 9600 baud 19200 baud or 38400 baud see table Parity is set at DIP switch 3...

Page 13: ...Function Code Parameter Data Type Answer 00 Echo of transmission data Loopback Echo data 01 Restart Modbus Reset listen only mode Echo telegram 04 Activation listen only mode No answer 10 Delete coun...

Page 14: ...ribers is greater the bus must be subdivided into several segments separated by repeaters The subscriber address can be set from 1 to 247 For the bus line a twisted pair cable data line power supply l...

Page 15: ...be adhered to It is imperative to avoid parallel laying of current carrying lines We recommend to use shielded cables with the shielding being attached at one side to the DDC PLC Before mounting make...

Page 16: ...s caused by a fault in this device are excluded from warranty or liability These devices must be installed and commissioned by authorised specialists The technical data and connecting conditions of th...

Page 17: ...ble et adressable via interrupteur DIP Interface de bus RS 485 s paration galvanique terminaison de bus activable via interrupteur DIP Jusqu 32 appareils possibles sur un segment Pour un nombre sup ri...

Page 18: ...201 9226 1000 162 FSFTM Modbus P 0 100 h r default 0 80 g kg MV 0 80 g m3 a F 0 85 kJ kg ENT 20 80 C TP 0 50 C Potentiom tre Modbus 1201 9226 1400 282 Donn es humidit relative h r humidit absolue g m...

Page 19: ...B On peut r gler 9600 Baud 19200 Baud ou 38400 Baud voir tableau La parit est r gl e via la pos 3 de l interrupteur DIP B On peut r gler EVEN paire ou ODD impaire voir tableau La protection par parit...

Page 20: ...sion loopback rebouclage Donn es d cho 01 Red marrage Modbus Reset Listen Only Mode R init Mode coute Seule T l gramme d cho 04 Activation Listen Only Mode mode coute seule Pas de r ponse 10 Efface co...

Page 21: ...it tre r parti en plusieurs segments par l interm diaire de repeaters L adresse des correspondants peut tre fix e de 1 247 Pour la ligne de bus on peut utiliser un c ble avec ligne de donn es alimenta...

Page 22: ...e de temp ratures Les directives CEM celles ci sont respecter Ne pas poser les c bles de sonde en parall le avec des c bles de puissance Il est conseill d utiliser des c bles blind s ce faisant raccor...

Page 23: ...cons cutif provoqu par des erreurs commises sur cet appareil L installation et la mise en service des appareils doit tre effectu e uniquement par du personnel qualifi Seules les donn es techniques et...

Page 24: ...Merten Jung Siemens Busch Jaeger 24 10 1 1 24 2 2 24 DIP RS 485 DIP 32 RS485 Modbus RTU 0 247 9600 19 200 38 400 4 c 32 c C C Busch Jaeger 1 0 100 0 95 3 0 20 80 25 C 5 0 0 50 C 0 8 K 25 C 55 0 14 1 5...

Page 25: ...TM Modbus 60 HYGRASGARD FSFTM Modbus WG02 FSFTM Modbus FSFTM Modbus 0 100 default 0 80 MV 0 80 3 a F 0 85 ENT 20 80 C TP 0 50 C Modbus 1201 9226 1000 162 FSFTM Modbus P 0 100 default 0 80 MV 0 80 3 a...

Page 26: ...8 DIP 1 ON DIP 2 64 DIP 2 ON DIP 3 32 DIP 3 OFF DIP 4 16 DIP 4 OFF DIP 5 8 DIP 5 OFF DIP 6 4 DIP 6 OFF DIP 7 2 DIP 7 OFF DIP 8 1 DIP 8 ON 128 64 1 193 Modbus DIP 1 DIP 2 MODBUS DIP B 9600 ON OFF 1 2 3...

Page 27: ...0006 16 0 500 0 0 50 0 C 3x0007 16 0 800 0 0 80 0 3 3x0008 16 0 800 0 0 80 0 3x0009 16 0 850 0 0 85 0 08 Diagnostics 00 Loopback 01 Modbus Reset Listen Only Mode 04 Listen Only Mode 10 11 16 12 CRC 16...

Page 28: ...Modbus 32 1 247 100 Profibus Slave n MODBUS RTU Master RS 485 20 n 40 n Slave 1 Slave 2 LA LA A D1 D GND B D0 D MODBUS RTU Master Slave 1 Slave 2 5 B RBIAS RBIAS RAB RAB r AERASGARD FSFTM Modbus Rev...

Page 29: ...29 r EMV VDE VDI DDC PLC 0 5 g VDE...

Page 30: ...30 r ZVEI VDE EMV...

Page 31: ...rol their particular suitability must be verified by each customer and or end user themselves Existing property rights must be observed We warrant the faultless quality of our products as stated in ou...

Page 32: ...120 0 1 1 1 1 0 0 0 121 0 1 1 1 1 0 0 1 122 0 1 1 1 1 0 1 0 123 0 1 1 1 1 0 1 1 124 0 1 1 1 1 1 0 0 125 0 1 1 1 1 1 0 1 126 0 1 1 1 1 1 1 0 127 0 1 1 1 1 1 1 1 128 1 0 0 0 0 0 0 0 129 1 0 0 0 0 0 0 1...

Reviews: