ENDA ETC4420 PID TEMPERATURE CONTROLLER

Read this document carefully before using this device. The guarantee will be expired by 
damaging of  the device if you don't attend to the directions in the user manual. Also we don't 
accept any compensations for personal injury, material damage or capital disadvantages.  

Thank you for choosing ENDA ETC4420 temperature controller.

* 48 x 48mm sized.
* Selectable sensor type.

* Soft-Start.

 

Automatic calculation of PID parameters  (SELF TUNE).

* Selectable Heat/Cool control.

* Communication vai RS-485 ModBus protocol (Optional).

* Relay output can be programmable as second alarm or control output.
* AL1 relay output for first alarm out.

* Input offset feature.
* In the case of sensor failure 

relay state can be 

  selected.

periodical running or 

Parameter access protection on 3 levels.

Programming by using keypad or Modbus.

CE marked according to European Norms.

* Selectable SSR or relay control output.

 Enter PID parameters of the system if they are known at the beginning.
 Otherwise, Self-Tune should be activated.

 J (Fe-CuNi) Thermocouple

 K (NiCr-Ni) Thermocouple

 T (Cu-CuNi) Thermocouple
 S (Pt/0Rh-Pt) Thermocouple

 R (Pt13Rh-Pt) Thermocouple

               EN 60584
               EN 60584
               EN 60584
               EN 60584
               EN 60584

 0...  600
 0...1200
 0...  400
 0...1600

                  0...1600

°C

°C
°C
°C
°C

 +32... +1112

 +32... +2192
 +32...   +752
 +32... +2912

                  +32... +2912

°F
°F
°F
°F

°F

 Pt 100 Resistance Thermometer
 Pt 100 Resistance Thermometer

EN 60751
EN 60751

 -200...600 

 -99.9...300.0

°C
°C

 0,2% (

)

of full scale

 0,2% (

)

of full scale

1 digit
1 digit

 0,2% (

)

of full scale

digit

 0,2% (

)

of full scale

digit

 0,2% (

)

of full scale

digit

 0,2% (

)

of full scale

1 digit

 0,2% (

)

of full scale

digit

   -328... +1112 

  -99.9...+543.0

°F
°F

°C

°F

OUTPUTS

 

 Selectable as Control or  Alarm2 output.

 Relay : 250V AC, 2A ( for resistive load), NO/NC.

 Selectable  logic control output. (Max 12V 20mA( 

 

(Alarm1 output).

 Relay : 250V AC, 2A ( for resistive load), NO/NC selectable. 

 AL1

  SSR out 

 Mechanical 30.000.000 operation; Electrical 300.000 operation

  Life expectancy for relay 

 CONT./AL2 

TECHNICAL SPECIFICATIONS 

Input type

 Temperature range

  Accuracy

ENVIRONMENTAL CONDITIONS

 Height

 Max. 2000m

80  up to 31     decreasing linearly  50  at 40    . 

%

%

 Ambient/storage temperature
 Max. Relative humidity

0 ... +50

/

   

°C -25... +70°C  (with no icing)

°C

°C

Rated pollution degree

According to EN 60529                Front panel :    IP65
                                                       Rear panel  :    IP20

 Do not use the device in locations subject to corrosive and flammable gases.

ELECTRICAL CHARACTERISTICS

 Supply

 230V AC +10  -20 , 50/60Hz or 24V AC ±10 , 50/60Hz.

%

%

%

 Power consumption

Max. 5VA
2.5mm² screw-terminal connections

 Wiring
 Line resistance 
 Data retention
 EMC
 Safety requirements

 EN 61326-1: 1997, A1: 1998, A2: 2001 (Performance criterion B for standard EN 61000-4-3)   

EEPROM (minimum 10 years)

 EN 61010-1: 2001 (Pollution degree 2, overvoltage category II)

For thermocouple max.100ohm, for 3 wired Pt 100 max. 20ohm

CONTROL

 Control type

 Single set-point and alarm control

 On-Off / P, PI, PD, PID (selectable)

 Control algorithm
 A/D converter

 15 bits

 Sampling time
 Proportional band

 Derivative time

 Integral time

 Control period
 Hysteresis
 Output power

 500ms
 Adjustable between 0  and 100 . If Pb=0 ,  On-Off control is selected.

%

%

%

 Adjustable between 0.0 and 100.0 minutes

 Adjustable between 0.00 and 25.00 minutes
 

 and 250 seconds

Adjustable between 1

 

1 and 50

        

Adjustable between 

°C/F

  The ratio of power at a set point can be adjusted between 0  and 100

%

%

HOUSING

 Housing type

 Suitable for flush-panel mounting according to DIN 43 700.

 Dimensions  

 W48xH48xD87mm 

 Weight 

 Approx. 250g (after packing)
 Self extinguishing plastics. 

 Enclosure material 

 While cleaning the device, solvents (thinner, benzine, acid etc.) or 

corrosive materials 

must not be used.

TEMPERATURE 

 CONTROLLER

ENDA

PV

SV

CSET

ASET

SET

E

T

C

 

442

0

CNT/AL2

AL1

 

 

SSR

Summary of Contents for ETC4420

Page 1: ...lectable logic control output Max 12V 20mA Alarm1 output Relay 250V AC 2A for resistive load NO NC selectable AL1 SSR out Mechanical 30 000 000 operation Electrical 300 000 operation Life expectancy for relay CONT AL2 TECHNICAL SPECIFICATIONS Input type Temperature range Accuracy ENVIRONMENTAL CONDITIONS Height Max 2000m 80 up to 31 decreasing linearly 50 at 40 Ambient storage temperature Max Rela...

Page 2: ...the maximum scale value of the selected input The minimum value is the value of C Lo L parameter Set point upper limit C LoL If InP or UnIt parameters are changed the minimum value of the C Lo L parameter changes to the minimum scale value of the selected input The maximum value is the value of C Hi L parameter Set point lower limit oFFS Offset value is added to the measurement value Adjusted betw...

Page 3: ...0 C SEt 150 A1 sE 250 A1 sE 249 First press and hold key until the massage C Set appears on the display Then the value is adjusted by using keys SET CSET SET CSET SET CSET SET CSET ASET ASET ASET When CSET is released it returns to normal operation When ASET is released it returns to normal operation 130 150 PV PV PV PV PV PV PV PV PV PV SV SV SV SV SV SV C SEt 149 PV SV SV SV SV SV Error Messages...

Page 4: ...e close to the power cables or components The installation and electrical connections must be carried on by a qualified staff and must be according to the relevant locally applicable regulations For J K T S R type thermocouple Use suitable compensation cables Don t use jointed cables Pay attention to the polarities of the thermocouple cables as shown in the figure right are connected to the For re...

Reviews: