8
H o o k i n g u p L o w Vo l t a g e L i g h t s t o C i r c u i t 1
To connect a Low Voltage lighting product to Circuit 1 (12VAC), an NEC or local jurisdiction approved Pull
/ Junction / Bell Box must be used to directly connect the conduit from the lighting product, in line with the
WPC2-XXXX-T.
This box must be a minimum of 4” above ground level and may also serve as a convenient location to store
service loop cable. Use appropriate wire from the separate 12VAC output block (terminals L1, L2) to supply
Low Voltage power from the WPC2-XXXX-T to the approved Pull, Junction, or Bell Box.
Use the lower right conduit knockout location(s) and be sure to replace the Isolation Cover using the grounding
attachment screw. Lastly - use the supplied cable tie to secure the lighting wiring to the cover.
If this product is used to connect 120VAC underwater lights directly, refer to 1999 NEC 680-
21(b), 2002 NEC 680-24(b) or CEC 68-060, 062 and 066 for details.
GROUND