6
SUITABLE LISTED BREAKERS
MANUFACTURER
CIRCUIT BREAKER
FILLER PLATE
SINGLE
DOUBLE
TWIN
QUAD
GFCB
Thomas & Betts
TB
TB
TBBD
TBBQ
GFB
FP-1C-TB
Cutler-Hammer
BR
BR
BRD
BRD
GFCB
BRFP
Square D
HOM
HOM
HOMT
HOMT
HOM-GFI
HOMFP
Murray
MP-T
MP-T
MH-T
MH-T
MP-GT
LX100FP
Siemens/ITE
QP
QP
QT
QT
QPF
QF-3
Challenger
C
-
A-CT
-
HAGF
#FC-1C
Westinghouse or Bryant
BR
-
BQ
-
GFCB
FP-1
Crouse Hinds
MP
-
TRIPLEX
-
MP-GF
-
GE Regular
THOP
-
-
-
THOP-GF
TQLFP-1
WIRING INFORMATION - COPPER CONDUCTORS ONLY
Wire Size
75°C min.
Insulation
Supply Circuit
Breaker Rating
Terminal Torque*
Max Motor Load
(Continuous Duty)
General Purpose
Branch Circuit
Breaker Rating
General Purpose
Branch Circuit
Maximum Current
Capacity
Line and
Neutral Main
Lugs
Neutral and
Ground
120V
240V
AWG
AMP
LB-IN
LB-IN
HP
HP
AMP
AMP
14
15
35
20
1/2
1
15
12
12
20
35
20
1
2
20
16
10
30
35
20
1 1/2
3
30
24
8
50
40
25
2
5
40
32
6
65
45
35
-
-
60
44
4
85
45
35
-
-
-
-
3
100
50
-
-
-
-
-
2
100/125
50
-
-
-
-
-
E L E C T R I C A L R AT I N G S
Do n
ot exceed the maximum electrical rati
n
gs of the WPC-
2
. A circuit breaker rated at
20
Amps at
120VAC
must be i
nstalled in
the breaker pa
nel to conn
ect to the WPC-
2 power in
put. Circuit
1 is rated for use of up
to
2.5 amps @
12
VAC, a
nd Circuit 2 is rated for use of up to 8
amps @
120
VAC. The Pump Relay is rated at
a maximum of 3HP @
240
VAC.