Functions of the CompTrol Interface expansion module
5.1.3 Resistive circuit
If a fixed temperature setpoint is to be transferred to the indoor units, two fixed resistors or two
potentiometers can be connected to analog inputs
X3-S
+
X3-(+RV)
and
X3-S
+
X3-(-RV)
to act
as voltage dividers. A temperature setpoint between 18 °C and 30 °C can be specified.
Resistive circuit operation for analog input is possible in the following programs:
–
Program 0 and programs 2 to 7.
IU
3
2
1
5
4
7
8
6
Figure 6: Resistive circuit at analog input X3-S
No. Name
No. Name
1
Indoor unit
2
X/Y remote control bus
3
Wired remote control RC-EX1 or RC-EX3
4
Volt-free digital outputs
5
Digital inputs
6
CompTrol Interface expansion module
7
Resistor R1
8
Resistor R2