E n e r g y T e c h n o l o g y
Ltd.
8
4.0 technical
data & dimensions
underside - models 45/62/76
plan - models 45/62/76
238
229
108
458
38
55
231
435
1
2
3
4
193
108
38
24
35
55
1
2
5
6
7
8
front - all models
950
50
CONNECTION MICROMAT EC
45
62
76
1. Return
1
1
/
4
” BSP-M
1
1
/
4
” BSP-M
1
1
/
4
” BSP-M
2. Flow
1
1
/
4
” BSP-M
1
1
/
4
” BSP-M
1
1
/
4
” BSP-M
3. Flue Gas (OD)
70mm
70mm
70mm
4. Air Duct (OD)
125mm
125mm
125mm
5. Condense Siphon Cleaning
3
/
4
” BSP
3
/
4
” BSP
3
/
4
” BSP
Point (capped)
6. Condensate
3
/
4
” BSP-M
3
/
4
” BSP-M
3
/
4
” BSP-M
7. Cable Entries
Multiple
Grommets
8. Gas
3
/
4
” BSP
3
/
4
” BSP
3
/
4
” BSP
MODEL
MICROMAT EC
45
62
76
Nominal Heat Input Nett (max)
kW
43
57
72
Nominal Heat Output 80/60
°
C
kW
41.3
55.8
70.6
Nominal Heat Output 50/30
°
C
kW
45.2
60.4
76.0
Input Rate Nat Gas (max)
m3/h
4.5
6.01
7.6
Minimum/Maximum Gas Pressure
mbar
15/60
15/60
15/60
Flue Gas Volume (hot)
m3/h
64
81
104
Pressure at Flue Outlet
pa
100
100
100
Maximum Working Pressure
bar
3.0
3.0
3.0
Minimum Working Pressure
bar
0.5
0.5
0.5
Maximum Flow Temperature
°
C
85
85
85
Power Supply
Volts
230
230
230
Fuse rating
Amps
3.0
3.0
3.0
Average Power Consumption
Watts
115
115
164
Water Content
Litres
6
7
8
Weight (Dry)
kg
64
69
73
Summary of Contents for MICROMAT EC 45
Page 1: ......
Page 2: ......
Page 43: ...43 18 2 dipswitch settings E n e r g y T e c h n o l o g y Ltd ...
Page 46: ...46 18 4 setting weather compensation E n e r g y T e c h n o l o g y Ltd ...
Page 47: ...47 18 4 setting weather compensation E n e r g y T e c h n o l o g y Ltd ...
Page 56: ......