27
16.0 hydraulic system
design
E n e r g y T e c h n o l o g y
Ltd.
system type 5
Typical Single MICROMAT EC boiler installation serving heating & domestic hot water with hot water priority.
Hotwater & heating circuits both have index resistance exceeding 1 metre & are served by independent
pumps from a low velocity mixing header. Heating flow temperature may be fixed/constant or weather variable.
W/T = Alternative to "S" where "W" is a time switch
in series with a cylinder thermostat "T".
Allows for timed HWS.
PR01= Pump regulation module from RVR Ltd.
Allows heating pump to be driven from boiler,
providing for auto operation, frost protector
running & summer standstill exercising.
Must be used where RE2132 modulating room unit
is installed. Max pump motor load 2A.
OS = Outside air temperature sensor, used where
direct-on-boiler weather compensated flow
temperatures are required.
C = Room temperature controls e.g. RE2132
modulating room unit from RVR Ltd., or,
separated time clock & room thermostat.
S = HWS sensor from RVR Ltd. Gives 24hr HWS
operation
Micromat
EC Boiler
AV's
Safety Valve
IV
IV
Strainer
AV
Low velocity mixing header
Max. velocity 0.5m/s
IV
DOC
Calorifier
T
S
Return from
system circuits
Flow to
HWS Primary
Pump Max 1A
system circuits
C
W
OS
DOC
IV
IV
DOC
Condensate
LSV
DOC
Expansion Vessel
CWM
PRO 1
Heating
Pump
Summary of Contents for MICROMAT EC 45
Page 1: ......
Page 2: ......
Page 43: ...43 18 2 dipswitch settings E n e r g y T e c h n o l o g y Ltd ...
Page 46: ...46 18 4 setting weather compensation E n e r g y T e c h n o l o g y Ltd ...
Page 47: ...47 18 4 setting weather compensation E n e r g y T e c h n o l o g y Ltd ...
Page 56: ......