15.0 ventilation requirements
single appliances
E n e r g y T e c h n o l o g y
Ltd.
The room or space in which the MICROMAT EC boiler is installed may require to be ventilated in accordance with
BS5440: Part 2:1989 or BS 6644: 1991 as appropriate to the boiler input.
The following tables must be read to ascertain the amount of ventilation required.
Table 1
Room Installation - Non Room Sealed Flue.
Natural Ventilation Direct to Outside Air
Boiler Model
Ventilation Openings Free Area cm
2
High Level
Low Level
MICROMAT EC 45
196
Position Not Dictated
MICROMAT EC 62
278
555
MICROMAT EC 76
319
637
Table 2
Room Installation - Non Room Sealed Flue.
Natural Ventilation From Adjacent Room
Boiler Model
Ventilation Openings Free Area cm
2
MICROMAT EC 45
196cm
2
with adjacent room similarly ventilated direct to outside air.
MICROMAT EC 62 & 76
Ventilation from adjacent room not permitted see Table 1 for ventilation
area direct to outside air.
Table 3
Room Installation – Room Sealed Flue
There are not specific requirements for a room to be ventilated where the appliance
is room sealed. However, consideration should be given to providing ventilation for
general cooling, (BS6644 specifies room temperature limits) and the following free
ventilation areas are recommended to be installed.
Boiler Model
Recommended Natural Ventilation Free Area cm
2
MICROMAT EC 45
196 cm
2
(if ventilated from adjacent room, then adjacent room must be equally ventilated
direct to outside air)
MICROMAT EC 62
253 cm
2
Direct to outside air.
MICROMAT EC 76
335 cm
2
Direct to outside air.
Table 4
Compartment Installation – Non room sealed flue Natural Ventilation Direct to
outside air
Boiler Model
Ventilation Openings Free Area cm
2
High Level
Low Level
MICROMAT EC 45
227
454
MICROMAT EC 62
278
555
MICROMAT EC 76
319
637
Summary of Contents for MICROMAT EC 45
Page 1: ......
Page 2: ......
Page 43: ...43 18 2 dipswitch settings E n e r g y T e c h n o l o g y Ltd ...
Page 46: ...46 18 4 setting weather compensation E n e r g y T e c h n o l o g y Ltd ...
Page 47: ...47 18 4 setting weather compensation E n e r g y T e c h n o l o g y Ltd ...
Page 56: ......