
55
E n e r g y T e c h n o l o g y
Ltd.
21.2 (possible) causes of fault
&corrective action
CAUSE No. REASON/ACTION
11
Fan is defective / Replace fan
12
There is no gas supply available / Investigate, restore gas supply
13
Low gas pressure / Investigate and rectify
14
Fuse defective / Check fuses and replace as necessary
15
Gas valve min output setting is incorrect / Check and adjust min output C0
2
%
17
Poor ignition lead connection to electrode or damp connection or lead damaged and
shorting to earth / Check and rectify
18
Transformer defective / Replace transformer
19
Condense siphon is blocked or condensate blocked or frozen / Clear siphon or waste pipe
20
Flue gas leakage from connection at rear of heat exchanger / Check, reposition or replace seal
21
System strainer blocked, isolation valve closed. Or some other interruption to waterflow /
Check and rectify
22
Unacceptably high resistance in flue or air supply tubes or flue blocked / Check flue for
suitability or clear obstruction
23
Leakage of flue gas from flue gas tube into air tube vitiating the combustion air / Strip
out flue system and remake joints
24
Zone pumps not running / Check and rectify
25
Heat exchangers fouled internally with silt or scale / Clean, descale heat exchangers
and system and re-dose system with water treatment
26
Heat exchanger high limit stat defective / Replace limit stat
27
Boiler set for wrong gas type / Convert boiler to burn the gas being supplied
28
Flue gas limit stat defective / Replace limit stat
29
Boiler control panel defective / Replace control panel
30
Incorrect position of ignition electrode / Reset gap 4-5mm
31
moisture in-on electrical connections or components / Dry carefully using warm air
from a hair dryer
32
Incorrect electrical connection / Check and rectify
33
Wiring interrupted (broken wire) / Check and rectify
34
reset button stuck / Press button in attempt to free sticking contacts. If no success
then replace control panel
35
Ignition electrode damaged or broken / Replace electrode
Summary of Contents for MICROMAT EC 45
Page 1: ......
Page 2: ......
Page 43: ...43 18 2 dipswitch settings E n e r g y T e c h n o l o g y Ltd ...
Page 46: ...46 18 4 setting weather compensation E n e r g y T e c h n o l o g y Ltd ...
Page 47: ...47 18 4 setting weather compensation E n e r g y T e c h n o l o g y Ltd ...
Page 56: ......