29
16.0 hydraulic system
design
E n e r g y T e c h n o l o g y
Ltd.
system type 7
Typical Single MICROMAT EC boiler installation serving domestic hot water and radiator heating zone and
an underfloor coil zone all via a low velocity mixing header. The HWS will always have priority. The 2Nr
heating zones may operate independently via 2 Nr separate room units. The 2 Nr heating zones will always
be weather compensated but may have differing compensation slopes.
OS = Outside air temperature sensor. Provides
outside air temperature references for both
heating zones
MR03 = Pumps and mixer regulation control box from
RVR Ltd. provides pump control for both
heating zones i.e. auto operation, frost
protection and summer stand still protection
running.
Provides drive for underfloor coil zone VT mixing valve
with max flow temperature limitation set at 55
°
C. Includes
ratio setter for compensation of under floor coils. Max
pump motor loads 2A
RC1 = RE2132 modulating room unit from RVR Ltd.
provides Time & Temperature control for radiator
heating zone.
RC2 = As RC1 but for underfloor coil zone.
VS = Underfloor zone VT flow sensor (supplied
with MR03)
S = HWS sensor from RVR Ltd. Gives 24hr
operation.
W/T = Alternative to "S" where "W" is a time switch in
series with a cylinder thermostat "T". Allows for
timed HWS.
Radiator Zone
Micromat EC boiler
OS
AV's
Under Floor Zone
VT Pump
HWS Primary
Pump
Radiator
Zone
Pump
Under Floor
VT Mixing
Valve
Low Velocity
Mixing Header
V max 0.5m/s
Under Floor Coils
Zone
∆
t 10
°
C
Strainer
LSV
DOC
Filling Point
DOC
IV
IV
DOC
IV
Condensate
DOC
SV
IV
IV
Expansion
Vessel
CWM
RC
2
DOC
DOC
Calorifier
S
T
W
VS
MRO3
RC
Summary of Contents for MICROMAT EC 45
Page 1: ......
Page 2: ......
Page 43: ...43 18 2 dipswitch settings E n e r g y T e c h n o l o g y Ltd ...
Page 46: ...46 18 4 setting weather compensation E n e r g y T e c h n o l o g y Ltd ...
Page 47: ...47 18 4 setting weather compensation E n e r g y T e c h n o l o g y Ltd ...
Page 56: ......