3.2  Installation Site 

RG-S7808C series must be used in the room. To ensure normal operation and a prolonged use life of the device, the installation site 

must meet the requirements of weight capacity, humidity , cleanness, EMI consideration, grounding system, power, and ventilation. 

See the 

Preparation before Installation 

chapter of 

RG-S7808C Series Switches Hardware Installation and Reference Guide 

for details. 

 

3.3  Cabinet Mounting 

Make sure the cabinet complies with the following conditions: 

 

Install the switch in a 19-inch cabinet in 4-port form hold.   

 

Be sure the distance between two square hole strips, one on each side, is 465 mm. 

Figure 3-2 19-inch Cabinet   

 

 

Be sure that the square hold strip is at least 125 mm far from the outboard front door and the door is at most 25 mm thick to 

ensure a minimum available distance of 100 mm. The front door is at least 500 mm far from the back door, 

Summary of Contents for RG-S7808C Series

Page 1: ...RG S7808C Series Switches Quick Installation Guide V1 1...

Page 2: ...or by any means without the prior written consent of Ruijie Networks is prohibited Exemption statement This document is provided as is The contents of this document are subject to change without any n...

Page 3: ...mechanisms that supported by the product with configuration examples Command Reference Describes the related configuration commands including command modes parameter descriptions usage guides and rel...

Page 4: ...the whole switch weight The whole switch weight may be greater than 70 kg during the movement 3 Preparations Before Installation 3 1 ESD Prevention Precaution To avoid the damages from static electric...

Page 5: ...s Switches Hardware Installation and Reference Guide for details 3 3 Cabinet Mounting Make sure the cabinet complies with the following conditions Install the switch in a 19 inch cabinet in 4 port for...

Page 6: ...r straight screwdriver related electric and optical cables Bolts diagonal pliers straps Special Tools Anti static glove stripping pliers crimping pliers crimping pliers for the crystal head wire cutte...

Page 7: ...odules packing list documentation A normal delivery should contain the above mentioned items which may differ from the actual delivery depending on purchase contracts Please check your goods carefully...

Page 8: ...g Slide Rails When installing slide rails for the RG S7808C ensure that the plane to carry the chassis should be installed on the plane of delimiters of 1 RU as shown in Figure 4 2 Figure 4 2 Installi...

Page 9: ...installed If you are mounting multiple devices to the cabinet mount the heaviest device in the lowest position of the cabinet first and proceed to mount the rest of the devices from bottom to top 4 3...

Page 10: ...Frame Optional The PoE power frame M78 PSE is an optional accessory See RG S7808C Series Switch Installation and Reference Guide for details If the system is installed with a PoE powered service modu...

Page 11: ...for RG S7808C 4 6 Mounting the Switch to a Cabinet Precautions Before mounting RG S7808C series to the cabinet first verify that the front and back brackets of the cabinet are at the right locations...

Page 12: ...on the other bracket through the carrying plane and mark the locations Install seven cage nuts on the marked square holes on each bracket as shown in figure 4 7 Figure 4 7 Slide Rail Installation Posi...

Page 13: ...steps 1 Remove the two screws on the rear of the switch 2 Attach the one end of the grounding wire to the switch with the two screws Connect the other end of the grounding wire to the grounding wire...

Page 14: ...dule by the handle Otherwise the module may be damaged Before inserting or removing the power module please verify whether the switch is well mounted The switch is high avoid switch tumble when you ar...

Page 15: ...operly 2 Tighten the captive screws on the fan tray with a screwdriver Figure 4 11 Installing M08 FAN Do not remove the fan tray forcibly You can use the fan handle Otherwise component damage may occu...

Page 16: ...adopt the design of self locking lever See figure 4 13 for operation 1 Lever Operation Figure 4 13 Pulling out Lever 2 Module Installation 1 Pull out both levers in figure 4 14 2 Insert the module in...

Page 17: ...the power cord is connected 1 Insert the AC power plug into the power module socket 2 Take out the spring clip 3 Install the spring clip on the front panel of the power module 4 Fasten the spring cli...

Page 18: ...at a damp place to prevent the moisture from entering the switch Be sure of the location of the emergency power switch If an emergency occurs cut off the power first Verify that all power supplies ar...

Page 19: ...ing table lists the operational conditions indicated by the module LEDs Module LED Indicator Status Supervisor Module Status Solid green Service Module Status Solid green Power Supply Status Solid gre...