The RG-S6220-48XS4QXS V2.XX series switches support power supply 1+1 redundancy. To improve the stability 

and reliability of the entire system, it is recommended to configure power supply module 1+1 redundancy. When 

the two power supply modules work normally, the switch is in the status of current sharing. 

 

It  requires at  least  one power  supply module  to  work normally.  Baffles  need  to  be  installed  in  the empty power 

supply module slots to ensure ventilation and heat dissipation and avoid dusts. 

Heat Dissipation 

The working temperature of the RG-S6220-48XS4QXS V2.XX switches is 0-50

, and the heat dissipation design 

needs to ensure the stability, safety and maintainability in such environment. The RG-S6220 series switches adopt fan 

ventilation and forced convection to ensure the device can work normally in specified environment. Dust the device 

every three months to avoid blocking the ventilation openings. 

The RG-S6220-48XS4QXS V2.XX supports fan module M6220-FAN II-F and provides fan speed regulation, fan failure 

warning, and fan hot plugging. 

Figure 1-10 Ventilation and Heat Dissipation of the RG-S6220-48XS4QXS V2.XX 

 

 

Leave sufficient space in the front and at the back of the chassis (at least 20 cm) for ventilation. 

 

It requires at least two fan modules to work normally. Baffles need to be installed in the empty fan moduslots to 

ensure ventilation and heat dissipation and avoid dusts. 

1.3  RG-S6220-48XT4QXS 

Specifications 

Model 

RG-S6220-48XT4QXS 

CPU 

Dual-core CPU, each core with the clock speed of 1.0G 

BOOT ROM 

8MB 

Flash Memory 

512MB 

SDRAM 

DDR3 1GB 

Extension Module 

Slot 

Unsupported 

Extension Module 

Unsupported 

Fan Slot 

4 (support 3+1 redundancy, configure at least three fan modules in one switch) 

Fan Module 

M6220-FAN-F 

Power Supply Slot 

2 (support 1+1 redundancy) 

Summary of Contents for RG-S6220-24XS

Page 1: ...RG S6220 Series Switches Hardware Installation and Reference Guide V1 06...

Page 2: ...or by any means without the prior written consent of Ruijie Networks is prohibited Exemption Statement This document is provided as is The contents of this document are subject to change without any n...

Page 3: ...taining Technical Assistance Ruijie Networks Website http www ruijienetworks com Service Email service_rj ruijienetworks com Technical Support http www ruijienetworks com service aspx Technical Suppor...

Page 4: ...A N A 2 1 1 1 RG S6220 48XT4QXS N A 48 4 N A N A 3 1 1 1 RG S6220 24XS 24 N A N A N A 2 3 1 1 1 An SFP port supports both 10Gbase R and 1000base X A QSFP port support both 40G mode and 40 x 10G mode 1...

Page 5: ...dules and two power modules Dimensions 440 x 420 x 44 L x W x H mm 1RU RG S6220 switch is a class A product In a domestic environment this product may cause radio interference in which case the user m...

Page 6: ...000Base T RCMI Ethernet port Console 10G SFP port 40G QSFP port The RG S6220 48XS4QXS V1 XX supports 10G SFP module and 1G SFP module But the 10G SFP module cannot function as the 1G SFP module Port 1...

Page 7: ...s connected with the serial port of terminal PC to perform system debugging configuration maintenance management and host software uploading 10 100 1000M RCMI management port This is an out band Ether...

Page 8: ...rmally RCMI port indicator RCMI Off The port is not linked up Green The port is linked up in 1000M mode Yellow The port is linked up in 10M or 1000M mode Blinking Data are transceiving at the port Cyc...

Page 9: ...eat Dissipation The working temperature of the RG S6220 48XS4QXS V1 XX switches is 0 50 and the heat dissipation design needs to ensure the stability safety and maintainability in such environment The...

Page 10: ...0Gbase T Port Unsupported Temperature Warning Support temperature warning and over temperature protection EMC GB9254 2008 CLASSA EMI GB4943 2011 Working Temperature 0 C to 50 C Storage Temperature 40...

Page 11: ...220 48XS4QXS V2 XX Front Panel Figure 1 7 Front Panel of the RG S6220 48XS4QXS V2 XX Notes Switch status indicator PWR1 status indicator PWR2 status indicator MGMT management interface indicator Fan s...

Page 12: ...oid device damage use qualified USB flash disks of good brands At the same time the local USB interface is compatible with most of the USB controllers except some USB flash disks Console port Use RS 2...

Page 13: ...t is not linked up Green The port is linked up in 1000M mode Yellow The port is linked up in 10M or 1000M mode Blinking Data are transceiving at the port Cycling blinking green yellow and red This sta...

Page 14: ...ice can work normally in specified environment Dust the device every three months to avoid blocking the ventilation openings The RG S6220 48XS4QXS V2 XX supports fan module M6220 FAN II F and provides...

Page 15: ...humidity 10 to 90 RH non condensing Weight Net weight 11 kg including four fan modules and two power modules Dimensions 440 x 500 x 44 L x W x H mm 1 RU RG S6220 48XT4QXS switch is a class A product I...

Page 16: ...lex mode of 10Gbase T 1000Base T and 100Base TX Back Panel Figure 1 13 Back Panel of the RG S6220 48XT4QXS Notes Power supply module slot USB2 0 interface Fan module slot Asset management label Ground...

Page 17: ...45 connector This interface is connected with Ethernet port of a PC to perform program downloading This interface also supports DCMI protocol and users can do remote management and maintenance for the...

Page 18: ...fan modules are in the position and working normally Solid yellow Only three fan modules are in the position Solid red 1 A fan fails 2 The number of the fan module is less than three 10GBase Tport sta...

Page 19: ...M6220 FAN F and provides fan speed regulation fan failure warning and fan hot plugging Figure 1 6 Ventilation and heat dissipation of the RG S6220 48XT4QXS Leave sufficient space in the front and at...

Page 20: ...g temperature 0 C to 50 C Storage temperature 40 C to 70 C Working humidity 10 to 90 RH non condensing Weight Net weight 9 5 kg including four fan modules and two power modules Dimensions 440 x 480 x...

Page 21: ...xtension module Slot 2 The RG S6220 24XS supports10G SFP module and 1G SFP module But the 10G SFP module cannot function as the 1G SFP module The RG S6220 24XS supports two extension module slots Baff...

Page 22: ...RJ45 connector This interface is connected with the serial port of terminal PC to perform system debugging configuration maintenance management and host software uploading 10 100 1000M RCMI management...

Page 23: ...his status helps to locate the device position Fan module indicator Fan Solid green All fan modules are in the position and working normally Solid yellow Only three fan modules are in the position Sol...

Page 24: ...at the back of the chassis at least 20 cm for ventilation It requires at least three fan modules to work normally Baffles need to be installed in the empty fan module slots to ensure ventilation and...

Page 25: ...rks normally SFP port indicator 1F 12F Off The port is not linked up Solid green The port is linked up Blinking Data are transceiving at the port Specifications Model M6220 12XS Applicable Model RG S6...

Page 26: ...e DAC and QSFP module hot plugging Indicator Specifications Indicator Panel Identification Status Meaning Status Indicator Status Off The module is not powered up Solid red The module fails or the mod...

Page 27: ...ty 10 to 90 RH non condensing Weight Net weight 0 5 kg Dimensions 224 5 x 110 x 36 8 L x W x H mm The QSFP port of the M6220 02QXS supports 40G mode and 4x10Gmode Please configure the required working...

Page 28: ...ly FC port indicator 1F 8F Ethernet mode Off The port is not linked up Solid green Port 10G 1G is linked up Blinking green Port 10G 1G is transceiving data 1F 8F FC mode Off The port is not linked up...

Page 29: ...rance of the M6220 08XT Notes Extension module status indicator 1 8 are port status indicators 10GBASE T RJ45 port External Interface The M6220 08XT provides eight RJ45 ports which support 10GBASE T a...

Page 30: ...orage temperature 40 C to 70 C Working humidity 10 to 90 RH non condensing Weight Net weight 0 75 kg Dimensions 224 5 x 110 x 36 8 L x W x H mm The M6220 08XT port supports only the full duplex mode o...

Page 31: ...x H mm 1 5 6 M6220 FAN II F The M6220 FAN II F is the fan module of S6220 48XS4QXS V2 XX The M6220 FAN II F provides heat dissipation system and ensures system satiability The M6220 FAN II F supports...

Page 32: ...ltage direct current HVDC input External Interface The front panel of the power supply module provides a three core power port which can be connected to standard 10 A power cord Indicator Indicator Pa...

Page 33: ...the back When the device is being removed do not hold the power supply handle or the fan handle for these parts are not designed for bearing the entire weight of the device It will cause damage to th...

Page 34: ...sure the antistatic wrist strap is well grounded Do not use bare hand to directly touch the components and the printed circuit board PCB when the boards are used Use an anti static shielding bag to p...

Page 35: ...electricity And sometimes the materials may suffer from mechanical performance change and metallic parts may get rusted On the other hand in an environment with low relative humidity the insulating st...

Page 36: ...as needed Safety Grounding The device using AC power supply must be grounded by using the yellow green safety grounding cable Otherwise when the insulating resistance decreases between the power suppl...

Page 37: ...is difficult to shield Effective measures should be taken for the power system to prevent electric grid interference The working ground of the routers should be properly separated and kept as far as...

Page 38: ...n guide Packing list Pouched documents Module Carton Various modules Packing list Quick installation guide A normal delivery should contain the above mentioned items which may differ from the actual d...

Page 39: ...g before installation Verify the following requirements before installation The installation location provides sufficient space for heat dissipation The installation location meets the temperature and...

Page 40: ...of the same model should be ready and tightened Various boards of the equipment should be installed securely and the fastening screws on the panel should be tightened All wiring inlets at the top and...

Page 41: ...ckets 1 Take out the two L shape brackets and eight M4 8FMO countersink screws from the plastic package 2 Install the brackets at the side panels of the switch and fix the brackets with four M4 FMO co...

Page 42: ...depth of 800mm 1200mm Mounting the Switch to a Workbench In some cases users do not have the 19 inch standard cabinet The common solution is to place the switch on a clean workbench The operation is s...

Page 43: ...o avoid wrong insertion If the position is not proper withdraw the inserted module and re insert it If the screws cannot be tightened it is probably because the fan module is not fully inserted Please...

Page 44: ...fix the extension module in the switch chassis Figure 3 6 Installing an M6220 series extension module Insert the extension module smoothly Pay attention to the direction of the extension panel to avo...

Page 45: ...er Module 1 Take a new power module out of the package and confirm the input mode and the input parameters of the power module match the requirements 2 Remove the power baffle and take the plane print...

Page 46: ...k of RG S6220 First connect the PGND to the grounding terminal of the cabinet and then connect the grounding terminal to the grounding bar of the equipment room Precautions The cross sectional area of...

Page 47: ...the NMS or a control terminal 2 Insert the single mode or multi mode fiber into the appropriate interface according to the identification on the panel of the line card Distinguish the Rx Tx end of th...

Page 48: ...binet Verify that there is sufficient space around the device especially in the front and at the back of the device at least 20cm Verifying the Cables Verify that the fibers and twisted pairs match th...

Page 49: ...ort of the PC 2 Connect one end of the console cable RJ45 to the console port of the switch Setting Terminal Parameters Step One Start the PC and run the terminal simulation program on the PC such as...

Page 50: ...column of Connect Using field select the serial port you want to use Figure 4 3 After the serial port is selected click OK The Serial Port Parameter Setting window is displayed as shown in Figure 4 4...

Page 51: ...the power supply voltage complies with the requirement of the switch Check if the console cable is correctly connected the terminal can be a PC used for configuration is already started and the param...

Page 52: ...th the management software When the indicator of the host or the extension module is red or flashing it indicates a failure in which case you need to find out the cause and turn off the power when nec...

Page 53: ...e it with a qualified one and then connect the power cables Replacing Lithium Battery The built in lithium batteries can support the real time clock of the RG S6220 series switches without external po...

Page 54: ...e power connection Check the installation of the power supply module Check the plug in units of each module Check the installation and fastening of the modules Check the indicators on the device and t...

Page 55: ...Description After the system starts the fans in the fan module do not work or the Status indicator is OFF Troubleshooting Check if the connection between the fan module and the backplane is secure and...

Page 56: ...the fiber interface is inserted into the optical module and the optical fiber is properly connected the link cannot be set up Troubleshooting 1 Check whether the receiving and sending ends are wrongly...

Page 57: ...on and influenced by external crosstalk It is recommended to use CAT6A shielded wire or wires with higher specifications for the cabling of the new equipment room CAT6A or CAT7 shielded wire can maxim...

Page 58: ...put Transmit Data 3 Output Transmit Data Input Receive Data 6 Output Transmit Data Input Receive Data 4 5 7 8 Not Used Not Used Figure A 3 shows the feasible connections of the straight through and cr...

Page 59: ...of Received Light dBm min max min max MINI GBIC SX MM850 850 MF No 9 5 3 17 0 MINI GBIC LX SM1310 1310 SF No 9 5 3 20 3 GE eSFP SX MM850 850 MF Yes 9 5 3 17 0 GE eSFP LX SM1310 1310 SF Yes 9 5 3 20 3...

Page 60: ...ter AWG Data Rate Gb s DDM Supporte d Yes No XG SFP CU1M Passive SFP 1 28 10 3125 No XG SFP CU3M Passive SFP 3 28 10 3125 No XG SFP CU5M Passive SFP 5 26 10 3125 No Models and Technical Specifications...

Page 61: ...m Fiber Type Core Size m Modular Bandwidth MHz km Max Cabling distance Intensity of Transmitte d Light dbm Intensity of Received Light dbm DDM Supported Yes No min max min max FC2G SFP SR MM850 850 MF...

Page 62: ...ons for installation Make sure that the PE terminal of the power arrester has been well grounded After the switch AC power plug is connected to the socket of the power arrester lightning protection ca...

Page 63: ...nding terminal of the switch 3 Use the multimeter to check whether the grounding line for the arrester is in good contact with the switch grounding terminal and the framework 4 According to the descri...

Page 64: ...switch Ethernet port to the OUT end Poor arrester grounding The length of the grounding line should be as short as possible to ensure that it is in good contact with the switch grounding terminal Use...

Page 65: ...e diameters After cabling is fixed the bend radius of a common coaxial cable should be over seven times greater than its diameter The bend radius of this type of cables that often bend or suffer remov...

Page 66: ...versed by cables should have a smooth and fully rounding surface or an insulated lining Proper buckles should be selected to bundle up cables It is forbidden to connect two or more buckles to bundle u...

Page 67: ...f moving parts The power cables connecting moving parts such as door grounding wires should be reserved with some access after assembled to avoid suffering tension or stress When the moving part reach...

Page 68: ...n should be bundled up into cable bunches with cables in cable bunches clean and straight Binding by using buckles should be performed according to Table D 1 Cable Bunch Diameter mm Binding space mm 1...

Page 69: ...ll as away from dust If the dust is unavoidable keep the door and window away from the pollution source The machine room should be away from the residential area Otherwise the machine room should meet...

Reviews: