SECTION 13 – CARD ADDRESS SETTINGS
Each card in the system must be set to a unique address using switch SW1 position 1
to 8, which is located in the top left hand corner of the associated P925TS-I input
Card, P925TS-O Output Card. The first P925TS-I Input Card in the system is normally
set to address O (All SW1-* switches off) and the remaining cards should be set
according to card type as follows:-
9000TS systems equipped with P925TS-I Input Cards each card is set to its own
unique address
9000TS systems equipped with P925TS-I Input Cards and P925TS-O Output Cards
each pair of input and output cards needs to be set to the same address.
9000TS systems equipped with P925TS-I Input Cards, P925TS-0 Output Cards and
P925TS-R Relay cards each pair of input and output cards needs to be set to the
same address.
Note:- The P925TS-R Repeat Relay cards do not require the address to be set
1 2 3 4
SW1
OFF
ON
5
8
7
6
1 2 4 8 16 32 64 128
BINARY
CARD ADDRESS SETTING
Please note
A maximum of 250 unique addresses can be set as required
Card Address Switch Location