- page 10 of 13
–
Inst ruct ion and operat ing manual CVS
SKL1200 direct driven
(for-030/031013)
5.2
WEEKLY INSPECTION
* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *
ONLY CARRY OUT WHEN INSTALLATION IS COOL AND AT A STANDSTILL
* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *
A:
Check the level of lubricating oil w eekly.
Unscrew the upper screw plug (1) from the oil
pan and check w hether the oil reaches the low er
edge of the threaded hole (2) (see magnification).
• Correct oil level if necessary. If the oil level is
too high: The oil flow s out of the control bore.
Collect oil and dispose of in accordance w ith
legal regulations.
• If the oil level is too low : Top up w ith oil. To do
this, either unscrew the higher of the tw o filling
screw s (3) or the vent plug (4) and slow ly fill in
the oil until the oil reaches the low er edge of the
threaded hole (2).
ATTENTION!
When filling via the bore of the vent plug (4), the
oil level changes only after a time delay due to
the oil flow ing in.
B:
Check the air intake filter at regular intervals.
Clean or replace the air filter if necessary.
* Please note that the air filter is reinserted in the
same position (paying attention to the front and
back of the element).
Also check the functioning of the air indicator.
Air filter
C:
It is important to check the airflow and cleanliness of the fan louvres to prevent
overheating of the compressor.
(compressed air cooler and w hen installed the oil cooler)
This check may only be carried out by skilled mechanics. Observe the safety very
carefully, the enclosure must be removed and rotating parts will be accessible.
D:
Check the functioning of the fan. Check if the control light is on (image 3.1.2). You
w ill find the safety fuse in the sw itch box.