Emergency and Mains only Luminaires
1. Mounting and wiring
●
To remove the diffuser, insert a small screwdriver into the narrow
groove and lever out to unclip as shown.
●
To remove the gear tray, insert a small screwdriver into the slot at
one end and lever out.
●
The fitting may be mounted in any position, but when mounted
vertically (ie. on a wall) the Luminaire should be positioned as
shown inside, ie.
‘This way up’.
●
Drill the body of the Luminaire for fixings and screw into position.
●
Connect the main electrical supply:
E
Use
N
Neutral
Solid
Lch
Permanent supply
wires
Lsw
Switched supply
Only
The permanent supply is not required for the mains only Luminaires.
●
Refit the geartray taking care to position the cables away from
internal components.
●
Finally refit the diffuser and secure
Emergency Luminaires
2. Commissioning
●
Switch on the mains supply. Check that the unit operates correctly.
●
On self-contained units check that the LED shows. Leave the unit
on charge for about 1 hour, then simulate a mains failure, and check
that the lamp operates in the emergency mode.
●
The battery requires 24 hours to fully charge the battery and
become operational.
3. Maintenance
Daily:
Check the LED indicator shows, and on maintained
units check that the lamp operates.
Monthly:
Check that the unit operates in the emergency mode
for up to a 1/4 of the required duration.
Bi-annually: Check that the unit operates for 1 hour.
3 years:
Check that the unit operates for the full duration.
Annually
thereafter:
Check that the unit operates for the full duration.
If the unit fails to provide the required duration, replace the battery
with the identical type.
4. Rated Lumen Output
lamp
type
lumen output
16W
NM/M
110
28W
NM/M
120
5. Temperature Range 0°C - 25°C
All data given on this sheet assume a 25°C ambient temperature.
Important: Disconnect the supply and unplug the internal battery
before working on the unit.
RS Components shall not be liable for any liability or loss of any nature (howsoever
caused and whether or not due to RS Components’ negligence) which may result
from the use of any information provided in RS technical literature.
RS
Stock No.
V10546
Unit location
Emergency Lighting
Installation Enginners
Test Record Sheet
Ref No................................................
Date of Installation.................................
Telephone.........................................
Duration.......................................hours
Installation Engineers
Lamp size - Fluorescent
Test Report
4W 6W 8W 10W 16W 28W
Luminare Type..................................
Red charge indicator shows..........(tick)
Full charge / Discharge test.............(tick)
Delete as appropriate
TEST RECORD - TO BS.5266
month
test
first year
second year
third year
fourth year
fifth year
signed
date
signed
date
signed
date
signed
date
signed
date
1
functional
2
functional
3
functional
4
functional
5
functional
6
functional
7
functional
8
functional
9
functional
10
functional
11
functional
12
1hr duration
full duration