X8 Instruction Set Reference Manual
Using the High-Speed Counter and Programmable Limit Switch
5
-
21
ErrorDetected
The ErrorDetected flag is ON when a HSC error is generated. When this bit is
set, the user should look at the error information in the ErrorCode flag. This
bit is automatically set and cleared by the controller.
UserInterruptExecuting
The UserInterruptExecuting flag is set when the internal processing is begin
by the conditions below.
• low preset reaches
• high preset reaches
• HSC value covers the Overflow condition
• HSC value covers the Underflow condition
This flag is used to detect in the user control program if an HSC interrupt is
executing and will be automatically cleared when the PLC completes its
processing.
3
Invail ed High Preset
0,1
If the high preset value is less than 0
4
Invalid High Preset
2~9
This error is generated when the high preset value is less than or
equal to the low preset.
5
In va il ed Underflow Value
Configuration
2~9
This error is generated when the low preset value is less than
Underflow.
Error Code
Error Name
Mode
Description
Description
Data Format
HSC Mode
Function
User Program
Access
HSC:0.ErrorDetected
Bit
0~9
Status
Read Only
Description
Data Format
HSC Mode
Function
User Program
Access
HSC:0.UserInterruptExecuting
Bit
0~9
Status
Read Only
Summary of Contents for X8 Series
Page 1: ...Catalog Number s X8 M14DDT X8 M16DDR X8 M32DDT X8 Instruction Manual Reference Manual ...
Page 16: ......
Page 64: ...X8 Instruction Set Reference Manual 2 12 X8 Series PLC Memory and Data Table ...
Page 166: ...X8 Instruction Set Reference Manual 7 8 Relay Type Bit Instructions ...
Page 180: ...X8 Instruction Set Reference Manual 8 14 Timer and Counter Instructions ...
Page 205: ...X8 Instruction Set Reference Manual Math Instructions 10 17 ...
Page 206: ...X8 Instruction Set Reference Manual 10 18 Math Instructions ...
Page 212: ...X8 Instruction Set Reference Manual 11 6 Converion Instructions ...
Page 218: ...X8 Instruction Set Reference Manual 12 6 Logical Instructions ...
Page 236: ...X8 Instruction Set Reference Manual 15 8 Shift and FIFO LIFO Instructions ...
Page 242: ...X8 Instruction Set Reference Manual 16 6 Sequencing Instructions ...
Page 252: ...X8 Instruction Set Reference Manual 18 4 Input and Output Instructions ...
Page 280: ...X8 Instruction Set Reference Manual 20 12 PID Control ...
Page 296: ...X8 Instruction Set Reference Manual 21 16 ASCII Instructions ...
Page 308: ...X8 Instruction Set Reference Manual 22 12 Communications Instructions ...
Page 312: ...Appendix A 4 System Error Code ...
Page 313: ...Appendix B MSG Instruction Error Code MSG Instruction Error Code ...
Page 322: ...Appendix B 10 MSG Instruction Error Code ...
Page 325: ...ASCII Character Set Appendix C 3 ...
Page 326: ...Publication number X8 RM001A EN September 2012 ...
Page 327: ...Copyright 2012 RS Automation Co Ltd All rights reserved ...