Troubleshooting 34
6.11 PC 02(Top temperature protection of compressor or High temperature protection of
IPM module diagnosis and solution)
Description:
For some models with overload protection, If the sampling voltage is not 5V, the LED will display the failure.
If the temperature of IPM module is higher than a certain value, the LED displays the failure code.
Recommended parts to prepare:
• Connection wires
• Outdoor PCB
• IPM module board
• High pressure protector
• System blockages
Troubleshooting and repair:
Check if the air flow system
of indoor and outdoor units
are obstructed?
Clear up the air inlet and outlet or the heat
exchanger of indoor and outdoor units.
Yes
No
Yes
Yes
Turn off the power supply and turn
it on 10 minutes later.
Check if the temperature of
compressor Top
Is more than 90
℃?
No
Check if the refrigerant
system
is normal?
Repair the refrigerant
system .
Replace the outdoor control PCB.
Yes
Check if all the connection, especially
the connection of OLP (Over Load
Protector) sensor is good.
Correct the connection.
No
Measure the resistance
between the two ports of
the OLP. Is it zero?
Yes
Replace the OLP.
No
Replace the outdoor control PCB.
Yes
No
Summary of Contents for ANERU Series
Page 2: ......
Page 5: ......
Page 6: ...Contents 1 Precautions 2 2 Information servicing For flammable materials 3 Safety Precautions...
Page 12: ...Contents 1 Model Reference 2 2 External Appearance 3 Model Reference...
Page 15: ...Model Reference 4 2 2 Outdoor Unit Single Fan Outdoor Unit Double Fan Outdoor Unit...
Page 18: ...IDU Console 3 2 Dimensional Drawings 16 Drain pipe Hanging arm 195 700 600 210...
Page 21: ...IDU Console 6 6 Air Velocity and Temperature Distributions Discharge Angle 60...
Page 36: ...IDU Compact Cassette 4 2 Dimensional Drawings...
Page 38: ...IDU Compact Cassette 6 4 Service Place...
Page 56: ......
Page 115: ...IDU Super Slim Casstte 54 36k 42k 48k 55k...
Page 118: ......
Page 131: ...IDU Duct 7 6 Fan Performance 12K...
Page 132: ...IDU Duct 8 18K...
Page 133: ...IDU Duct 9 24K...
Page 134: ...IDU Duct 10 30K 36K...
Page 135: ...IDU Duct 11 42K 48K...
Page 136: ...IDU Duct 12 55K...
Page 165: ...IDU Duct 41 12k 18k 24k 30k...
Page 166: ...IDU Duct 42 36k 42k 48k 55k...
Page 178: ......
Page 179: ...35mm 1 38in...
Page 180: ......
Page 256: ...IDU Floor Ceiling 82 36k 48k 55k...
Page 259: ......
Page 267: ...Outdoor Unit 3 Panel Plate B30...
Page 268: ...Outdoor Unit 4 Panel Plate BA30...
Page 269: ...Outdoor Unit 5 Panel Plate CA30...
Page 270: ...Outdoor Unit 6 Panel Plate D30...
Page 271: ...Outdoor Unit 7 Panel Plate X230...
Page 272: ...Outdoor Unit 8 Panel Plate X330...
Page 273: ...Outdoor Unit 9 Panel Plate X430...
Page 274: ...Outdoor Unit 10 Panel Plate E30...
Page 275: ...Outdoor Unit 11 Panel Plate 590...
Page 276: ...Outdoor Unit 12 2 Service Place...
Page 285: ...Outdoor Unit 21 UO70Xo UO90Xo UO100Xo UO100Xo3F...
Page 286: ...Outdoor Unit 22 UO120Xo UO140Xo UO160Xo...
Page 291: ......
Page 292: ......
Page 293: ......
Page 294: ......
Page 295: ...Outdoor unit printed circuit board diagram 17122000044714 17122000048121 17122000046453...
Page 297: ...Outdoor unit printed circuit board diagram 17122000048064...
Page 299: ...Outdoor unit printed circuit board diagram 17122000047742 1 3 4 6 8 9 5 7 10 12 11 2 13...
Page 302: ...Outdoor unit printed circuit board diagram 17122000041841...
Page 304: ...Outdoor unit DC motor driver board diagram 17122000021912 5 6 1 2 3 4...
Page 320: ...3 IDU Installation Duct Connector Connector...
Page 352: ...Product Features 13 Remote LCD Screen Indicators...
Page 549: ......
Page 550: ......
Page 551: ......
Page 552: ...email info rotenso com www rotenso com INSTALLER STAMP...