10. Engineering of Electrical Wring
10.
Engineering of Electrical Wring
1. Highlights of electrical wiring installation
•
All field wiring construction should be finished by
qualified electrician.
•
Air conditioning equipment should be grounded ac-
cording to the local electrical regulations.
•
Current leakage protection switch should be in-
stalled.
•
Do not connect the power wire to the terminal of
signal wire.
•
When power wire is parallel with signal wire, put
wires to their own wire tube and remain at least
300mm gap.
•
According to table in indoor part named “the speci-
fication of the power” to choose the wiring, make
sure the selected wiring not small than the date
showing in the table.
•
Select different colors for different wire according to
relevant regulations.
•
Do not use metal wire tube at the place with acid or
alkali corrosion, adopt plastic wire tube to replace it.
•
There must be not wire connect joint in the wire
tube If joint is a must, set a connection box at the
place.
•
The wiring with different voltage should not be in
one wire tube.
•
Ensure that the color of the wires of outdoor and
the terminal No. are same as those of indoor unit
respectively.
Table: Minimum Cross-Sectional Area able of Power and
Signal Cables
For North America:
Rated Current of
Appliance (A)
AWG
≤ 6
18
6 - 10
16
10 - 16
14
16 - 25
12
25 - 32
10
For the other regions:
Rated Current of
Appliance (A)
Nominal Cross-Sectional
Area(mm
2
)
≤ 6
0.75
6 - 10
1
10 - 16
1.5
16 - 25
2.5
25 - 32
4
32 - 45
6
11. Test Operation
1. The test operation must be carried
out after the entire installation has been
completed.
2. Please confirm the following points
before the test operation.
•
The indoor unit and outdoor unit are installed prop-
erly.
•
Piping and wiring are properly connected.
•
Ensure that there are no obstacles near the inlet and
outlet of the unit that might cause poor perfor-
mance or product malfunction.
•
The refrigeration system does not leak.
•
The drainage system is unimpeded and draining to a
safe location.
•
The heating insulation is properly installed.
•
The grounding wires are properly connected
•
The length of the piping and the added refrigerant
stow capacity have been recorded.
•
The power voltage is the correct voltage for the air
conditioner.
CAUTION: Failure to perform the test run may result in unit
damage, property damage or personal injury.
3. Test Run Instructions
1. Open both the liquid and gas stop valves.
2. Turn on the main power switch and allow the unit to
warm up.
3. Set the air conditioner to COOL mode, and check the
following points.
Indoor unit
•
Whether the switch on the remote controller works
well.
•
Whether the buttons on the remote controller
works well.
•
Whether the air flow louver moves normally.
•
Whether the room temperature is adjusted well.
•
Whether the indicator lights normally.
•
Whether the temporary buttons works well.
•
Whether the drainage is normal.
•
Whether there is vibration or abnormal noise during
operation.
Outdoor unit
•
Whether there is vibration or abnormal noise during
operation.
•
Whether the generated wind, noise, or condensed
of by the air conditioner have influenced your neigh-
borhood.
•
Whether any of the refrigerant is leaked.
Summary of Contents for ANERU Series
Page 2: ......
Page 5: ......
Page 6: ...Contents 1 Precautions 2 2 Information servicing For flammable materials 3 Safety Precautions...
Page 12: ...Contents 1 Model Reference 2 2 External Appearance 3 Model Reference...
Page 15: ...Model Reference 4 2 2 Outdoor Unit Single Fan Outdoor Unit Double Fan Outdoor Unit...
Page 18: ...IDU Console 3 2 Dimensional Drawings 16 Drain pipe Hanging arm 195 700 600 210...
Page 21: ...IDU Console 6 6 Air Velocity and Temperature Distributions Discharge Angle 60...
Page 36: ...IDU Compact Cassette 4 2 Dimensional Drawings...
Page 38: ...IDU Compact Cassette 6 4 Service Place...
Page 56: ......
Page 115: ...IDU Super Slim Casstte 54 36k 42k 48k 55k...
Page 118: ......
Page 131: ...IDU Duct 7 6 Fan Performance 12K...
Page 132: ...IDU Duct 8 18K...
Page 133: ...IDU Duct 9 24K...
Page 134: ...IDU Duct 10 30K 36K...
Page 135: ...IDU Duct 11 42K 48K...
Page 136: ...IDU Duct 12 55K...
Page 165: ...IDU Duct 41 12k 18k 24k 30k...
Page 166: ...IDU Duct 42 36k 42k 48k 55k...
Page 178: ......
Page 179: ...35mm 1 38in...
Page 180: ......
Page 256: ...IDU Floor Ceiling 82 36k 48k 55k...
Page 259: ......
Page 267: ...Outdoor Unit 3 Panel Plate B30...
Page 268: ...Outdoor Unit 4 Panel Plate BA30...
Page 269: ...Outdoor Unit 5 Panel Plate CA30...
Page 270: ...Outdoor Unit 6 Panel Plate D30...
Page 271: ...Outdoor Unit 7 Panel Plate X230...
Page 272: ...Outdoor Unit 8 Panel Plate X330...
Page 273: ...Outdoor Unit 9 Panel Plate X430...
Page 274: ...Outdoor Unit 10 Panel Plate E30...
Page 275: ...Outdoor Unit 11 Panel Plate 590...
Page 276: ...Outdoor Unit 12 2 Service Place...
Page 285: ...Outdoor Unit 21 UO70Xo UO90Xo UO100Xo UO100Xo3F...
Page 286: ...Outdoor Unit 22 UO120Xo UO140Xo UO160Xo...
Page 291: ......
Page 292: ......
Page 293: ......
Page 294: ......
Page 295: ...Outdoor unit printed circuit board diagram 17122000044714 17122000048121 17122000046453...
Page 297: ...Outdoor unit printed circuit board diagram 17122000048064...
Page 299: ...Outdoor unit printed circuit board diagram 17122000047742 1 3 4 6 8 9 5 7 10 12 11 2 13...
Page 302: ...Outdoor unit printed circuit board diagram 17122000041841...
Page 304: ...Outdoor unit DC motor driver board diagram 17122000021912 5 6 1 2 3 4...
Page 320: ...3 IDU Installation Duct Connector Connector...
Page 352: ...Product Features 13 Remote LCD Screen Indicators...
Page 549: ......
Page 550: ......
Page 551: ......
Page 552: ...email info rotenso com www rotenso com INSTALLER STAMP...