11.
Assembly
44
Rev. D 2013_03_en
44
SM60 series only:
fasten the right and left slider blocks G to the lift
column each with 3 bolts. Then slide the latch
bar into the slider blocks.
Slide on the lift column onto the two cross beam
guides leaving a gap of 1 mm and align precise-
ly with a spirit level (see Fig.43).
5.
Mark the 4 anchoring holes on the floor and for
each lift column and drill (Ø 16 mm,
130 mm deep). Clean the drill holes.
6.
Insert all 16 anchor bolts into the holes. Use a
rubber mallet if necessary.
Approved anchor bolts
Manufacturer Type
Thread
MKT
Anchor bolt BZ plus
M16
MKT
Anchor bolt BZ plus
A4 or HCR
M16
MKT
Injection system
VMZ (chem.)
105/M16
125/M16
145/M16
HILTI
HVZ (chem.)
M16x105
HILTI
Through bolt anchor
HST, HST-R and
HST-HCR
M16
Fischer
Anchor bolt FAZ II
M16
Fischer
High-bond anchor
FHB II (chem.)
M16x95
Würth
FAZ M20
M16
Anchor bolt clamping zone
The clamping zone for these anchor bolts is
the sum of the non-bearing flooring plus the
thickness of the column base plateof 12 mm.
7.
Fit the 4 lift columns onto the shims with ap-
proved nuts and bolt locking devices. Select the
tightening torque according to the bolt manufac-
turer’s specifications. Also consider the on-site
conditions.
DANGER
Risk of fatal injury if lift columns
are not secured properly. Lift or
load could topple or collapse.
Comply with the specified torque on each bolt.
If this is not possible, repair the floor according
to specifications (
Chapter 11.3),
otherwise
commissioning cannot be carried out.
11.11 Attach the latch bars and cables
Proceed as follows on all 4 lift columns.
Series SM40 and SM40 LT:
45
Series SM60
46
i