Modes of Operation
AYC-B7661 Installation Manual
29
In Reader mode, when using Rosslare’s controllers and AxTrax™
software, the unit sends specific messages when failures occur.
The AxTrax™ software can handle the following messages:
•
Fingerprint data reading from card failed
•
Fingerprint reading failed
•
Fingerprint capacitive sensor / card verification failed
6.5
Lockout Mode
The reader enters Lockout mode when there are a number of invalid
card and/or finger reads within a 30-second period. During Lockout
mode, the two LEDs flash red simultaneously for 1 minute. After 1
minute, the reader enters Standby mode.
The default number of invalid reads before the reader enters
Lockout mode is 5. The number of invalid reads can be
programmed to be 1-10.
The default duration of Lockout mode is 1 minute. The duration
can be programmed to be 1-5 minutes.
6.6
Factory Defaults
Upon initial power up, the unit remains in Factory Default mode until
valid Master and Configuration cards are presented.