Reference Manual
00809-0100-4026, Rev FA
July 2009
Rosemount 5400 Series
C-10
Full Tank Handling
With the Full Tank Handling function product levels close to the antenna can
be reported as a
Full Tank
. Normally, measurements are not allowed closer
to the antenna than specified by the
Hold Off Distance
parameter. If the
product level enters the
Hold Off Distance
region, the transmitter reports
Measurement Error
and starts searching for the surface.
By setting the
Level above Hold Off Distance possible
parameter, the
transmitter reports
Full Tank
when the product level enters the
Hold Off
Distance
region. Note that:
• The region where the tank is considered full is specified by the
Full
Tank Detection Area
• The level alarm for Full Tank is normally disabled
Amplitude
Dist
ance
If the product surface
is lost in this region
the transmitter
presents full tank.
Full Tank
Detection
Area
Hold Off
Distance
Summary of Contents for 5401
Page 2: ......
Page 4: ......
Page 10: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series TOC 6 ...
Page 24: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series 2 10 ...
Page 80: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series 5 26 ...
Page 90: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series 6 10 ...
Page 160: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series B 16 ...
Page 174: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series C 14 ...
Page 177: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Index 3 Rosemount 5400 Series ...
Page 178: ...Reference Manual 00809 0100 4026 Rev FA July 2009 Rosemount 5400 Series Index 4 ...
Page 179: ......