Reference Manual
00809-0100-4825, Rev BB
August 2005
Rosemount 248
3-6
Set Output Units
The
Set Output Unit
command sets the desired primary variable units. Set the
transmitter output to one of the following engineering units:
•
Degrees Celsius
•
Degrees Fahrenheit
•
Degrees Rankine
•
Kelvin
•
Ohms
•
Millivolts
50/60 Hz Filter
The
50/60 Hz Filter
command sets the transmitter electronic filter to reject the
frequency of the AC power supply in the plant.
Terminal Temperature
The
Terminal Temp
command sets the terminal temperature units to indicate
the temperature at the transmitter terminals.
Process Variable (PV) Damping
The
PV Damp
command changes the response time of the transmitter to
smooth variations in output readings caused by rapid changes in input.
Determine the appropriate damping setting based on the necessary response
time, signal stability, and other requirements of the loop dynamics of the
system. The default damping value is 5.0 seconds and can be reset to any
value between 0 and 32 seconds.
The value chosen for damping affects the response time of the transmitter.
When set to zero (or disabled), the damping function is off and the transmitter
output reacts to changes in input as quickly as the intermittent sensor
algorithm allows (refer to “Intermittent Threshold” on page 3-12) for a
description of the intermittent sensor algorithm). Increasing the damping value
increases the transmitter response time.
With damping enabled, the transmitter outputs values according to the
following relationship. At time t
Damping Value =
At the time which the damping time constant is set, the transmitter output is at
63% of the input change and it continues to approach the input according to
the damping equation above.
After one damping time constant following a sensor input step change, the
transmitter output will be at 63.2% of that change. The output will continue to
approach the input according to the damping equation above.
Fast Key Sequence
1, 3, 2, 1, 2, 2
Fast Key Sequence
1, 3, 5, 1
Fast Key Sequence
1, 3, 2, 2
Fast Key Sequence
1, 3, 3, 1, 3
P
N
P
–
(
)
1
e
t
–
T
----
–
⎝
⎠
⎜
⎟
⎛
⎞
×
+
P =previous damped value
N =new sensor value
T = damping time constant
U =update rate
Summary of Contents for 248
Page 2: ......
Page 4: ......
Page 46: ...Reference Manual 00809 0100 4825 Rev BB August 2005 Rosemount 248 4 8 ...
Page 64: ...Reference Manual 00809 0100 4825 Rev BB August 2005 Rosemount 248 A 18 ...
Page 74: ...Reference Manual 00809 0100 4825 Rev BB August 2005 Rosemount 248 B 10 ...
Page 77: ...Reference Manual 00809 0100 4825 Rev BB August 2005 0 1 Rosemount 248 NOTES ...
Page 78: ...Reference Manual 00809 0100 4825 Rev BB August 2005 Rosemount 248 0 2 NOTES ...
Page 79: ...Reference Manual 00809 0100 4825 Rev BB August 2005 0 3 Rosemount 248 NOTES ...