Reference Manual
00809-0100-4825, Rev BB
August 2005
2-5
Rosemount 248
Typical North and South
American Installation
Head Mount Transmitter with Threaded Sensor
1.
Attach the thermowell to the pipe or process container wall. Install
and tighten thermowells before applying process pressure.
2.
Attach necessary extension nipples and adapters to the thermowell.
Seal the nipple and adapter threads with silicone tape.
3.
Screw the sensor into the thermowell. Install drain seals if required for
severe environments or to satisfy code requirements.
4.
Pull the sensor wiring leads through the universal head and
transmitter. Mount the transmitter in the universal head by threading
the transmitter mounting screws into the universal head mounting
holes.
5.
Mount the transmitter-sensor assembly into the thermowell. Seal
adapter threads with silicone tape.
6.
Install conduit for field wiring to the conduit entry of the universal
head. Seal conduit threads with silicone tape.
7.
Pull the field wiring leads through the conduit into the universal head.
Attach the sensor and power leads to the transmitter. Avoid contact
with other terminals.
8.
Install and tighten the universal head cover. Enclosure covers must
be fully engaged to meet explosion-proof requirements.
A = Threaded Thermowell
D = Universal Head
B = Threaded Style Sensor
E = Conduit Entry
C = Standard Extension
A
B
C
D
E
Summary of Contents for 248
Page 2: ......
Page 4: ......
Page 46: ...Reference Manual 00809 0100 4825 Rev BB August 2005 Rosemount 248 4 8 ...
Page 64: ...Reference Manual 00809 0100 4825 Rev BB August 2005 Rosemount 248 A 18 ...
Page 74: ...Reference Manual 00809 0100 4825 Rev BB August 2005 Rosemount 248 B 10 ...
Page 77: ...Reference Manual 00809 0100 4825 Rev BB August 2005 0 1 Rosemount 248 NOTES ...
Page 78: ...Reference Manual 00809 0100 4825 Rev BB August 2005 Rosemount 248 0 2 NOTES ...
Page 79: ...Reference Manual 00809 0100 4825 Rev BB August 2005 0 3 Rosemount 248 NOTES ...