Reference Manual
00809-0100-4825, Rev BB
August 2005
3-3
Rosemount 248
375 FIELD
COMMUNICATOR
The HART Communicator exchanges information with the transmitter from
the control room, the instrument site, or any wiring termination point in the
loop. To facilitate communication, connect the HART Communicator in parallel
with the transmitter (see Figure 2-6). Use the loop connection ports on the
rear panel of the HART Communicator. The connections are non-polarized.
Do not make connections to the serial port or the NiCad recharger jack in
explosive atmospheres. Before connecting the HART communicator in an
explosive atmosphere, make sure the instruments in the loop are installed in
accordance with intrinsically safe or non-incendive field wiring practices.
When using a HART Communicator, any configuration changes made must
be sent to the transmitter by using the “Send” key (F2).
For more information regarding the 375 Field Communicator, please see the
375 Field Communicator Reference Manual
(http://www.fieldcommunicator.com/suppmanu.htm).
HART Menu Tree
Options listed in bold type indicate that a selection provides other options. For
ease of operation, changing calibration and setup, such as sensor type,
number of wires, and range values, can be completed in several locations
The review menu lists all of the information stored in the Rosemount 248. This
includes device information, measuring element, output configuration, and software
1. TEST DEVICE
2.
CALIBRATION
3. Write Protect
On-line Menu
1. Snsr 1 Digital Reading
2. Terminal Digital Reading
1. Snsr 1 Input Trim
2. Snsr 1 Trim-Fact
3. Active Calibrator
1. Loop Test
2. Self test
3. Master Reset
4. Status
1. SNSR 1 TRIM
2. D/A trim
3. Scaled D/A trim
1. Revision #s
2. Sensor Review
3. Dev Outputs Review
4. Device Information
5. Measurement Filtering
1. PROCESS
VARIABLES
2. DIAGNOSTICS
AND SERVICE
3. CONFIGURATION
4. REVIEW
1. VARIABLE
MAPPING
2. SENSOR
CONFIGURATION
3. DEVICE OUTPUT
CONFIGURATION
4. DEVICE
INFORMATION
5. MEASUREMENT
FILTERING
1. TRANSMITTER VARS
2. PV is
3. Snsr 1
4. AO
5. % rnge
6. PV LRV
7. PV URV
8. PV LSL
9. PV USL
10.PV Damping
1. DEVICE SETUP
2. PV is
3. PV
4. PV AO
5. % RNGE
6. PV LRV
7. PV URV
1. PV is
2. SV is
3. Variable re-map
1. SENSOR 1
2. TERMINAL TEMP
1. Connections
2. SNSR 1 SETUP
3. Sensor S/N
1. Terminal Units
2. Terminal Damp
3. Terminal LSL
4. Terminal USL
1. PV RANGE
VALUES
2. ALARM/
SATURATION
3. HART OUTPUT
1. AO Alarm Type
2. Low Alarm
3. High Alarm
4. Low Sat.
5. High Sat.
1. Poll Addr
2. Num Req Preams
3. Burst Mode
4. Burst Option
1. Tag
2. Date
3. Descriptor
4. Message
5. Final Assembly number
1. 50/60 Hz Filter
2. Active Calibrator
3. Open Sensor Holdoff
4. Intermit Detect
5. Intermit Thresh
1. 2-wire Offset
2. Snsr 1 Units
3. Snsr 1 Damp
4. Snsr LSL
5. Snsr USL
1. PV LRV
2. PV URV
3. PV Damping
4. PV Units
5. Apply Values
6. PV LSL
7. PV USL
8. Min. Span
These
numbers are
to be entered
by the user.
Summary of Contents for 248
Page 2: ......
Page 4: ......
Page 46: ...Reference Manual 00809 0100 4825 Rev BB August 2005 Rosemount 248 4 8 ...
Page 64: ...Reference Manual 00809 0100 4825 Rev BB August 2005 Rosemount 248 A 18 ...
Page 74: ...Reference Manual 00809 0100 4825 Rev BB August 2005 Rosemount 248 B 10 ...
Page 77: ...Reference Manual 00809 0100 4825 Rev BB August 2005 0 1 Rosemount 248 NOTES ...
Page 78: ...Reference Manual 00809 0100 4825 Rev BB August 2005 Rosemount 248 0 2 NOTES ...
Page 79: ...Reference Manual 00809 0100 4825 Rev BB August 2005 0 3 Rosemount 248 NOTES ...