Unit functions
Page 40
RESM-5
Part 2 of 3: Error messages (warnings)
NOTE:
The specified error messages are initially output as warnings (actual value output jumps back and forth
between two values; alarm output is de-energized). When the "START" signal on the temperature controller is
activated, the warning changes to a fault (actual value output no longer jumps back and forth, see
bold italic
values
; alarm output is energized).
Error
code
Act. val.
output
voltage
[V]
Cause
Action if machine
started for first time
Action if machine
already operating, HS
band not changed
8
104
5.33
10
Current signal incorrect,
incorrect specification of
impulse transformer
Run AUTOCAL
,
check specification of
transformer,
fault areas
Fault areas
(loose contact)
105
Voltage signal incorrect,
incorrect specification of
impulse transformer
106
Voltage and current signals
incorrect,
incorrect specification of
impulse transformer
119
Measurement pause too short
during AUTOCAL
Run AUTOCAL
, don't
start controller
302
Temperature too low,
calibration wasn't performed,
loose contact,
ambient temp. fluctuates
Run AUTOCAL
and / or
fault areas
(loose contact)
303
Temperature too high,
calibration wasn't performed,
loose contact,
ambient temp. fluctuates
9
211
6.00
10
Data error
Run AUTOCAL
Run AUTOCAL