background image

13 

| Automate

 Installation Instructions | DC Power Distribution Panel   

ROLLEASE ACMEDA

If motors powered by the DC Power Distribution Panel are to be used 

with the 

Automate Pulse 2 Hub and Application

, the output voltage of the 

Distribution Panel 

MUST

 be adjusted to allow for proper communication 

between the Hub and Motor.

If motors are connected to the Automate Pulse 2 Hub, it is RECOMMENDED the motors of the same type (MTDCRF28/25 or 
MTDCRF45/35) are used in the installation. It is NOT recommended to power motors of differing types from one DC Power 
Distribution Panel.

Output Voltage (11.4VDC to 15VDC) of the DC Power Distribution Panel 

can be adjusted via the Trim-Pot located on the converter within the 

Distribution Panel.

NOTE: Adjusted Output voltage is applicable to all 18 Channels.

WARNING: DANGEROUS LIVE VOLTAGE. 
DO NOT ATTEMPT UNLESS QUALIFIED TO OPERATE AC MAINS VOLTAGE DEVICES.

Output Voltage of the Distribution Panel must 

be monitored as it is adjusted. This involves 

probing the output of the Panel while it is live. 

Monitor output voltage using a 

multimeter

and adjust potentiometer using an 

appropriately sized Philips Head screwdriver.

When motors are to be controlled via the 

Automate Pulse 2 Hub, the maximum 

allowable voltages for each motor is as shown:

A.1  PULSE 2.0 HUB - ADDITIONAL INSTALLATION/SET UP INSTRUCTIONS

A.2  ADJUSTMENT PROCEDURE

MOTOR

12V

MTDCRF35-3
MTDCRFQ45-3
MTDCRF45-10
MTDCRF-CL-0.6-50
MTDCRF-TILT-1

14V

MTDCRF25-1.1
MTDCRF28-2
MT01-3001-069001

IMPORTANT!

IMPORTANT!

IMPORTANT!

Summary of Contents for AUTOMATE MT03-0301-411005

Page 1: ...wer for up to 18 separate ARC DC motors Higher 15V output allows for greater cable lengths from motor to power panel freeing up routing options within an installation Removes the need for multiple ind...

Page 2: ...Table Maximum Lengths 6 3 2 Motor Power Distribution Setup 7 3 3 Wiring Diagram Individual Connection MTDCRF28 25 8 3 4 Wiring Diagram Two Wire Entry Connections in Parallel MTDCRF45 35 8 3 5 JST Conn...

Page 3: ...t 5 18 Individual fuses for channel protection Quick Blow Fuse 3 15A M205 6 18 Channel Status LEDs 7 Plastic Plugs For cable routing 8 Potentiometer for output voltage adjustment 9 Cooling fan 10 Term...

Page 4: ...ial is clear and protected from moving parts If cable or power connector is damaged do not use MISE EN GARDE Ne pas exposer l humidit ou des environnements extr mes Ne laissez pas les enfants jouer av...

Page 5: ...e s curit importantes lire avant utilisation Pour la s curit des personnes il est important de suivre les instructions fournies Les personnes y compris les enfants dont les capacit s physiques sensori...

Page 6: ...18 AWG 16 AWG N A 18 AWG 18 AWG N A 100m 18 AWG 16 AWG N A 16 AWG 18 AWG N A 105m 18 AWG 16 AWG N A 16 AWG 18 AWG N A 110m 18 AWG 16 AWG N A 16 AWG 18 AWG N A 115m 18 AWG 16 AWG N A 16 AWG 18 AWG N A...

Page 7: ...re power applies to the distribution panel Use of two parallel connections ensures the power supply is not overloaded during larger motor operation OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 OUT...

Page 8: ...d viter de surcharger le circuit d alimentation et d endommager le tableau de distribution Due to 1 33A limit per channel working current can be doubled to 2 66A with parallel configuration as shown...

Page 9: ...que soient en place couvrant les borniers V rifiez que les borniers de connexion du moteur page 2 ne pr sentent pas de fils desserr s ainsi que la polarit connexion voir ci dessous WIRING POLARITY FRO...

Page 10: ...e the appropriate repairs and replace the fuse with a 3 15A M205 quick blow fuse In order to replace fuse carefully pry the fuse out of the plastic cradle using a small tool such as a small screwdrive...

Page 11: ...Power is supplied to panel but exterior LED is not lit Open panel and switch internal power switch to ON position A C terminal block wiring is incorrect CAUTION Do NOT attempt to rewire mains power t...

Page 12: ...OLLEASE ACMEDA APPENDIX CONTENTS A APPENDIX 1 DC POWER DIST PANEL PULSE 2 0 HUB APP A APPENDIX 1 DC POWER DIST PANEL PULSE 2 0 HUB APP 12 A 1 PULSE 2 0 HUB ADDITIONAL INSTALLATION SET UP INSTRUCTIONS...

Page 13: ...ia the Trim Pot located on the converter within the Distribution Panel NOTE Adjusted Output voltage is applicable to all 18 Channels WARNING DANGEROUS LIVE VOLTAGE DO NOT ATTEMPT UNLESS QUALIFIED TO O...

Page 14: ...stribution est connect au secteur 120V 240V Ne pas tenter d panner le panneau sans d abord couper l alimentation et attendre un certain temps de 5 minutes A 3 TROUBLE SHOOTING PROBLEM CAUSE REMEDY Mot...

Page 15: ...15 Automate Installation Instructions DC Power Distribution Panel ROLLEASE ACMEDA A 4 NOTES...

Page 16: ...Broadmeadows VIC 3047 T 61 3 9355 0100 F 61 3 9355 0110 ROLLEASE ACMEDA USA 7th Floor 750 East Main Street Stamford CT 06902 6320 T 1 800 552 5100 F 1 203 964 0513 ROLLEASE ACMEDA EUROPE Via Conca De...

Reviews: