 Installation Instructions | DC Power Distribution Panel   

ROLLEASE ACMEDA

5 TROUBLESHOOTING

WIRE GAUGE DIMENSIONS

IMPORTANT!

WARNING: Distribution panel is connected to (120V/240V) mains power. Do not attempt to troubleshoot panel without first 
disconnecting all power and waiting a period of 5 minutes.
AVERTISSEMENT: le panneau de distribution est connecté au secteur (120V / 240V). Ne pas tenter dépanner le panneau 
sans d’abord couper l’alimentation et attendre un certain temps de 5 minutes.

PROBLEM

CAUSE

REMEDY

No Motors are responding

A/C power supply not plugged in

Check exterior LED

Check Panel to power connection and 

IEC connector and AC plug

Internal power switch turned off

Power is supplied to panel, but 

exterior LED is not lit. Open panel and 

switch internal power switch to ON 

position

A/C terminal block wiring is incorrect

CAUTION: 

Do NOT attempt to rewire 

mains power terminal block. Only to 

be performed by a suitably qualified 

installer

Individual Motor is not 

responding

Motor channel fuse has blown

Check individual LED’s

Replace fuse as necessary (refer to 

section 1.5)

Motor wiring is  incorrect

Refer to wiring diagram on page 6

Motor is in sleep mode

Refer to motor’s programming 

instructions in order to change motor 

sleep status

AMERICAN WIRE GAUGE DIMENSIONS

WIRE GAUGE

DIAMETER

CROSS-SECTIONAL AREA

24 AWG

0.51054 mm (0.0201 in)

0.205 mm

2

 (0.00032 in

2

)

22 AWG

0.64516 mm (0.0254 in)

0.326 mm

2

 (0.00051 in

2

)

20 AWG

0.8128 mm (0.032 in)

0.518 mm

2

 (0.00080 in

2

)

18 AWG

1.02362 mm (0.0403 in)

0.823 mm

2

 (0.00128 in

2

)

16 AWG

1.29032 mm (0.0508 in)

1.31 mm

2

 (0.00203 in

2

)

Summary of Contents for AUTOMATE MT03-0301-411005

Page 1: ...wer for up to 18 separate ARC DC motors Higher 15V output allows for greater cable lengths from motor to power panel freeing up routing options within an installation Removes the need for multiple ind...

Page 2: ...Table Maximum Lengths 6 3 2 Motor Power Distribution Setup 7 3 3 Wiring Diagram Individual Connection MTDCRF28 25 8 3 4 Wiring Diagram Two Wire Entry Connections in Parallel MTDCRF45 35 8 3 5 JST Conn...

Page 3: ...t 5 18 Individual fuses for channel protection Quick Blow Fuse 3 15A M205 6 18 Channel Status LEDs 7 Plastic Plugs For cable routing 8 Potentiometer for output voltage adjustment 9 Cooling fan 10 Term...

Page 4: ...ial is clear and protected from moving parts If cable or power connector is damaged do not use MISE EN GARDE Ne pas exposer l humidit ou des environnements extr mes Ne laissez pas les enfants jouer av...

Page 5: ...e s curit importantes lire avant utilisation Pour la s curit des personnes il est important de suivre les instructions fournies Les personnes y compris les enfants dont les capacit s physiques sensori...

Page 6: ...18 AWG 16 AWG N A 18 AWG 18 AWG N A 100m 18 AWG 16 AWG N A 16 AWG 18 AWG N A 105m 18 AWG 16 AWG N A 16 AWG 18 AWG N A 110m 18 AWG 16 AWG N A 16 AWG 18 AWG N A 115m 18 AWG 16 AWG N A 16 AWG 18 AWG N A...

Page 7: ...re power applies to the distribution panel Use of two parallel connections ensures the power supply is not overloaded during larger motor operation OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 OUT...

Page 8: ...d viter de surcharger le circuit d alimentation et d endommager le tableau de distribution Due to 1 33A limit per channel working current can be doubled to 2 66A with parallel configuration as shown...

Page 9: ...que soient en place couvrant les borniers V rifiez que les borniers de connexion du moteur page 2 ne pr sentent pas de fils desserr s ainsi que la polarit connexion voir ci dessous WIRING POLARITY FRO...

Page 10: ...e the appropriate repairs and replace the fuse with a 3 15A M205 quick blow fuse In order to replace fuse carefully pry the fuse out of the plastic cradle using a small tool such as a small screwdrive...

Page 11: ...Power is supplied to panel but exterior LED is not lit Open panel and switch internal power switch to ON position A C terminal block wiring is incorrect CAUTION Do NOT attempt to rewire mains power t...

Page 12: ...OLLEASE ACMEDA APPENDIX CONTENTS A APPENDIX 1 DC POWER DIST PANEL PULSE 2 0 HUB APP A APPENDIX 1 DC POWER DIST PANEL PULSE 2 0 HUB APP 12 A 1 PULSE 2 0 HUB ADDITIONAL INSTALLATION SET UP INSTRUCTIONS...

Page 13: ...ia the Trim Pot located on the converter within the Distribution Panel NOTE Adjusted Output voltage is applicable to all 18 Channels WARNING DANGEROUS LIVE VOLTAGE DO NOT ATTEMPT UNLESS QUALIFIED TO O...

Page 14: ...stribution est connect au secteur 120V 240V Ne pas tenter d panner le panneau sans d abord couper l alimentation et attendre un certain temps de 5 minutes A 3 TROUBLE SHOOTING PROBLEM CAUSE REMEDY Mot...

Page 15: ...15 Automate Installation Instructions DC Power Distribution Panel ROLLEASE ACMEDA A 4 NOTES...

Page 16: ...Broadmeadows VIC 3047 T 61 3 9355 0100 F 61 3 9355 0110 ROLLEASE ACMEDA USA 7th Floor 750 East Main Street Stamford CT 06902 6320 T 1 800 552 5100 F 1 203 964 0513 ROLLEASE ACMEDA EUROPE Via Conca De...

Reviews: