MCT88M-IO Operating Manual.doc 

  

2019-03-06 

 

18/20 

 

Key 

Parameter defines access key for Desfire file with PCN. 3-KTDES key 
is  24  bytes  (48  HEX  digits),  TDES  and  AES  keys  are  16  bytes  (32 
HEX digits).  

 

Manual addressing 

Manual  addressing  procedure  enables  configuration  of  new  RS485  address  with  all  other  settings 
unchanged. 
 
Manual addressing procedure: 

1.  Remove all connections from A and B lines. 
2.  Place jumper on MEM contacts (fig. 15). 
3.  Restart the device (switch power supply off and on). The terminal will display CONFIG MODE text and 

orange LED SYSTEM will pulsate. 

4.  Enter 3 digits of RS485 address in range of 100-115 with keypad. 
5.  Wait till device starts to emit continuous sound. 
6.  Remove jumper from MEM contacts and restart the device. 

Memory reset procedure 

Memory reset procedure resets all settings to factory default ones including ID=100 address. 
 
Memory reset procedure: 

1.  Remove all connections from A and B lines. 
2.  Place jumper on MEM contacts (fig. 15). 
3.  Restart the device (switch power supply off and on). The terminal will display CONFIG MODE text and 

orange LED SYSTEM will pulsate. 

4.  Read any MIFARE card 11 times. 
5.  Wait till device confirms reset with continuous sound. 
6.  Remove jumper from MEM contacts and restart the device. 

High level configuration (VISO) 

The purpose of high level configuration is to define logical functioning of the terminal which communicates 
with  the  MC16  access  controller  and  it  depends  on  applied  scenario  of  operation. The  example  of  access 
control system configuration is given in AN006 application notes which is available a

www.roger.pl

. 

5.

 

F

IRMWARE UPDATE

 

New firmware can be uploaded to the terminal by means of included memory card. The latest firmware file is 
available a

www.roger.pl

. 

 
Firmware update procedure: 

1.  Disconnect power supply. 
2.  Press and remove memory card from socket (fig. 15). 
3.  Using  memory  card  reader,  copy  main  firmware  (*.frg)  to  the  card  and  rename  it  as  FW.BUF.  Copy 

additional firmware (*.cyacd) for keypad and BLE and rename it as KBDFW.CYA. 

4.  Insert the card into socket. 
5.  Connect  power  supply  and  wait  till  device  completes  starting  procedure.  The  progress  of  additional 

firmware uploading is shown on the display. 

6.  Disconnect power supply when additional firmware KBD is 100% uploaded. 
7.  Connect power supply and wait till device completes starting procedure. 
8.  Start RogerVDM and perform low level configuration. 

Note: During the firmware update process, it is necessary to ensure continuous and stable power supply for 
the device. If interrupted the device may require repair by Roger. 

Summary of Contents for MCT88M-IO

Page 1: ...Roger Access Control System MCT88M IO Operating Manual Product version 1 0 Firmware version 1 0 2 97 or newer Document version Rev A ...

Page 2: ...light Classic DESFire Plus cards reader NFC and BLE mobile device identification Colour graphic display Touch keypad 4 function keys 3 parametric EOL inputs 2 transistor outputs 1 relay output RS485 interface Ethernet LAN interface Dimensions 155 5 x 85 0 21 5 Power supply The terminal requires power supply voltage in range of 11 15VDC It can be supplied from the MC16 access controller e g TML out...

Page 3: ...r tree or any combination of them except for loop The matching resistors terminators connected at the ends of transmitting lines are not required In most cases communication works with any cable type standard telephone cable shielded or unshielded twisted pair etc but the recommended cable is unshielded twisted pair U UTP cat 5 Shielded cables should be limited to installations subject to strong e...

Page 4: ...thin high level configuration VISO e g Set T A Mode Register Guard Tour Event Set Automation Node On etc Within low level configuration RogerVDM of the terminal it is possible configure if terminal distinguishes short and long key pressings Consequently each types of key press can be assigned with different function Display The terminal is equipped with colour display 4 lines 16 characters each Th...

Page 5: ...ge LED indicates card reading and can signal other system functions including device malfunction Note Synchronic pulsing of all three LEDs signifies lost communication with MC16 controller Buzzer The terminal is equipped with buzzer which is used to signal integral functions and it can be additionally programmed with other available functions within high level configuration VISO Inputs The termina...

Page 6: ...OL NO type EOL NO input can be in normal triggered or tamper sabotage state In normal state CA contacts are opened Input triggering is caused by CA contacts closing The change of RTamp resistor measured resistance in normal state indicates the tamper sabotage state Fig 7 EOL NO input type EOL NC type EOL NC input can be in normal triggered or tamper sabotage state In normal state CA contacts are c...

Page 7: ...t triggering is caused by CA contacts opening CTamp contacts opening is recognized as the tamper sabotage state Input shorting to the ground is recognized as the malfunction state Fig 10 2EOL NC input type 3EOL NO type 3EOL NO input can be in normal triggered masking triggered with masking tamper sabotage or malfunction state In normal state CA and CB contacts are opened while CTamp contacts are c...

Page 8: ...er than value of Alarm B resistor at least by three positions in the list above Total resistance of wire used to connect contacts to input should not exceed 100 Ω Default values of parametric resistors Tamp 1 kΩ Alarm A 2 2 kΩ Alarm B 5 6 kΩ Response time Response time parameter defines minimal impulse time on the input which triggers the input Each input can be configured individually in range of...

Page 9: ...ndroid iOS using NFC or Bluetooth BLE communication Prior to use of BLE NFC identification on the terminal within its low level configuration see section 4 configure own NFC BLE authentication factor encryption key and NFC BLE communication encryption key while in case of Bluetooth additionally verify if the parameter BLE activated is enabled Install Roger Mobile Key RMK app on mobile device and c...

Page 10: ...STALLATION Fig 14 Enclosure disassembly Fig 15 Internal side of the front panel Table 3 Screw terminals Screw terminal Description OUT2 OUT2 output line OUT1 OUT1 output line IN3 IN3 input line IN2 IN2 input line IN1 IN1 input line NO REL relay output NO ...

Page 11: ...ont panel regularly by means of wet cloth and mild detergent Do not clean by means of abrasive materials and strong cleaners like alcohols solvents etc Damages to screen surface are beyond the scope of warranty 3 OPERATION SCENARIOS Access T A and building automation terminal The MCT88M IO terminal when connected to MC16 access controller can be at the same time used for access control Time Attend...

Page 12: ...oftware and they can be made available to third party software through RACS 5 Integration Server Assets management terminal The MCT88M IO terminal when connected to virtual controller via Ethernet LAN can be used as terminal for management of assets under control of RACS 5 system Virtual controller is a Windows Service installed on computer by means of RogerSVC software which is available at www r...

Page 13: ...atically display Configuration tab 5 Select RS485 communication interface and specify unoccupied RS485 address in range of 100 115 or select Ethernet communication interface and specify IP address Configure other low level configuration parameters as needed e g NC input type for IN1 input as for diagram in fig 17 6 Click Send to Device to update the configuration of device 7 Optionally make a back...

Page 14: ...l Range 1 REK 2 UCE 3 UCE REK Default value 3 UCE REK Optical signalisation LED SYSTEM pulsing when card near reader Parameter enables LED SYSTEM orange pulsing when card is close to the device Range 0 No 1 Yes Default value 0 No Backlight level Parameter defines backlight level When set to 0 then backlight is disabled Range 0 100 Default value 100 Backlight dimming when card key used Parameter en...

Page 15: ...e elapses the buffer is cleared even if card PIN is not transmitted to controller Range 1 64 Default value 10 AF type Parameter defines authentication factor type returned by terminal Default value 0010 Number 40bits Long card read time s Parameter defines long card read time When set to 0 then long read is disabled Range 0 64 Default value 0 Long key press time s Parameter defines long press time...

Page 16: ...hich will be used to generate returned card number RCN RCN is the actual card number read by reader and it is created as sum of serial card number CSN and programmable card number PCN Programmable card number PCN settings for Mifare Ultralight Sector type Parameter defines sector type with programmable number PCN If the option 0 None is selected then card returned number RCN will include only CSN ...

Page 17: ... 0 2 to for sectors 0 31 and 0 14 for sectors 32 39 Default value 0 Key type Parameter defines key type used to access sector with PCN Range 0 A 1 B Default value 0 A Programmable card number PCN settings for Mifare Desfire Sector type Parameter defines sector type with programmable number PCN If the option 0 None is selected then card returned number RCN will include only CSN and PCN will be disc...

Page 18: ...s sound 6 Remove jumper from MEM contacts and restart the device High level configuration VISO The purpose of high level configuration is to define logical functioning of the terminal which communicates with the MC16 access controller and it depends on applied scenario of operation The example of access control system configuration is given in AN006 application notes which is available at www roge...

Page 19: ... Reading range Up to 7 cm for MIFARE and NFC Up to 10 m for BLE depends on ambient conditions and particular mobile device Terminal s radio power can be increased within low level configuration Distances Up to 1200 m between controller and terminal RS485 IP Code IP41 Environmental class acc to EN 50133 1 Class I indoor general conditions temperature 5 C to 40 C relative humidity 10 to 95 no conden...

Page 20: ... electric and electronic waste For detailed information on recycling contact your local authorities waste disposal company or point of purchase Separate collection and recycling of this type of waste contributes to the protection of the natural resources and is safe to health and the environment Weight of the equipment is specified in the document Contact Roger sp z o o sp k 82 400 Sztum Gościszew...

Reviews: