31
21
30
Pause time for automatic reclosing
00
-
90
SECONDS
92
-
99
from 2 to 9 MINUTES
NOTE: parameter
2-
in simplified mode.
When one of the photocells is obscured the timer is reset and the count restarts upon the return of
the safety protection at pause.
25
03
Phase shift when opening (for motor 2)
00
-
10
SECONDS
26
05
Phase shift when closing (for motor 1)
00
-
30
SECONDS
NOTE: parameter
4-
in simplified mode .
27
03
Time taken to move back after the intervention of the safety edge or the anti-crushing protection
00
-
60
SECONDS
Establishes how many seconds the reversal operation on obstacle lasts; set to a value high enough
to reach the opening limit switch it also performs automatic reclosing according to parameter
49
.
29
01
Electric lock
00
DEACTIVATED
01
ENABLED
The activation starts 0.5 seconds before the start of the operation and lasts for 2 seconds.
30
05
Fine adjustment of the impact forces (combined with par. 31 and 32)
01
-
09
1 = -8%, 2 = -6%, 3 = -4%, 4 = -2%
5 = 0%
6 = +2%, 7 = +4%, 8 = +6%, 9 = +8%
NOTE: increasing / decreasing the parameter increases / decreases the nominal torque of the motors.
31
15
Impact force level motor 1
32
15
Impact force level motor 2
01
-
10
low torque motor : 1 minimum impact force ... 10 maximum impact force
11
-
19
medium torque motor : 11 minimum impact force ... 19 maximum impact force
20
Maximun torque motor : without any adjustment of the anti-crushing protection
NOTE: parameter
9-
and
A-
in simplified mode
In order to fall within the limits of impact forces, usually use the values from
11
to
19
; the check is
to be performed at each installation. The values from
01
to
10
are to be used only in case the values
11-19
are not adequate. The value
20
should be used only in the presence of sensitive edges.
The torque values of low and medium engine can be modified by acting on the parameter
30
.